Features
Individually addressed and controlled multi-candela TrueAlert ES
A/V (audible/visible) notification appliances provide:
• Multi-candela xenon strobe with synchronized 1 Hz flash rate and
with intensity programmable from the FACU or jumper selected as 15
cd, 30 cd, 75 cd, or 110 cd on the AV model, or 110 cd, 135 cd, or 185
cd on the AVH model
• Advanced addressable notification controlled by IDNAC SLCs.
• IDNAC SLCs provide regulated 29 VDC allowing horns to operate with
lower current
• Wiring supervision to each appliance allowing “T-tapped” connections
for Class B circuits to simplify wiring. Class A circuits require in/out
wiring.
• Self-Test Mode allows on-board sensors to detect the strobe and
horn output and then report their status to the FACU
• TrueAlert Device Reports at the FACU detailing appliance point ID,
custom label, type, and candela setting, see sample in TrueAlert
Device Reports Reference
• Magnet Test diagnostics to assist checkout and testing of appliances
and wiring
• Electrical test point access by removing the cover
• Compatibility with ADA requirements; see Installation Reference for
important installation information
• Compatibility with legacy TrueAlert addressable systems for upgrade
and replacement, see TrueAlert ES A/V LEGACY Compatibility
Reference
• Strobe operation is listed to UL Standard 1971 and ULC Standard
S526; Horn operation is listed to UL Standard 464 and ULC Standard
S525
LED indicator and magnet test feature:
• Appliance LED can be selected to display each polling cycle to
indicate appliance supervision
• When the controller is in diagnostic mode, the Magnet Test pulses
the LED to indicate appliance address and can be set to also briefly
flash the strobe and sound the horn
Mechanical design features
• Rugged, high impact, flame retardant thermoplastic housing in red
with white letters or white with red letters, with clear lens, available
with FIRE, FEU, ALERT, FEU/FIRE, FUEGO/FOGO, or blank lettering
• Separate covers are available to change application type onsite or for
replacement
• You can use a back box to mount the appliance assembly to the wall.
Mount to a 4 in. (10.16 cm) square electrical box
• Covers can be easily removed without disturbing the connected
housing and avoiding trouble conditions
• In/out wiring terminals for 18 AWG to 12 AWG
• Optional red wire guards, see Product Selection
Audible notification appliance (horn):
• Harmonically rich output sound for either coded or steady operation
• Horns sound as Temporal Code 3, March Time pattern, continuous;
or Temporal Code 4, controlled separately from visible appliances on
the same two-wire circuit
• Selectable March Time rates of 20, 60, or 120 beats per minute
• Output is “high” or “low” (~5 dBA difference) selectable at the
appliance or from the controller with FACU mode selected at the
appliance