Loop Resistance Meter Clamp on Ground Resistance Tester with Range 0.01 to 1200Ω


Note: Battery cannot be included during the shipping !!! 


Instruction:


1. Clamp Earth Resistance Tester is our company's technology research and development team on technical quality of the pursuit of excellence, through continuous innovation to improve, upgrade with the old product. Its performance is mainly reflected in:



2. Clamp Earth Resistance Tester is widely used in the grounding resistance measurement of the power, telecommunications, meteorology, oilfield, construction and the industrial and electrical equipment. In the measurement of a grounding system with loop, does not require breaking down the grounding down lead, and no need the auxiliary electrode. It is safe, fast and simple in use. The tester can measure ground faults which cannot be measured by traditional methods. It can be used in applications where traditional methods cannot be measured, because the ETCR series clamp grounding resistance meter measures the combined value of grounding body resistance and grounding lead resistance.


Specification:


▲Function Ground resistance test, Loop resistance test

▲Power Supply 6VDC 4 PCS of AA Alkaline batteriesnot included

▲Resistance Range 0.01-1200Ω

▲Resistance Resolution 0.001Ω

▲Highest Resistance Accuracy ±1%±0.01Ω

▲Data memory 99 Sets

▲Alarm Threshold Setting Range Resistance: 1-199Ω

▲Alarm Sound and Light "Beep-beep-beep" alarm tone, Alarm Symbol Flashing, Press AL key to turn on, turn off Alarm or set Alarm Threshold.

▲Interference Signal Recognition "Beep-beep-beep" tone, NOISE symbol blinking

▲Working Temperature and Humidity -20°c-55°c; 20%RH-90%RH

▲LCD Screen 4 Digits LCD display, Screen L*W: 47mm*28.5mm

▲Clamp Size 65mm×32mm

▲Clamp Opening Extent 32mm

▲Tester Weight 1160g

▲Clamp Dimension L*W*T: 285mm*85mm*56mm

▲Protection Level Dual Insulation

▲Structural Feature Clamp CT

▲Shifting Automatic shifting

▲External magnetic field <;40A/m

▲External electrical field <;1V/m

▲Single measurement time 0.5 second

▲Resistance measurement frequency >1KHz

▲Measured current frequency 50/60Hz Automatic measurement

▲Low Battery Indication Low battery symbol displays when battery is lower then 5.3V

▲Memory Full Indication M

▲ Accessories:Meter: 1 piece, Test ring: 1 Piece, Meter Suitcase: 1 Piece


Packing:


Package

 Outer package

 Carton

 Inner package

 Aluminum case

 Accessory

 Meter

 1pcs

 Aluminum Case

 1pcs

 Test Ring

 1pcs

 Manual

 1pcs

 Certification

 1pcs

 Warranty Card

 1pcs