Model: APC Smart-UPS SRT 1500VA 1350W Tower 120V 15A
Condition: New Batteries, Refurbished UPS
Part Number: SRT1500XLA
Maximum Output: 1350W / 1500VA
Typical Backup Time at Half Load: 13.2 Minutes (675 Watts)
Typical Backup Time at Full Load: 4.6 Minutes (1350 Watts)
Input: NEMA 5-15P, 120V / 15A
Output: (6) NEMA 5-15R
Topology: True Online Double-Conversion
Output Waveform: Sine Wave
Extended Runtime: Supports up to (10) SRT48BP External Battery Packs
Network Management: SmartSlot Available for Optional Network Management Card
Display: Graphical LCD Status & Control Display
Emergency Power Off: EPO Supported
Warranty: 1 Year Full Replacement Warranty
Description: The APC Smart-UPS SRT1500XLA is a 1500VA / 1350W True Online Double-Conversion tower UPS designed for servers, networking equipment, and other critical systems. It delivers sine wave output, built-in bypass, (6) NEMA 5-15R outlets, LCD monitoring, and supports up to (10) SRT48BP external battery packs for extended runtime. Refurbished with new batteries and backed by a 1 Year Full Replacement Warranty.
APC Smart-UPS SRT 1500VA 1350W SRT1500XLA - User Manual
SRT1500XLA - APC Smart-UPS SRT Specifications:
| Main | |||
| Manufacturer | APC | ||
| Product Series | Smart-UPS SRT | ||
| Model | SRT1500XLA | ||
| Product Type | Uninterruptible Power Supply (UPS) | ||
| Power Capacity | 1500VA / 1350W | ||
| UPS Topology | True Online Double-Conversion | ||
| Output Waveform | Sine Wave | ||
| Configuration | Tower | ||
| Mounting Position | Vertical | ||
| Nominal Voltage | 120V | ||
| High-Density Design | Yes | ||
| Built-In Bypass | Yes | ||
| Green Mode | Supported | ||
| Cold Start | Supported | ||
| Generator Compatibility | Yes | ||
| IP Protection | IP20 | ||
| Color | Black | ||
| Condition | New Batteries, Refurbished UPS | ||
| Warranty | 1 Year Full Replacement Warranty | ||
| Input | |||
| Nominal Input Voltage | 120V | ||
|
Input Connection Type |
|
||
| Branch Circuit Rating | 15A | ||
| Input Voltage Range | 90–150V | ||
| Input Frequency | 40–70 Hz Auto-Sensing | ||
| Input Phase | Single-Phase | ||
| Input Cord Length | 6 ft (1.83 m) | ||
| Number of Input Cables | 1 | ||
| Output | |||
| Rated Output Power | 1350W | ||
| Rated Output Capacity | 1500VA | ||
| Maximum Configurable Power | 1350W / 1500VA | ||
| Nominal Output Voltage | 120V | ||
|
Output Connection Type |
|
||
| Total Output Receptacles | 6 | ||
| Output Waveform | Sine Wave | ||
| Output Frequency | 50/60 Hz ±3 Hz Sync to Mains | ||
| Harmonic Distortion | Less than 2% | ||
| Crest Factor | 3:1 | ||
| Built-In Bypass | Yes | ||
| Controllable Outlet Groups | (2) | ||
| Outlet Group Control | On / Off / Shutdown / Reboot / Sleep | ||
| Power Sequencing | Supported | ||
| Load Shedding | Supported | ||
| Batteries & Runtime | |||
| Battery Type | Lead-Acid Battery | ||
| Included Battery Modules | 1 | ||
| Empty Battery Slots | 0 | ||
| Battery Voltage | 48V | ||
| Battery Capacity | 9Ah | ||
| Battery Power | 273 VAh Runtime | ||
| Replacement Battery | APCRBC155 | ||
| RBC Quantity | 1 | ||
| Hot-Swappable Battery | Yes | ||
| User-Replaceable Battery | Yes | ||
| Typical Recharge Time | 3 Hours | ||
| Battery Charging Power | 91W Rated | ||
| Battery Life | 3–5 Years | ||
| Typical Backup Time at Half Load | 13.2 Minutes (675W) | ||
| Typical Backup Time at Full Load | 4.6 Minutes (1350W) | ||
| Extended Runtime | Yes | ||
| Compatible External Battery Pack | SRT48BP | ||
| Maximum External Battery Packs | Up to (10) | ||
| 1 External Battery Pack | 819 VAh | ||
| 2 External Battery Packs | 1365 VAh | ||
| 3 External Battery Packs | 1910 VAh | ||
| 4 External Battery Packs | 2456 VAh | ||
| 5 External Battery Packs | 3002 VAh | ||
| 6 External Battery Packs | 3548 VAh | ||
| 8 External Battery Packs | 4640 VAh | ||
| 10 External Battery Packs | 5731 VAh | ||
| External Battery Detection | Automatic | ||
| Smart Battery Management | Yes | ||
| Battery Health Monitoring | Yes | ||
| Battery End-of-Life Monitoring | Yes | ||
| Communications & Management | |||
| Network Management Card | Not Included | ||
| Network Management Slot | (1) SmartSlot Available | ||
| Free SmartSlot | 1 | ||
| Optional Network Management | Supported | ||
| Web / SNMP Management | Supported with Compatible Network Management Card | ||
| Remote UPS Monitoring | Supported with Compatible Management Interface | ||
| Remote UPS Management | Supported with Compatible Network Management Card | ||
| Environmental Monitoring | Supported with Compatible Network Management Card / Sensor | ||
| USB Port | Yes | ||
| Serial Port | Yes | ||
| Serial Interface | DB9 RS-232 | ||
| Communication Interfaces | USB, RS-232, SmartSlot, EPO | ||
| Emergency Power Off | Yes | ||
| Power Management Software | PowerChute / APC Power Management Software Compatible | ||
| Monitoring | Load, Battery, Voltage and Alarms | ||
| Firmware Upgrade Support | Yes | ||
| User Interface, Alerts & Controls | |||
| Front Panel Display | Multifunction Graphical LCD | ||
| LCD Status Display | Yes | ||
| Front Panel Indicators | Online, Battery, Bypass, Fault, Overload and Battery Status | ||
| UPS Status Monitoring | Yes | ||
| Input Voltage Monitoring | Yes | ||
| Output Voltage Monitoring | Yes | ||
| Output Frequency Monitoring | Yes | ||
| Load Monitoring | Yes | ||
| Battery Status Monitoring | Yes | ||
| Runtime Monitoring | Yes | ||
| Controls | Power On/Off, Menu Navigation, Alarm Control and Self-Test | ||
| Audible Alarm | Yes | ||
| Battery Operation Alarm | Yes | ||
| Low Battery Alarm | Yes | ||
| Overload Alarm | Yes | ||
| Fault / System Event Alarm | Yes | ||
| Alarm Management | Supported | ||
| Event Monitoring | Supported | ||
| Self-Test | Supported | ||
| Operating Modes | |||
| Online Double-Conversion Mode | Yes | ||
| Battery Mode | Yes | ||
| Bypass Mode | Yes | ||
| Green Mode | Yes | ||
| Cold Start / Start on Battery | Yes | ||
| Automatic Bypass | Supported | ||
| Manual Bypass Control | Supported | ||
| Power Management Features | |||
| Controllable Outlet Groups | (2) | ||
| Delayed Power On | Configurable | ||
| Delayed Power Off | Configurable | ||
| Reboot Control | Supported | ||
| Reboot Duration | Configurable | ||
| Power Sequencing | Supported | ||
| Minimum Return Runtime | Configurable | ||
| Load Shedding on Battery | Supported | ||
| Load Shedding by Runtime | Supported | ||
| Load Shedding on Overload | Supported | ||
| Automatic Restart | Supported | ||
| Energy Monitoring | Supported | ||
| Power Protection Features | |||
| Blackout Protection | Yes | ||
| Brownout Protection | Yes | ||
| Voltage Sag Protection | Yes | ||
| Surge Protection | Yes | ||
| Voltage Fluctuation Protection | Yes | ||
| Frequency Variation Protection | Yes | ||
| Double-Conversion Power Conditioning | Yes | ||
| Built-In Bypass | Yes | ||
| Emergency Power Off | Yes | ||
| Physical | |||
| Form Factor | Tower | ||
| Mounting Position | Vertical | ||
| Rackmount Conversion | Rack-Mounted with Optional Kit | ||
| Height | 17.01 in (43.2 cm) | ||
| Width | 3.35 in (8.5 cm) | ||
| Depth | 20.00 in (50.8 cm) | ||
| Net Weight | 48.50 lb (22 kg) | ||
| Color | Black | ||
| USB Compatible | Yes | ||
| Environmental | |||
| Operating Temperature | 32–104°F (0–40°C) | ||
| Storage Temperature | -4–122°F (-20–50°C) | ||
| Operating Altitude | 0–10,000 ft | ||
| Storage Altitude | 0–50,000 ft (0–15,240 m) | ||
| Relative Humidity | 0–95%, Non-Condensing | ||
| Storage Relative Humidity | 0–95%, Non-Condensing | ||
| Acoustic Level | 50 dBA | ||
| Heat Dissipation | 463 BTU/hr | ||
| IP Degree of Protection | IP20 | ||
| Surge Protection & Filtering | |||
| Surge Protection | Yes | ||
| Surge Energy Rating | 432 J | ||
| Online Power Conditioning | Yes | ||
| Sine Wave Output | Yes | ||
| Conformance | |||
| Product Certification | ENERGY STAR V2.0 (USA) | ||
| Condition & Warranty | |||
| UPS Condition | Refurbished | ||
| Battery Condition | New Batteries | ||
| Replacement Battery | APCRBC155 | ||
| Network Management Card | Not Included | ||
| Warranty | 1 Year Full Replacement Warranty |