Waterproof NRC-150 Series Rogowski Coil Current Transformers (IP67) for Smart Grid Harmonic Monitoring
Ø8 screw type flexible Rogowski coil
* Excellent linearity
* Wide dynamic range
* Not damaged by large overloads
* Excellent degree of rejection to the external current conductor
* No danger from open-circuited secondary
* Zero power consumption
* Small position error
* Soft and light, easy to install
* Long-term stability
* Wide dynamic range
* IP68 protection level
|
MODEL
|
NRC-100
|
NRC-150
|
NRC-200
|
|
Coil length
|
395mm
|
525mm
|
665mm
|
|
Window size
|
100mm
|
150mm
|
200mm
|
|
Reference
Rated current |
1000A
|
3000A
|
6000A
|
|
Ratio
|
Calibrated:85±0.5mV/kA@50Hz
100±0.5mV/kA@50Hz |
||
|
Uncalibrated:105±5mV/kA@50Hz
|
|||
|
Reference Rated current
|
100A,600A,3000A,6000A...(Unlimited)
|
|
|
Ratio @50Hz
|
Calibrated
(Manufacturing tolerance<0.5%) |
...
22.5mV/kA 50mV/kA 85mV/kA 100mV/kA ... |
|
Sensitivity temperature drift coefficient
|
Uncalibrated, <50ppm/℃
|
|
|
Calibrated, <100ppm/℃
|
||
|
Internal resistance temperature drift coefficient1)
|
Uncalibrated, <3800ppm/℃
|
|
|
Read Accuracy
|
0.5%class (Vertically centered position)
|
|
|
Internal resistance
|
50~250 Ω
|
|
|
Position Error 2)
|
<1%
|
|
|
Output on 0A (zero drift)
|
<0.05mV
|
|
|
Phase error
|
<0.5°(45Hz~65Hz)
|
|
|
Linearity
|
±0.1% (1%~100%)
|
|
|
Bandwidth(3dB)
|
1Hz~20kHz
|
|
|
Operating temperature
|
-40℃~85℃
|
|
|
Coil Section
|
8mm
|
|
|
Lead length(default)
|
2 meter
|
|
|
For other requirements, please contact us for customization.
|
||