MEBAY ATS520IR Auto Diesel Generator Controller Dual Power Switch ATS Control Module LCD Intelligent programmable Panel RS485
Summary
This series of controllers is a dual power switching controller, which has programmable function, automatic measurement and control, LCD display of dual power intelligent switching module.
This controller uses 3.5 inch 240*128 large screen high resolution LCD display, a completely new and original UI design.Controller built-in Simplified Chinese, English and other display interfaces can be selected, and language interface can be customized according to customer requirements. All parameters of the controller can be adjusted by keys on the controller panel, or adjusted and monitored by PC through USB port or RS485 interface. It can be widely used in various types of power systems.
The ATS520 series has four models:
ATS520: Dual power intelligent switching module;
ATS520I: On the basis of ATS520, the electric energy measurement function is added.
ATS520R: RS485 port is added on the basis of ATS520.
ATS520IR: On the basis of ATS520, power measurement and RS485 port are added.
Main Features
32 units Micro-procession technology is used.
3.5-inch 240*128 large screen high resolution liquid crystal display, with Chinese and English switchable, customized language according to customer needs;
Acrylic material is adapted to protect the screen.
With USB interface, the parameters can be set through USB interface to monitor real-time, and the parameters can be set when the controller does not turn on the power supply.
With RS485 communication port, can achieve “Three Remote” functions via MODBUS protocol.
S1/S2 has independent over-current warning function and trip warning function.
Detect and display power generation, municipal power, phase and other parameters;
S1/S2 accumulative active power, accumulative reactive power and accumulative closing times are displayed.
Automatic/manual state switching. In manual mode, the switch can be forced to close/open.
Two generators can be controlled to realize cycle operation, main operation and balanced time operation.
Adapt to 3P4W,3P3W,1P2W,2P3W(120V/240V,50/60HZ)
Input and output port status display;
Real time clock inside: preset time operate and auto maintenance is available. Genset working plan can be set as per week or month.
Records function: relative faults shall be recorded in real time.
With 8 relay output (including 2 channels of fixed functions, 6 channels of functions can be configured), a variety of functions are optional;
6-way switch input (2-way function fixed,4-way function can be configured) and many functions are optional;
Control Protection:to realize automatic ATS switching and complete fault display and protection of the generator set;
Standard water-proof rubber gasket. The waterproof can reach IP65.
Module design: All the connections are adapted with European connectors so that installation, connection, repair and replacement can be more easily.
Parameters Display
S1, S2 Voltage State
Generator Unit Status
Switching state
S1/S2 line voltage
S1/S2 Phase Voltage
S1/S2 Phase Angle
S1 Frequency
Generator Battery Voltage(If connected)
S2 Frequency and Current Load Percentage
Continuous power supply time
Last continuous power supply time
Cumulative power supply time of S1/S2
Cumulative closing times of S1/S2
Alarm serial number and number of alarms
Alarm type
Alarm incident
Input port status
Output port status
Real-time clock
The following parameters are only available for series I:
S1/S2 Total kWh
S1/S2 Total kVarh
3 phase current
Current phase angle
Active power kW
Apparent power kVA
Reactive power kVar
Power factor
Parameters
Options | Parameters |
Power supply | DC8-36V Continuous |
AC90-280V(L1N1/L2N2) | |
Power Consumption | Standby:24V:MAX 2W |
Working:24V:MAX 6W | |
Mains AC Voltage Input | 1P2W 30VAC-369VAC(L-N) |
2P3W 30VAC-625VAC(L-L) | |
3P3W 30VAC-625VAC(L-L) | |
3P4W 30VAC-625VAC(L-L) | |
Gens AC Voltage Input | 1P2W 30VAC-369VAC(L-N) |
2P3W 30VAC-625VAC(L-L) | |
3P3W 30VAC-625VAC(L-L) | |
3P4W 30VAC-625VAC(L-L) | |
S1 Close Output | 16Amp(AC250V) free output |
S2 Close Output | 16Amp(AC250V) free output |
Programmable Relay output 1-6 | 10Amp(AC250V) free output |
Switch Value Input | Available if connecting with Battery - |
Working Condition | -25-65℃ |
Storage Condition | -40-85℃ |
Protection Level | IP65:when waterproof rubber gasket is added between controller and its panel |
Insulation strength | Apply AC1.5kV voltage between high voltage terminal and low voltage terminal; The leakage current is not more than 3mA within 1min. |
Overall Dimension | 210mm*160mm*50mm |
Panel Cutout | 186mm*142mm |
Weight | 0.85Kg |
Parameter Display:
- S1, S2 voltage state;
- Genset status;
- Switch state;
- S1/S2 line voltage;
- S1/S2 phase voltage;
- S1/S2 phase;
- S1 frequency;
- Generator battery pack voltage (if connected);
- S2 frequency;
- Continuous power supply time (hours, minutes, seconds);
- Last continuous power supply time (hours, minutes, seconds);
- S1/S2 cumulative power supply time (hours, minutes, seconds);
- S1/S2 cumulative number of closings;
- Module cumulative power-on time
- Alarm serial number and number of alarms;
- Alarm type;
- Alarm events;
- Input and output port serial number;
- Input port status: S1/S2 is the closed state, and input 1-4 is the programming port;
- Output port status: S1/S2 is closed output, 1-6 is programming port;
- Real-time clock;
- Current date/time.
The following parameters are available only to ATS520I and ATS520IR:
- Phase current;
- Current phase angle;
- Apparent power;
- Reactive power;
- Active power;
- Power factor;
- S1/S2 cumulative active energy;
- S1/S2 accumulated reactive energy.
Specifications:
- Operating voltage: DC 8V to 36V continuous; AC 90 to 280V (L1N1/L2N2)
- Power consumption: Standby: MAX 2W at 24V; Operation: MAX 6W at 24V
- Power generation input: one-phase two-wire 30VAC-369VAC(L-N), two-phase three-wire 30VAC-625VAC(L-L), three-phase three-wire 30VAC-625VAC(L-L) and three-phase four-wire 30VAC-625VAC(L-L)
- Mains input: one-phase two-wire 30VAC-369VAC (L-N), two-phase three-wire 30VAC-625VAC (L-L), three-phase three-wire 30VAC-625VAC (L-L) and three-phase four-wire 30VAC-625VAC (L-L)
- Maximum cumulative running time: 99999.9 hours (minimum storage time is 6 minutes)
- S1 closed output: 16Amp AC250 passive output
- S2 closed output: 16Amp AC250 passive output
- Configurable output 1-6: 10Amp passive output (contact type can be set)
- Switching input: valid when the negative pole of the battery is connected
- Operating conditions: -20 to 70°C
- Storage conditions: -30 to 80°C
- Protection class: IP54 (when the controller and control screen are equipped with waterproof rings)
- Insulation level: Apply AC2.2kV voltage between the AC high-voltage terminal and the low-voltage terminal, and the leakage current within 1min is not more than 3mA
- Dimensions: 210 x 160 x 50mm/8.3 x 6.3 x 2"
- Hole spacing: 186 x 142mm/7.3 x 5.6"
- Weight: 0.85Kg/1.9Lb