EDR-75 is one economical slim 75W Din rail power supply series, adapt to be installed on TS-35/7.5
or TS-35/15 mounting rails. The
body is designed 32mm in width, which
allows space saving inside the cabinets. The entire series adopts the full range AC input from 90VAC to 264VAC and conforms to BS
EN/EN61000-3-2, the norm the European Union regulates for harmonic current.
EDR-75 is designed with metal housing
that enhances the unit's power dissipation. With working efficiency up to 88.5%, the entire series
can operate at the ambient temperature between
-20℃ and 60℃ under air
convection. It is equipped with constant current mode for over-load
protection, fitting various inductive
or capacitive applications. The complete protection functions and relevant
certificates for industrial control apparatus (UL508, TUV
BS EN/EN62368-1, and etc.) make
EDR-75 a very competitive
power supply solution for industrial applications.
|
MODEL |
EDR-75-12 |
EDR-75-24 |
EDR-75-48 |
|
|
OUTPUT |
DC VOLTAGE |
12V |
24V |
48V |
|
RATED CURRENT |
6.3A |
3.2A |
1.6A |
|
|
CURRENT RANGE |
0 ~ 6.3A |
0 ~ 3.2A |
0 ~ 1.6A |
|
|
RATED POWER |
75.6W |
76.8W |
76.8W |
|
|
RIPPLE & NOISE (max.) Note.2 |
80mVp-p |
120mVp-p |
150mVp-p |
|
|
VOLTAGE ADJ. RANGE |
12 ~ 14V |
24 ~ 28V |
48 ~ 55V |
|
|
VOLTAGE TOLERANCE Note.3 |
±2.0% |
±1.0% |
±1.0% |
|
|
LINE REGULATION |
±0.5% |
±0.5% |
±0.5% |
|
|
LOAD REGULATION |
±1.0% |
±1.0% |
±1.0% |
|
|
SETUP, RISE TIME |
1200ms, 60ms/230VAC 2000ms, 60ms/115VAC at full load |
|||
|
HOLD UP TIME (Typ.) |
60ms/230VAC 12ms/115VAC at full load |
|||
|
INPUT |
VOLTAGE RANGE Note.6 |
90
~ 264VAC 127
~ 370VDC [DC input
operation possible by connecting AC/L(+), AC/N(-)] |
||
|
FREQUENCY RANGE |
47 ~ 63Hz |
|||
|
EFFICIENCY (Typ.) |
85.5% |
87.5% |
88.5% |
|
|
AC CURRENT (Typ.) |
1.45A/115VAC 0.9A/230VAC |
|||
|
INRUSH CURRENT (Typ.) |
20A/115VAC 35A/230VAC |
|||
|
LEAKAGE CURRENT |
<1mA / 240VAC |
|||
|
PROTECTION |
OVERLOAD |
105 ~ 130% rated
output power |
||
|
Protection type : Constant current
limiting, recovers automatically after fault condition is removed |
||||
|
OVER VOLTAGE |
14 ~ 17V |
29 ~ 33V |
56 ~ 65V |
|
|
Protection type : Shut down o/p voltage, re-power on to recover |
||||
|
OVER TEMPERATURE |
Shut down o/p voltage,
re-power on to recover |
|||
|
ENVIRONMENT |
WORKING TEMP. |
-20 ~ +60℃ (Refer to "Derating Curve") |
||
|
WORKING HUMIDITY |
20 ~ 95% RH non-condensing |
|||
|
STORAGE TEMP., HUMIDITY |
-40 ~ +85℃, 10 ~ 95% RH |
|||
|
TEMP. COEFFICIENT |
±0.03%/℃ (0 ~ 50℃) |
|||
|
VIBRATION |
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min.
each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 |
|||
|
SAFETY & EMC (Note 4) |
SAFETY STANDARDS |
UL508, TUV BS EN/EN62368-1, EAC TP TC 004, BSMI CNS14336-1 approved;(meet BS EN/EN60204-1) |
||
|
WITHSTAND VOLTAGE |
I/P-O/P:3KVAC I/P-FG:2KVAC O/P-FG:0.5KVAC |
|||
|
ISOLATION RESISTANCE |
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC
/ 25℃/ 70% RH |
|||
|
EMC EMISSION |
Compliance to BS EN/EN55032 (CISPR32) Class A, BS EN/EN61000-3-2,-3, EAC TP TC 020, CNS13438 Class A |
|||
|
EMC IMMUNITY |
Compliance to BS EN/EN61000-4-2,3,4,5,6,8,11, BS EN/EN55024, BS EN/EN61000-6-2 (BS EN/EN50082-2), heavy industry
level, criteria A, EAC TP TC 020 |
|||
|
OTHERS |
MTBF |
506.6K hrs min. MIL-HDBK-217F (25℃) |
||
|
DIMENSION |
32*125.2*102mm (W*H*D) |
|||
|
PACKING |
0.51Kg; 28pcs/15.3Kg/1.22CUFT |
|||
|
NOTE |
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor. 3. Tolerance : includes set up tolerance, line regulation and load regulation. 4. The
power supply is considered a component which will be installed into a final
equipment. The final equipment must be re-confirmed that it still meets EMC
directives. 5. Installation
clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side
are recommended when loaded permanently with full power. In case the adjacent device is a heat source, 15mm clearance is recommended. 6.
Derating may be needed under low input voltage. Please check the derating curve for more details. 7. The ambient temperature derating of 3.5℃/1000m with fanless models and of 5℃/1000m with fan models for operating altitude higher than 2000m(6500ft). ※ Product Liability Disclaimer:For detailed information, please refer to
https://www.meanwell.com/serviceDisclaimer.aspx |
|||