*********ALL IMPORT AND CUSTOMS DUTIES ARE THE BUYER'S RESPONSIBILITY********
Ordering
Minimum Order Quantity:
1 piece
Customs Tariff Number:
85362010
Popular Downloads
Data Sheet, Technical Information:
Data sheet - Manual Motor Starter MS116
Instructions and Manuals:
Installation instructions - Manual Motor Starter MS116
Instructions and Manuals (Part 2):
Manual Motor Starter Guide
Time-Current Characteristic Curve:
Tripping characteristic - Manual Motor Starter MS116-2.5 valid for production date from week 34/2014
I²t Characteristic:
I2t - Characteristic @ 400V - Manual Motor Starter MS116
I2t - Characteristic @ 500V - Manual Motor Starter MS116
I2t - Characteristic @ 690V - Manual Motor Starter MS116
Cut-off Current Characteristic:
Cut-off Current Characteristic @ 400V -Manual Motor Starter MS116
Cut-off Current Characteristic @ 500V -Manual Motor Starter MS116
Cut-off Current Characteristic @ 690V -Manual Motor Starter MS116
CAD Dimensional Drawing:
Information - 2D and 3D files for CAD systems
Dimension Diagram:
Dimension Drawing - MS116 (<20A) + HKF1 Manual Motor Starter
Dimensions
Product Net Width:
45 mm
Product Net Height:
90 mm
Product Net Depth / Length:
85.6 mm
Product Net Weight:
0.265 kg
Technical
Rated Service Short-Circuit Breaking Capacity (I
cs
):
(230 V AC) 50 kA
(400 V AC) 50 kA
(440 V AC) 10 kA
(500 V AC) 10 kA
(690 V AC) 5 kA
Rated Ultimate Short-Circuit Breaking Capacity (I
cu
):
(230 V AC) 75 kA
(400 V AC) 75 kA
(440 V AC) 30 kA
(500 V AC) 20 kA
(690 V AC) 10 kA
Rated Instantaneous Short-Circuit Current Setting (I
i
):
31.3 A
Setting Range:
1.6 ... 2.5 A
Rated Operational Power AC-3 (P
e
):
(400 V) Three Phase 0.75 kW
Rated Operational Power AC-3e (P
e
):
(400 V) Three Phase 0.75 kW
Rated Operational Voltage:
Main Circuit 690 V AC
Rated Operational Current (I
e
):
2.5 A
Rated Operational Current AC-3 (I
e
):
2.5 A
Rated Operational Current AC-3e (I
e
):
2.5 A
Rated Frequency (f):
Main Circuit 50 Hz
Main Circuit 60 Hz
Rated Impulse Withstand Voltage (U
imp
):
Main Circuit 6 kV
Rated Insulation Voltage (U
i
):
690 V
Power Loss:
at Rated Operating Conditions per Pole 0.7 ... 1.8 W
Number of Poles:
3P
Conventional Free-air Thermal Current (I
th
):
Main Circuit 2.5 A
Degree of Protection:
Housing IP20
Main Circuit Terminals IP10
Pollution Degree:
3
Electrical Durability:
100000 cycle
Mechanical Durability:
100000 cycle
Terminal Type:
Screw Terminals
Connecting Capacity Main Circuit:
Flexible with Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible with Insulated Ferrule 1/2x 0.75 ... 2.5 mm²
Flexible 1/2x 0.75 ... 2.5 mm²
Rigid 1/2x 1 ... 4 mm²
Tightening Torque:
Main Circuit 0.8 ... 1.2 N·m
Wire Stripping Length:
Main Circuit 9 mm
Recommended Screw Driver:
Pozidriv 2
Mounting Position:
1 ... 6
any
Mounting on DIN Rail:
TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715
TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
Minimum Mounting Distance:
Electrical Conductive Board, Horizontal - Up to 400 V 0 mm
Electrical Conductive Board, Horizontal - Up to 690 V 1.5 mm
Electrical Conductive Board, Vertical 75 mm
Other Device Same Type, Horizontal 0 mm
Other Device Same Type, Vertical 150 mm
Actuator Type:
Rotary Handle
Contact Position Indication:
ON / OFF
Standards:
IEC/EN 60947-1
IEC/EN 60947-2
IEC/EN 60947-4-1
UL 60947-1
UL 60947-4-1
IEC 60335-2-40 A2L
Technical UL/CSA
Short-Circuit Current Rating (SCCR):
Any UL Listed Fuses or Circuit-Breakers, Group Installations (480 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Group Installations (600 V AC) 5 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (480 V AC) 30 kA
Any UL Listed Fuses or Circuit-Breakers, Motor Disconnect (600 V AC) 5 kA
Maximum Operating Voltage UL/CSA:
Main Circuit 600 V AC
Horsepower Rating UL/CSA:
(200 V AC) Three Phase 0.5 Hp
(208 V AC) Three Phase 0.5 Hp
(220 ... 240 V AC) Three Phase 0.5 Hp
(440 ... 480 V AC) Three Phase 1 Hp
(550 ... 600 V AC) Three Phase 1.5 Hp
Full Load Amps Motor Use:
(200 V AC) Three Phase 2.5 A
(208 V AC) Three Phase 2.5 A
(220 ... 240 V AC) Three Phase 2.5 A
(440 ... 480 V AC) Three Phase 2.5 A
(550 ... 600 V AC) Three Phase 2.5 A
Locked Rotor Amps:
(200 V AC) Three Phase 15 A
(208 V AC) Three Phase 15 A
(220 ... 240 V AC) Three Phase 15 A
(440 ... 480 V AC) Three Phase 15 A
(550 ... 600 V AC) Three Phase 15 A
General Use Rating UL/CSA:
(600 V AC) 2.5 A
Connecting Capacity Main Circuit UL/CSA:
Flexible 1/2x 16-12 AWG
Stranded 1/2x 16-12 AWG
Tightening Torque UL/CSA:
Main Circuit 10 in·lb
Environmental
Ambient Air Temperature:
Around the Enclosure 0 ... +40 °C
Operation -25 ... +70 °C
Operation Compensated -25 ... +55 °C
Storage -50 ... +80 °C
Ambient Air Temperature Compensation:
Yes
Maximum Operating Altitude Permissible:
2000 m
Resistance to Shock acc. to IEC 60068-2-27:
11 ms Pulse 25g
Resistance to Vibrations:
2g 5 ... 150 Hz
5g 3 ... 150 Hz
Material Compliance
Conflict Minerals Reporting Template (CMRT):
CMRT - Conflict Minerals Reporting Template
REACH Declaration:
REACh Declaration for all Manual Motor Starters
RoHS Information:
RoHS II Declaration for all Manual Motor Starters
RoHS Status:
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
Toxic Substances Control Act - TSCA:
Toxic Substances Control Act (TSCA) declaration for Manual Motor starters
WEEE B2C / B2B:
Business To Business
WEEE Category:
5. Small Equipment (No External Dimension More Than 50 cm)
ABB EcoSolutions
End Of Life Disassembling Instructions:
End of life instruction MS116
Environmental Product Declaration - EPD:
Environmental Product Declaration PEP MS116 (DE)
Environmental Product Declaration PEP MS116 (CN)
Certificates and Declarations
A2L Certificate – IEC:
A2L Certificate - MS132, MO132, MS116 series, HK1, HKF1, SK1, CK1 - Manual Motor Starter
ABS Certificate:
ABS Certificate - MS116, HK1, HKF1,SK1, UA1, UA1-HK, AA1 - Manual Motor Starter
BV Certificate:
BV Certificate - MS116, HK1, HKF1,SK1, UA1, UA1-HK, AA1 - Manual Motor Starters
CB Certificate:
CB Certificate - MS116 - Manual Motor Starters - DE
CB Certificate - MS116- Manual Motor Starters - CN
CCC Certificate:
CCC Certificate, Motor protection circuit breaker, MS116, MS2X, Made in China
CCC Certificate, Motor protection circuit breaker, MS116, Made in Germany
CQC Certificate:
CQC2011010307506570
CQC Certificate, Motor protection circuit breaker, MS116, MS2X, Made in China
Cut-off Current Characteristic:
Cut-off Current Characteristic @ 400V -Manual Motor Starter MS116
Cut-off Current Characteristic @ 500V -Manual Motor Starter MS116
Cut-off Current Characteristic @ 690V -Manual Motor Starter MS116
Declaration of Conformity - CCC:
2020980307003705
CCC Declaration of Conformity, Motor protection circuit breaker, MS116, MS2X, Made in China
Declaration of Conformity - CE:
EU Declaration of Conformity - MS116-x - Manual Motor Starter
Declaration of Conformity - UKCA:
UK Declaration of Conformity - MS116-x - Manual Motor Starter
DNV Certificate:
DNV Certificate - MS116 - Manual Motor Starter
DNV GL Certificate:
DNV Certificate - MS116 - Manual Motor Starter
EAC Certificate:
EAC Certificate - MS116, MS132, MO132, MS165, MO165, HKF1-11 - Manual Motor Starters
GL Certificate:
1SAA963000-0402
I²t Characteristic:
I2t - Characteristic @ 400V - Manual Motor Starter MS116
I2t - Characteristic @ 500V - Manual Motor Starter MS116
I2t - Characteristic @ 690V - Manual Motor Starter MS116
KC Certificate:
KC Certificate MS116
LR Certificate:
LR Certificate - MS116, HK1, HKF1,SK1, UA1, UA1-HK, AA1 - Manual Motor Starters
RMRS Certificate:
RMRS Certificate - MS116, MS132, MO132, MS165, MO165, MS225, MS325, MO325, MS450, MS451, MS495, MS496, MS497 - Manual Motor Starters
UL Certificate:
UL Certificate of Compliance - MS116, HK1, HKF1, SK1, CK1, AA1, UA1 - Manual Motor Starters
Container Information
Package Level 1 Units:
box 1 piece
Package Level 1 Width:
92 mm
Package Level 1 Depth / Length:
95 mm
Package Level 1 Height:
50 mm
Package Level 1 Gross Weight:
0.28 kg
Package Level 1 EAN:
4013614320309
Package Level 2 Units:
carton 40 piece
Package Level 2 Width:
280 mm
Package Level 2 Depth / Length:
395 mm
Package Level 2 Height:
210 mm
Package Level 2 Gross Weight:
11.586 kg
Package Level 2 EAN:
4013614408670
External Classifications and Standards
Object Classification Code:
F
ETIM 4:
EC000074 - Motor protective circuit-breaker
ETIM 5:
EC000074 - Motor protective circuit-breaker
ETIM 6:
EC000074 - Motor protection circuit-breaker
ETIM 7:
EC000074 - Motor protection circuit-breaker
ETIM 8:
EC000074 - Motor protection circuit-breaker
eClass:
V11.0 : 27370401
UNSPSC:
39121521
IDEA Granular Category Code (IGCC):
4731 >> Manual Starters
E-Number (Finland):
3706007
E-Number (Norway):
4364273
E-Number (Sweden):
3111942