Burkert Fluid Control Systems SE56 558308 Valve 100-240VAC
Sensor
Sensor type
Magnetic inductive
Magnetic inductive type
Fullbore
Detection of flow direction
Yes
Measurand
Flow rate (volume)
Yes
Concentration 1
No
Precision of volume flow rate in relation to reading
0,2 %
Conductivity min
5 µS/cm
Voltage / Frequency
Voltage frequency
45/66 Hz
AC Voltage min.
90 V
AC Voltage max.
265 V
Process Pressure / Temperature
Temperature medium min
-20 °C
Temperature medium max
130 °C
Temperature environment min
-20 °C
Temperature environment max
60 °C
Features
Time dosing
No
Batch dosing
Yes
Extended diagnosis
No
Continuous measurement
Yes
Volumeter
Yes
Dosing
Yes
Switch
No
Parametrisation local
Yes
Parametrisation separate
No
Parametrisation fixed
No
Properties
Type
SE56
Construction device
Remote wall
Transmitter type
expanded
Electrical Port Connection
Electrical connection 1 type
Cable gland PG11
Electrical connection 1 quantity
6 PCE
Electrical connection 1 material category
Plastics
Electrical connection 1 material
PA (Polyamide)
Input / Output
Input type digital quantity
1 PCE
Output type analog quantity
1 PCE
Output 1 type analog current
4-20 mA
Output analogue current functioning principle source
Yes
Output analogue current functioning principle drain
Yes
Output 1 digital type
Transistor
Digital output 1 transistor contactless
0,1 A
Output 1 digital transistor connection NPN
Yes
Output 1 digital transistor connection PNP
Yes
Output 1 digital version NC
No
Output 1 digital version NO
No
Output 2 digital type
Transistor
Output 2 digital transistor connection NPN
Yes
Output 2 digital transistor connection PNP
Yes
Digital output 2 transistor contactless
0,1 A
Output 2 digital version NC
No
Output 2 digital version NO
No
Software / Communication
Display type
Display
Protection Type
Tropical climate version
No
Protection type transmitter front/wall-installation (IP)
IP67