General product information
| Scope of delivery | Jumper (Art-No. 90960) |
|---|
Electrical data | Input
| Input voltage DC | 24 V |
|---|
| Input voltage DC min. | 19,2 V |
|---|
| Input voltage DC max. | 30 V |
|---|
| Input current | 17 mA |
|---|
Electrical data | Output
| Utilization category AC-15 (EN IEC 60947-5-1) | 3 A @ 24 V, 3 A @ 110 V, 3 A @ 230 V |
|---|
| Utilization category DC-13 (EN IEC 60947-5-1) | 1,3 A @ 24 V, 0,25 A @ 110 V, 0,1 A @ 230 V |
|---|
| Switching frequency max. | 15 Hz |
|---|
| Power rating AC max. | 1500 VA |
|---|
| Power rating DC max. | 180 W |
|---|
| Switching voltage AC max. | 250 V |
|---|
| Switching voltage DC max. | 250 V |
|---|
| Switching current DC | 1 mA |
|---|
| Switching current max. | 5 A |
|---|
| Switching capacity AC-12 (EN IEC 60947-5-1) | 5 A (24/110/230 V AC) |
|---|
Diagnostics
| Status indication LED | yellow |
|---|
Device protection
| Condition lifetime | load-dependent |
|---|
Device protection | Electrical
| Rated surge voltage | 4 kV |
|---|
| Electrical lifetime | 100000000 Cycles |
|---|
Device protection | Mechanical
| Mechanical endurance | 100000000 Cycles |
|---|
Mechanical data
| Drop-out time max. | 10 ms |
|---|
| Response time max. | 10 ms |
|---|
| Bounce time max. | 1 ms |
|---|
Mechanical data | Material data
| Material contact | Ag Ni 0.15 hv, Ag hv |
|---|
Mechanical data | Mounting data
| Mounting method | geschnappt |
|---|
| Suitable for mounting type | Mounting rail TH35, G32, (EN 60715) |
|---|
| Height | 82 mm |
|---|
| Width | 12 mm |
|---|
| Depth | 68 mm |
|---|
Environmental characteristics | Climatic
| Operating temperature min. | -20 °C |
|---|
| Operating temperature max. | 60 °C |
|---|