Edwards SIGA-OSD (also written SIGA OSD) — a Signature Optica Series intelligent optical (photoelectric) smoke detector that reports analog sensor data digitally to a Signature loop controller. It supersedes the SIGA-PD.
The SIGA-OSD gathers analog information from multiple optical sensors and converts it to digital signals. Using dual optical wavelengths combined with multiple detection angles, it differentiates particles that are not representative of actual smoke; particle data feeds digital filters and a series of ratios that remove signal patterns typical of nuisance sources, reducing unwanted alarms. The on-board microprocessor measures and analyzes all optical sensor readings and compares them against preprogrammed settings to make the alarm decision. Continuous self-diagnostics and a permanently stored history log in non-volatile memory support maintenance, and automatic device mapping lets the loop controller supervise each device’s installed position so a detector cannot be returned to the wrong location after cleaning.
The detector head ships on its own. A mounting base is a separate catalog number and must be ordered to suit the application — standard, relay, fault-isolator, or audible/sounder.
| Operating voltage | 15.20 to 19.95 VDC |
| Normal operating current | 32 µA |
| Alarm current | 45 µA |
| Smoke sensitivity range | UL/ULC: 0.5 to 4.36 %/ft. (1.6 to 13.6 %/m) obscuration |
| Air velocity | 0 to 4,000 ft./min (0 to 20 m/s) |
| Vibration level | 10 to 35 Hz, amplitude 0.01 in. |
| Wall mounting | 12 in. (305 mm) max. from ceiling |
| Operating environment | 32 to 120°F (0 to 49°C), 0 to 93% RH, noncondensing |
| Storage temperature | -4 to 140°F (-20 to 60°C) |
| Environmental compensation | Automatic |
| Construction | High impact engineering polymer, white |
| Status LED | Bicolor (green/red) |
| Compatible detector testers | Testifire 1000, Testifire 2000 |
| Agency certifications | CAN/ULC-S529, UL 268-7, UL 268A, CSFM (7272-1657:0511) |
| Ship weight | 0.4 lb (0.16 kg) |
The SIGA-OSD supersedes the Edwards SIGA-PD, which uses a single optical sensor rather than dual wavelengths and multiple detection angles. It works only with control panels that use a Signature loop controller. The detector head ships alone; choose a standard base such as the SIGA-SB4, or a relay, isolator or audible base.
Does the SIGA-OSD come with a base?
No. The mounting base is a separate catalog number.
How many Signature addresses per loop?
Up to 250 total Signature addresses per loop.
Specifications taken from the Edwards data sheet “Intelligent Smoke Detector — SIGA-OSD,” document E85001-1001, Issue 1.5. Manufacturer specifications are subject to change without notice.
Brand new in original packaging. Ships same business day from Atlanta, GA when ordered by 3 PM ET. 30-day returns. 1-year warranty.