Edwards SIGA-OSD Smoke Detector (Replaces SIGA-PD)

Edwards SIGA-OSD (also written SIGA OSD) — a Signature Optica Series intelligent optical (photoelectric) smoke detector that reports analog sensor data digitally to a Signature loop controller. It supersedes the SIGA-PD.

The SIGA-OSD gathers analog information from multiple optical sensors and converts it to digital signals. Using dual optical wavelengths combined with multiple detection angles, it differentiates particles that are not representative of actual smoke; particle data feeds digital filters and a series of ratios that remove signal patterns typical of nuisance sources, reducing unwanted alarms. The on-board microprocessor measures and analyzes all optical sensor readings and compares them against preprogrammed settings to make the alarm decision. Continuous self-diagnostics and a permanently stored history log in non-volatile memory support maintenance, and automatic device mapping lets the loop controller supervise each device’s installed position so a detector cannot be returned to the wrong location after cleaning.

The detector head ships on its own. A mounting base is a separate catalog number and must be ordered to suit the application — standard, relay, fault-isolator, or audible/sounder.

Specifications

Operating voltage 15.20 to 19.95 VDC
Normal operating current 32 µA
Alarm current 45 µA
Smoke sensitivity range UL/ULC: 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m) obscuration
Air velocity 0 to 4,000 ft./min (0 to 20 m/s)
Vibration level 10 to 35 Hz, amplitude 0.01 in.
Wall mounting 12 in. (305 mm) max. from ceiling
Operating environment 32 to 120°F (0 to 49°C), 0 to 93% RH, noncondensing
Storage temperature -4 to 140°F (-20 to 60°C)
Environmental compensation Automatic
Construction High impact engineering polymer, white
Status LED Bicolor (green/red)
Compatible detector testers Testifire 1000, Testifire 2000
Agency certifications CAN/ULC-S529, UL 268-7, UL 268A, CSFM (7272-1657:0511)
Ship weight 0.4 lb (0.16 kg)

Installation notes

Related models

Replacement and compatibility

The SIGA-OSD supersedes the Edwards SIGA-PD, which uses a single optical sensor rather than dual wavelengths and multiple detection angles. It works only with control panels that use a Signature loop controller. The detector head ships alone; choose a standard base such as the SIGA-SB4, or a relay, isolator or audible base.

FAQ

Does the SIGA-OSD come with a base?
No. The mounting base is a separate catalog number.

How many Signature addresses per loop?
Up to 250 total Signature addresses per loop.

Specifications taken from the Edwards data sheet “Intelligent Smoke Detector — SIGA-OSD,” document E85001-1001, Issue 1.5. Manufacturer specifications are subject to change without notice.

Brand new in original packaging. Ships same business day from Atlanta, GA when ordered by 3 PM ET. 30-day returns. 1-year warranty.