Generator Control Module DSE705 Auto Transfer Switch Control Module

The DSE 705 Generator Controller is Transfer Switch Control Module that have been designed to monitor the mains (utility) provide.
When the mains (utility) power fails, the module will send a start request to the generator control unit. When the generator is up and running the module transfers the load across.
When the mains (utility) returns, the module transfers the load back and removes the start command. The generator should then begin its shutdown procedure.

The DSE705 Controller can be configured to follow the users’ pre-set start and stop sequences.
 
Features:
Main Features:
·Automatic mains (utility) supply monitoring
·Load changeover control
·Manual start
·Protected solid state (PSS) outputs
·Front panel mounting
·Front panel programming
·LED indicators
·Configurable timers
·Configurable outputs
·Single/three phase mains sensing
Benefits:
·Transfer’s between mains and generator power
·On-site module configuration to match user requirements
Operation:
The module is operated by the three push-buttons on the front:
Manual Off Load –This is used to manually start and run the engine off load. Should the mains (utility) supply fail, then the load is transferred to the generator automatically.
Manual On Load -
This mode is used to manually start and run the engine on load.
Auto Mode –This puts the module into automatic mode, where it will await a mains failure. Upon detection
it will send a start request to the generator control unit.

Parameters:
DC Supply 8 Volts to 35 Volts DC Continuous.
Cranking Dropouts Able to survive 0 Volts for 50 mS, providing supply was at least 10 V before dropout and supply recovers to 5 Volts.This is achieved without the need for internal batteries.
Max. Current Operating 50mA
Standby 10mA
Alternator Input Range 75 Volts (ph-N) to 277 Volts (ph-N) AC (+20%)
Mains Input Voltage 15~277 Volts (ph-N) AC (+20%)
Alternator Input Frequency 50~ 60 Hz at rated engine speed
(Minimum:75V AC Ph-N)
Generator available 45Hz
Generator failed 20Hz
Mains Frequency 50~60 Hz
Start Output 1.2 Amp DC at supply voltage.
Fuel Output 1.2 Amp DC at supply voltage.
Auxiliary Outputs 1.2 Amp DC at supply voltage.
Charge Fail 12 Volts = 8 Volts CF 24 Volts = 16 Volts CF
Dimensions 125mm x 165mm x 28 mm
Operating Temperature Range -30°C to + 70°C
Applicable Standards Compliant with BS EN 60950 Low Voltage Directive
Compliant with BS EN 50081-2:1992 EMC Directive
Compliant with BS EN 61000-6-4:2000 EMC Directive

KEY FEATURES of DSE 705 Generator ATS Controller

• Automatic mains (utility) provide monitoring
• Load changeover control
• Manual start
• Protected Solid State (PSS) outputs
• Front panel mounting
• Front panel programming
• LED indicators
• Configurable timers
• Single/three phase mains (utility) sensing
• Remote start input

KEY BENEFITS DSE705 Generator Controller

• Transfers between mains (utility) and generator power
• On-site module configuration to match user requirements


How to choose a suitable Generator Controller?

1. Cheap Generator Controller : DSE501K, DSE701, DSE702, DSE704, DSE3110, DSE4520, DSE4620 (for low cost small power generators)
2. More Functions Genset Controller: DSE5110, DSE5220, DSE6020, DSE6120, DSE7210, DSE7220, DSE7310, DSE7320, MRS-10, MRS-16, AMF-20, AMF-25 (for high power generator)
3. More Languages Generator Controller: DSE6120, DSE7210, DSE7220, DSE7310, DSE7320, MRS-10, MRS-16, AMF-20, AMF-25 (Avaliable Languages: English, Spanish, Portuguese, French, German, Russian, Chinese and etc.)
4. AMF Controller Modules: DSE704, DSE720, DSE5220, DSE6120, DSE7220, DSE7320; AMF-20, AMF-25 (Auto Mains Failure Generator Control Modules)
5. Synchronising and Load Share Controller: DSE8610, DSE8620, DSE8660, ICNT-MINT, ICNT-MCNT, ICNT-SPTM
6. Canbus ECU Communications Generator Control Panel: MRS-16, AMF-25, DSE7210, DSE7220, DSE7310, DSE7320, DSE3110 ECU, DSE4520, DSE7320 MKII
 



Notice: 

Because,the international air shipping forbid to ship liquid,powder and batteries, If you purchased goods containing such items, we will not be putting them packing. Thank you for your support.






payment

Payment must be made within 12 days after the auction/bid ends, or eBay will open Unpaid Item case automatically later.





Shipping

Please read this before buying International Shipping may Be Delayed Due to Customs. Customers are Responsible For All Import Charges, Tariffs, Duties, Taxes, and Fees Associated with Import of the product. Shipping Charges does not include any Import Charges, Tariffs, Duties, Taxes, and Fees Associated with it. We are not responsible for undeliverable address.We reserve the right to charge the shipping fee again for returned items due to wrong address.





About US

We work 6 Days a week From 9:00am - 6:00pm Monday - Saturday CHINA Time.Please contact us with any comments, questions or suggestions that you may have bysending ebay message, All the mail will be replied within 24 hours.