Features

Input 340~550VAC, 3-phase
Width only 110mm
Built-in active PFC function
High efficiency up to 94.5%
Protections: Short circuit / Overload / Over voltage / Over temp.
Cooling by free air convection
Installed on DIN rail TS-35 / 7.5 or 15
EN61000-6-2(EN50082-2) industrial immunity level
Current sharing up to 3840W (3+1)
Built-in DC OK relay contact
3 years warranty

General Specification

AC input voltage range340~550VAC, 3-phase ( two phase operation possible)
AC input current (Typ.)2A / 400VAC, 1.4A / 500VAC
AC inrush current (max.)Cold start, 60A at 400VAC
DC adjustment range24V: 24~28V, 48V: 48~55V
Overload protection105%~130% rated output power, constant current limiting, unit will shut down after 3 sec., re-power on to recover
Over voltage protection29~33V (24V model), 56~65V (48V model), shut down o/p voltage, re-power on to recover
Over temp.90ºC±5ºC (24V model), 85ºC±5ºC (48V model) shut down o/p voltage, recovers automatically after temperature goes down
Withstand voltageI/P-O/P:3kVAC I/P-FG:2kVAC O/P-FG:0.5kVAC O/P-DC OK: 0.5kVAC
Working temperature-30~+70°C (refer to output derating curve)
Safety standardsUL508 approved; IEC60950-1 CB approved by SIQ
EMC standardsEN55022 class B, EN61000-3-2,3, EN61000-4-2,3,4,5,6,8,11, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level
ConnectionI/P: 3 poles, O/P: 6 poles screw DIN terminal
Dimension (LxWxH)110x 125.2x 150 mm
CASE214A