Digital High Voltage Insulation Resistance Meter, also known as Megohmmeter, High Voltage Insulation Resistance Tester, is used for insulation resistance testing. This meter has LCD large screen gray backlight display, data storage, data access, alarm, automatic shutdown and other functions. At the same time also has the measurement of DC voltage AC voltage absorption ratio and polarization index function. The whole machine is beautiful and high-grade, wide range, high resolution, convenient operation, easy to carry, accurate, reliable, stable performance, strong anti-interference ability.
And has a shockproof, dustproof, moisture-proof structure, adapt to the harsh working environment, is the telecommunications, electric power, meteorology, engine room, oil fields, electromechanical installation and maintenance and the use of electric power as an industrial power or energy source of industrial enterprises commonly used and essential instrumentation. It is suitable for measuring the resistance value of various insulating materials and insulation resistance of transformers, motors, cables and electrical equipment.
Composed of medium and large-scale integrated circuits. This meter has large output power and many output voltage levels (5 voltage levels). Rated insulation test voltage range 100 ~ 5000V, insulation resistance measurement range 0.01 ~ 200GΩ. DC voltage measurement range 0 ~ 1000V, AC voltage measurement range 0 ~ 750V.
Function |
Insulation resistance test, AC voltage test, DC voltage measurement |
Ambient Temperature and Humidity |
23℃±5℃,below 75%rh |
Power |
DC 9V 6-section LR14 Dry Battery Standby for more than 100 hours |
Rated Voltage |
250;500;1000;2500;5000 |
Rated Voltage Accuracy |
±10% |
Output short-circuit Current |
≥2mA |
Absorption Ratio Measurement |
Have |
Polarization Index Measurement |
Have |
Test Method |
DC voltage drop method |
Test Voltage |
DC voltage measurement |
Maximum Capacitive Load |
Operates below 1uF |
Shift Gear |
Automatic shifting |
Back light |
Controllable gray backlight, suitable for use in dim places |
Display Mode |
4 large LCD display, gray backlight |
Measurement Indication |
LED flashes during measurement |
LCD Size |
108mm×65mm |
Instrument Size |
L/W/H:240mm×188mm×85mm |
Test Line |
High pressure rod: red 1 meter Test line: black 1 meter green 1 meter |
Measurement Time |
Voltage 2 times/sec, insulation resistance 7 seconds/time |
Line Voltage |
measure below AC600V |
Data Storage |
500 groups,“MEM”storage instructions, display“FULL”symbol indicates that the storage is full |
Data Review |
The “MR” symbol indicates when looking up data |
Overflow Display |
“OL” symbol indicates over-range overflow |
Alarm Function |
Alarm when the measured value exceeds the alarm setting value |
Battery Voltage |
Low battery voltage symbol, prompt battery replacement when battery voltage is low |
Automatic Shutdown |
“APO”Indicate Automatic Shutdown After 15 Minutes |
Power Consumption |
Standby: About 40mA (backlight off) |
|
Turn on backlight: about 43mA |
|
Measurement: about 75mA (backlight off) |
Weight |
Instrument:1230g (Including battery) |
Working Temperature and Humidity |
-10℃~40℃;Below 80%rh |
Storage Temperature and Humidity |
-20℃~60℃;Below 70%rh |
Insulation resistance |
200MΩ or more (500V between circuit and case) |
Pressure Resistance |
AC 5160V/rms(Between circuit and case) |
Electromagnetic properties |
IEC61326(EMC) |
Suitable for Safety Regulations |
IEC61010-1(CAT Ⅲ 300V、CAT IV 150V、Pollution degree 2); |