Features |
VICOTR 4105C Digital ground resistance tester |
VICOTR 4106C Ground resistance/soil resistivity tester |
VICTOR 6415A Double Clamp Ground Resistance Tester |
|
Features |
Ground resistance measurement, ground voltage measurement, low-value resistance measurement |
Two, three and four wires measure grounding resistance and soil resistivity; ground voltage and AC voltage measurement |
Ground resistance, soil resistivity, DC resistance, ground voltage, AC current, leakage current measurement |
|
power supply |
DC 7.4V 2600mAh rechargeable lithium battery, the battery is full of about 8.4V |
DC 7.4V 2600mAh rechargeable lithium battery, the battery is full of about 8.4V |
DC 8.4V (rechargeable battery, 300 hours of continuous standby) |
|
Range
|
Grounding resistance: 0.00Ω~2000Ω |
Grounding resistance: 0.00Ω~30.00kΩ |
Grounding resistance, DC resistance: 0.00Ω~30.00kΩ |
|
Grounding voltage: 0V~600V |
Grounding voltage: 0V~600V |
Grounding voltage: AC0.0V~100.0V |
|
|
/ |
Soil resistivity: 0.00Ωm~9000kΩm |
Soil resistivity: 0.00Ωm~9000kΩm |
|
|
/ |
/ |
Alternating current: AC 0.00mA~600.0A |
|
|
measurement method |
Precision three-wire measurement, simple two-wire measurement |
Precise 4-wire, 3-wire method measurement, simple 2-wire measurement of ground resistance |
Precision four-wire, three-wire method, simple two-wire, selection method, double clamp method to measure ground resistance |
|
Measurement methods
|
Grounding resistance: rated current pole changing method, measuring current 20mA Max; |
Grounding resistance: rated current pole changing method, measuring current 20mA Max |
Soil resistivity: quadrupole method (Winner method) |
|
Voltage to ground: average value rectification |
Voltage to ground: average value rectification (between P(S)-ES interface) |
DC resistance: pole changing method |
|
|
|
Soil resistivity: quadrupole method (Winner method) |
Alternating current: average value rectification (clamp-on) |
|
|
|
|
Voltage to ground: average value rectification (between P(S)-ES interface) |
|
|
Back light |
Controllable white screen backlight, suitable for dim places |
||
|
Display mode |
4-digit large LCD display with backlight |
||
|
Measurement instructions |
LED flashing indication in the measurement, LCD reverse count display |
LED flashing in measurement, LCD reverse count, progress bar diagram indication |
LED flashing indication in the measurement, LCD reverse count display |
|
LCD size |
128mm×75mm; display area: 124mm×67mm |
||
|
Instrument size |
Height, width and thickness: 280mm×260mm×160mm |
||
|
Standard test line |
3 strips: red 15m, yellow 10m, green 5m each |
4 strips: red 20m, black 20m, yellow 10m, green 10m each |
|
|
Simple test line |
2 strips: one for each of the red 1.6m and the green 1.6m |
2 strips: red 1.6m, black 1.6m each |
|
|
Auxiliary ground rod |
2 pieces: φ10mm×150mm |
4 pieces: φ10mm×150mm |
|
|
measure time |
Voltage to ground: about 3 times/second; ground resistance: about 15 seconds/time |
Ground voltage: about 3 times/second; ground resistance, soil resistivity: about 15 seconds/time AC current: about 2 times/second; |
ground voltage: about 2 times/second; ground resistance: about 7 seconds/time |
|
Number of measurements |
More than 5000 times (measure 10Ω in 20Ω mode, measure once, stop for 30 seconds and then measure) |
More than 5000 (short circuit test, 1, stop 30 seconds) |
|
|
Line voltage |
Measurement below the AC 600V |
||
|
Communication Interface |
With USB interface, software monitoring, storage data can be uploaded to the computer, saved and printed |
With RS232 interface, the stored data can be uploaded to the computer through software |
|
|
Communication line |
1 USB communication line, 1.5m long |
1 RS232 communication line, 1.5m long |
|
|
data storage |
400groups |
2000 groups |
2000groups |
|
Protection level |
IP65(cover) |
||
|
Overload protection |
Ground resistance measurement: AC 280V/3 seconds between E-P and E-C ports |
Measuring grounding resistance: AC 280V/3 seconds between C(H)-E, P(S)-ES ports |
Measuring grounding resistance: AC 280V/3 seconds between C(H)-E, P(S)-ES ports |
|
Insulation resistance |
10MΩ or more (500V between circuit and case) |
Above 20MΩ (500V between circuit and case) |
|
|
Resistant to pressure |
Between the AC 3700V/rms(circuit and the housing) |
||
|
Current clamp size |
/ |
/ |
Height, width and thickness: 185mm×115mm×43mm |
|
Current clamp |
/ |
/ |
2 pieces: blue and black plugs, 1 red and black plug each |
|
Current clamp diameter |
/ |
/ |
φ68mm |
|
Current clamp lead |
/ |
/ |
2m long |