3 Attempt Automatic Generator Control Module AECM105

In weather-proof IP67 rated wall mounted enclosure

1m multi core cable included (pre-wired)


24/7 Weekly programmable timer on-board


Set It and Forget It: Generator Scheduled Start and Stop Control


This time switch allows to start and stop your auto start enabled generator within 17 pre-set time slots throughout the whole week.



Suitable for single and three phase generators. 

 Not suitable for generators with manually operated choke.

DESCRIPTION 

The Model AECM105 is a new generation of AECM designed to start and stop the generator engine by using digital 24/7 timer and wired remote start input (so-called 2 wire start-stop). Optionally fitted devices are available during check out: wireless start and stop (key fob), Battery Voltage Sensor (BVS), pre-heat control output and load control output. The wireless control allows to start and stop the generator engine remotely within approximately 100 m distance. The actual working distance depends on many factors and could be less than 100m, for instance if the key fob is used inside the building or/and the generator controller is located inside the building. The Battery Voltage Sensor (BVS) controls the engine starting battery voltage and able to start the generator engine automatically upon registering Low Voltage Threshold (LVT) 12Vdc (default setting). This LVT can be re-adjusted on-site. It will continue to run the engine until the engine starting battery becomes fully charged at 13.5Vdc (default setting). When BVS senses the High Voltage Threshold (HVT) it will shut down the engine. The HVT can be also re-adjusted on-site. The BVS can work with voltages up to 30Vdc (12V and 24V batteries supported). AECM105 will indicate the operational status and fault conditions, automatically shut down the engine and indicate the start engine failure by flashing "START FAIL" LED on the front panel. Other faults are indicated by steady LED. Remote wired operation of the module is via single pole normally open maintained switch connected between terminal #1 (wire 1) and battery negative terminal #G/Y (wire G/Y).


IMPORTANT!


THIS CONTROL MODULE MUST NOT BE CONNECTED DIRECTLY TO STARTER MOTOR, FUEL SOLENOID, LOAD OR A GLOW PLUG. APPROPRIATELY RATED EXTERNAL POWER RELAYS SHOULD BE USED AS IT IS SHOWN ON THE DIAGRAM PROVIDED. The starter relay R1 can only energize for 2nd and 3rd crank cycle if “Low Oil Pressure” is sensed, to confirm that the engine is stationary. This is designed to prevent damage to the starter and ring gear in the event of the control module is not sensing that the engine has started (i.e. terminals #11 and #8 are not connected to the alternator AC output). Should the engine still fail to start after the maximum number of attempts, “START FAIL” LED is displayed and the starter is latched out.


WIRED REMOTE / LOCAL CONTROL


Toggle switch RST is On (closed).

0.5 second after the fuel relay R2 is energized, the 3 attempt start will begin its start sequence: the start relay R1 will energize, feeding battery +ve on terminal #7 (wire 7) to terminal #2 (wire 2) and thence on to the start circuit (external power relay PR1). The crank period is set for 12 seconds. If  the engine  has not fired by the end of 1st attempt, the starter is turned off for a 20 sec. period. The sequence will then repeat up to a maximum number of start attempts. Following a successful start, sensed when AC alternator's voltage rises above 40% of nominal (terminals #8 (wire 8) and #11 (wire 11), the crank relay is de-energized and latched out to prevent re-engagement of the starter with the engine running.


PRE-HEAT CONTROL (optional function)


Make sure that "pre-heat" DIP switch 1 is "ON"

When pre-heating cycle is timed out and flashing LED (HET/GL) on the panel is turned off, the fuel relay R2 is energized and the 3 attempt start will begin its start sequence: the start relay R1 will energize, feeding battery +ve on terminal #7 (wire 7) to terminal #2 (wire 2) and thence on to the start circuit (external power relay PR1). The crank period is set for 12 seconds. If  the engine  has not fired by the end of 1st attempt, the starter is turned off for a 20 sec. period. The sequence will then repeat up to a maximum number of start attempts. Following a successful start, sensed when AC alternator's voltage rises above 40% of nominal (terminals #8 (wire 8) and #11 (wire 11), the crank relay is de-energized and latched out to prevent re-engagement of the starter with the engine running. 


LOAD CONTROL (optional function)


After a successful start, when engine's parameters are settled (when 7 sec time delay provided by hold-off timer is timed out, then warm-up time delay is timed out), the Load Control Output (relay R4) will energize (ON LOAD LED will lit) and send AC signal from terminal #10 (wire 10) to an external customer's contactor which will connect the AC alternator output to the load. The warm-up time before accepting load and cool-down time after relieving load (while generator is still running and is ready to accept the load again if the remote/local start signal is switched back on) are re-programmable (by us) with a limit of 255 sec [4.25 min] max. Please contact us first If specific time settings are required. Otherwise the module will have 10 sec warm-up/cool-down time delays.


LOAD CONTROL DEFAULT SETTINGS:


10 SEC WARM-UP

10 SEC COOL-DOWN


WIRELESS CONTROL (optional function)


Toggle switch RST is Off

Make sure there are no metal doors/walls/other metal shields between you and AECM105 module. Any metal or brick wall may significantly reduce the working distance between the transmitter (key fob) and AECM105 module.

Press “A” button on a key fob for 1 sec and release it. The generator should try to start within a few seconds.

Press “B” button to stop. If command was unsuccessful - come closer to the module.


RELAY OUTPUTS ARE PROVIDED FOR:

    • Starter Motor Output R1
    • Fuel Solenoid Output R2
    • Glow Plug Output R3
    • Load Control Output R4

CONFIGURABLE INPUTS ARE AVAILABLE FOR:

    • Wired remote start/stop
    • High engine temperature
    • Oil pressure
    • Emergency stop
    • AC alternator frequency monitor (over/under speed s/d)

MULTIPLE ALARM CHANNELS ARE PROVIDED TO MONITOR THE FOLLOWING:

    • Under/Over speed S/D (speed fault). This alarm sensor can be enabled/disabled via SPEED DIP switch 2.
    • Low oil pressure S/D. “LOW OIL” led is lit when fault is identified.
    • High engine temperature S/D. “HET/GL” led is lit when fault is identified.
    • Fail to start S/D. “ST.FAIL” led is lit when fault is identified.
    • Emergency stop S/D. E. STOP led is lit when fault is identified.

* During engine cranking and for a short time afterwards the protective hold-off timer is active and the relevant alarms inputs are inhibited. This enables the engine to start and achieve normal running conditions. Once the timer has expired, the inputs are enabled providing normal protection from the module.

BVS (BATTERY VOLTAGE SENSOR)
(optional function)

IMPORTANT NOTES!
 BVS Sensor Is Disabled By Default. Fit The Configurable Link (Shown Below) to Enable.
Your BVS is set to monitor the engine starting battery.
To re-configure BVS please contact us BEFORE purchasing the module.

The BVS (Battery Voltage Sensor) allows the AECM (Automatic Engine Control Module) to start and run the engine automatically when your engine starting battery is ready to be charged. The BVS monitors two voltage thresholds: Low Voltage Threshold (LVT) and High Voltage Threshold (HVT).When controlled voltage becomes equal to LVT the BVS tells the AECM to start and run the engine until it measures the HVT.

Please note that BVS controls the engine starting battery voltage which is also a power supply to the AECM105. The BVS circuit is designed to control DC voltage from 6Vdc to 30Vdc max. and we can pre-set your specific voltage HVT and LVT for you.

This BVS enabled control module comes with following BVS thresholds:

Start the engine @ 12.00 Vdc
Stop the engine @ 13.50 Vdc
 
Please note: you can always re-calibrate these thresholds on-site (this procedure requires an adjustable precise power supply from "0" to "30" Vdc, a small flat screwdriver and digital DC voltmeter).

  1. Wireless receiver circuit (optional)
  2. Configurable DIP switch: 1: pre-heat activation. 2: frequency control activation.
  3. BVS link. Remove the link to disable the BVS
  4. BVS control circuit
BVS set up instructions

      Make sure the generator engine is disabled and unable to start automatically (press the emergency stop button)!

Setting up the low voltage threshold (this is when you would like the generator to start and run):

    • Make sure the AECM105 controller is powered by the generator battery which requires charging (low battery state).
      Note: It is advisable to use an adjustable DC power supply unit (0V to 30V adjustable voltage output) connected to terminals #G/Y (-) and #7 (+), instead of real battery to speed up the process of calibration.

HOW TO SET UP THE BVS LOW THRESHOLD
 
Connect your discharged (ready to be charged) engine starting battery to terminals # G/Y and # 7
Start turning "PL" (very slowly) clockwise/anticlockwise* until LED "L" changes its state from OFF to ON
Stop turning immediately when you notice this change.

HOW TO SET UP THE BVS HIGH THRESHOLD
 
Connect your fully charged engine starting battery to terminals #G/Y) and #7.
Start turning "PH" (very slowly) clockwise/anticlockwise* until LED "H" changes its state from ON to OFF
Stop turning immediately when you notice this change.
Enable AECM105 by switching off Emergency Stop Button.
The accuracy of these adjustments could be as good as ±0.1 V
*Note: the direction of turning depends on previous threshold settings and is usually clockwise, however sometimes it needs to turn anti-clockwise.

Wiring Diagram


SPECIFICATION


DC Supply: generator starting battery 12V or/and 24V (6...40Vdc max)

Max. Standby Current: 10 mA @ 12 V

AC Alternator Input Range: 300 VAC max

Under speed shut down: @ 30 Hz [45Hz for USA and Canada]

Over speed shut down: @ 57 Hz [69Hz for USA and Canada]

Number of attempts: 3 (user-configurable prior to order)

Crank duration: 12 sec (user-configurable prior to order)

Preheat time: 10 sec (user-configurable prior to order)

Load on (warm-up) time delay: 10 sec (user-configurable prior to order)

Load off (cool-down) time delay: 10 sec (user-configurable prior to order)

Hold-off timer set for: 7 sec (user-configurable prior to order)

Starter relay output (terminal 1): 10A max

Fuel solenoid output (terminal 3): 10A max

Glow plug relay output (terminal 2): 10A max

Load control relay output (terminal 4): 10A max

Operating Temperature Range: -30 to +60°C.

Humidity Range Operating: 20 - 80% (non-condensing)


-----------------------------------------------------------------

Package includes:

 

1 X AECM105 control module with digital timer fitted and 1m cable pre-wired

1X user manual and wiring diagram

1 remote control (if ordered). More than 1 remote control could be paired, please ask for details.

All other external parts (external relays, contactors, switches, fuses etc not included and purchased separately by customer (if required)

-----------------------------------------------------------------

*Please give us your desired settings so we could program your module as required, otherwise all time settings remain as per this description.