| Signal type | Voltage |
| Signal type (voltage) | 24 VDC |
| Supply voltage (system) | 5 VDC; via data contacts |
| Supply voltage (field) | 24 VDC (-25 … +30 %); via power jumper contacts (power supply via CAGE CLAMP® connection; transmission (field-side supply voltage only) via spring contact |
| Current consumption (system supply) | 5mA |
| Current carrying capacity (power jumper contacts) | 6.3A |
| Number of outgoing power jumper contacts | 3 |
| Fuse | 5 x 20; T 6.3 A (not included) |
| Diagnostics | Supply voltage (field): Detection “on” at > 15 VDC; Detection “off” at < 5 VDC |
| Data width | 2 bits (1 bit current monitoring, 1 bit fuse fault) |
| Indicators | LED (A) red: defective fuse error; LED (B) green: power supply status |