ES3000 Digital Three-wire Ground Resistance Tester Digital Earth Resistance Meter

 

Main Feature

FunctionGround resistance measurement, ground voltage measurement, low value resistance measurement

Resistance range0.01Ω~3000Ω

Voltage range0100V AC

Measure modePrecision three-wire measurement, simple two-wire measurement (sine wave)

USB interfaceWith USB interface, software monitoring, storage data can upload computer, save and print

Data storage500 groups

 

Product Description

 ES3000 digital grounding resistance tester, also known as the three-wire grounding resistance tester, grounding resistance meter, etc., is a commonly used instrument for measuring common grounding resistance meters.It uses a large LCD gray screen backlight display and microprocessor technology to meet the two-wire, three-wire test resistance requirements.Suitable for telecommunications, electricity, meteorology, computer rooms, oil fields, power distribution lines, iron tower transmission lines, gas stations, factory grounding networks, lightning rods and so on.The instrument has the characteristics of precise, fast, simple, stable and reliable.

Main Feature

 

Technical Data

Grounding resistance range0.01Ω~3000Ω

Accuracy:±1.5%rdg±3dgt

Grounding resistance resolution0.01Ω

Grounding voltage range0100V AC

Accuracy:±1.5%rdg±3dgt

Grounding voltage resolution0.01V

Base condition:23℃±5℃,below 75%rh (Auxiliary grounding resistance 100Ω±5%voltage to ground10V)

Function:Ground resistance measurement, ground voltage measurement, low value resistance measurement

Power:DC 6V 4.5AhLead-acid battery, standby for more than 100 hours

Backlight:Controllable gray screen backlight, suitable for use in dim places

Measuring mode:Precise three-wire measurement, simple two-wire measurement

Measuring methods:Grounding resistance: rated current change pole method, 128Hz;

Ground Voltage: Average Rectification

Test frequency:128Hz

Short-circuit test current:> 20mA ( sine wave)

Wire resistance check:Avoid the errors cause of the test line is not fully inserted into the instrument interface or the contactor is incorrectly replaced or the user replaces the extended test lead, to make the ground resistance test more accurate

Display mode:4-bit large LCD display, gray screen backlight

Measurement instructions:LED flashing indicator during measurement, LCD countdown display

LCD size:108mm×65mm

Instrument size:L/W/H277.2mm×227.5mm×153mm

Test line length:3 stripsred 15myellow 10mgreen 5m each one

Simple test line:2 stripsyellow 1.6mgreen 1.6m each one

Auxiliary grounding rod:2PCS:φ10mm×200mm

Measure time:Ground voltage: about 3 times/sec; grounding resistance: about 5 seconds/time

Measurement times:More than 5000 times

Line voltage:Measuring voltage to ground: test below AC 100V

USB interface:With USB interface, software monitoring, storage data can be uploaded to the computer, save and print

Communication line:One USB communication line, 1.5m long

Data storage:500 groups, "MEM" storage instructions, display "FULL" symbol indicates that the storage is full

Data review:Data review function: "MR" symbol display

Overflow display:Over-range overflow function: "OL" symbol display

Alarm function:Alarm when the measured value exceeds the alarm setting value

Battery voltage:Real-time display of battery power, reminding timely charging when battery voltage is low

Automatic shut-down:"APO" indicates automatic shutdown after 15 minutes

Power consumption:Standby: 40mA Max (backlight off)

Turn on backlight: 43mA Max

Measurement: 120mA Max (backlight off)

Weight:Instrument: 2397g (with battery)

Test line: 850g (including simple test line)

Auxiliary grounding rods: 425g (2)

Instrument bag: 271g

Working temperature and humidity:-10℃~40℃;below 80%rh

Storage temperature and humidity:-20℃~60℃;below 70%rh

Overload protection:Grounding resistance: AC 280V/3 seconds between E-H and E-S ports

Insulation resistance:Above 10MΩ (500V between circuit and case)

Pressure resistance:AC 3700V/rms(between circuit and case)

Electromagnetic properties:IEC61010-4-3Wireless frequency electromagnetic field1V/m

Suitable for safety regulations

IEC61010-1IEC1010-2-31IEC61557-1,5IEC60529(IP54)pollution level 2CAT 300V