| range | TeSys TeSys Deca |
|---|---|
| device short name | GV3P |
| product name | TeSys GV3 TeSys Deca |
| Product or Component Type | Circuit breaker |
| Device Application | Motor |
| trip unit technology |
Complementary>th >poles description
| 3P | |
| network type | AC |
|---|---|
| utilisation category | AC-3 IEC 60947-4-1 Category A IEC 60947-2 |
| network frequency | 50/60 Hz IEC 60947-4-1 |
| fixing mode | 35 mm symmetrical DIN rail clipped Panel screwed with 3 x M4 screws) |
| operating position | Any position |
| motor power kW | 18.5 kW 400/415 V AC 50/60 Hz 22 kW 500 V AC 50/60 Hz 37 kW 690 V AC 50/60 Hz |
| breaking capacity | 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 50 kA Icu 440 V AC 50/60 Hz IEC 60947-2 6 kA Icu 690 V AC 50/60 Hz IEC 60947-2 50 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 12 kA Icu 500 V AC 50/60 Hz IEC 60947-2 |
| [Ics] rated service short-circuit breaking capacity | 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 50 % 500 V AC 50/60 Hz IEC 60947-2 50 % 690 V AC 50/60 Hz IEC 60947-2 |
| Control Type | Rotary knob |
| Line Rated Current | 40 A |
| thermal protection adjustment range | 30…40 A |
| magnetic tripping current | 560 A |
| [Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ui] rated insulation voltage | 690 V AC 50/60 Hz IEC 60947-2 |
| [Ith] conventional free air thermal current | 40 A IEC 60947-4-1 |
| [Uimp] rated impulse withstand voltage | 6 kV IEC 60947-2 |
| power dissipation per pole | 8 W |
| mechanical durability | 50000 cycles |
| electrical durability | 50000 cycles AC-3 440 V In |
| maximum operating rate | 25 cyc/h |
| rated duty | Continuous IEC 60947-4-1 |
| tightening torque | 44.25 lbf.in (5 N.m) EverLink BTR screw connectors 0.04 in² (25 mm²) 70.81 lbf.in (8 N.m) EverLink BTR screw connectors 0.05 in² (35 mm²) |
| suitability for isolation | Yes IEC 60947-1 |
| phase failure sensitivity | Yes IEC 60947-4-1 |
| height | 5.20 in (132 mm) |
| Width | 2.17 in (55 mm) |
| depth | 5.35 in (136 mm) |
| Net Weight | 2.12 lb(US) (0.96 kg) |
| color | Dark grey |
Environment>th >IP degree of protection
| standards | EN/IEC 60947-2 EN/IEC 60947-4-1 CSA C22.2 No 60947-4-1 UL 60947-4-1 |
|---|---|
| Product Certifications | IECEE CB Scheme br>CSA CCC EAC ATEX BV LROS (Lloyds register of shipping) DNV-GL ABS UKCA |
| protective treatment | |
| IP20 IEC 60529 | |
| IK degree of protection | IK09 |
| ambient air temperature for operation | -4…140 °F (-20…60 °C) |
| Ambient Air Temperature for Storage | -40…176 °F (-40…80 °C) |
| fire resistance | 1760 °F (960 °C) IEC 60695-2-1 |
| operating altitude | 9842.52 ft (3000 m) |
Ordering and shipping details
| Category | 22366 - MAN STR PROTECTORS-GV1/GV3 |
|---|---|
| Discount Schedule | I11 |
| GTIN | 3389119405393 |
| Nbr. of units in pkg. | 1 |
| Package weight(Lbs) | 34.67 oz (983 g) |
| Returnability | Yes |
| Country of origin | FR |
Packing Units
| Unit Type of Package 1 | PCE |
|---|---|
| Package 1 Height | 2.56 in (6.5 cm) |
| Package 1 width | 5.75 in (14.6 cm) |
| Package 1 Length | 6.30 in (16 cm) |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 120 |
| Package 2 Weight | 295.33 lb(US) (133.96 kg) |
| Package 2 Height | 28.94 in (73.5 cm) |
| Package 2 width | 23.62 in (60 cm) |
| Package 2 Length | 31.50 in (80 cm) |