Technical dataEL3202
Number of inputs2
Power supplyvia the E-bus
Technology2-, 3-wire (default setting: 3-wire)
Distributed clocks
Input filter limit frequencytyp. 1 kHz
Sensor typesPt100, Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000, resistance measurement (e.g. potentiometer, 10 Ω…1/4 kΩ), KTY sensors (types see documentation)
Connection method2- or 3-wire (default: 2-wire)
Resolution0.1 °C per digit
Conversion timeapprox. 85 ms default setting, 2…800 ms configurable
Temperature range-200…+850 °C (Pt sensors); -60…+250 °C (Ni sensors)
Measuring current< 0.5 mA (load-dependent)
Measurement error/ uncertainty< ±0.5 °C for Pt sensors
Electrical isolation500 V (E-bus/signal voltage)
Current consumption power contacts
Current consumption E-bustyp. 190 mA
Bit width in the process image2 x 32 bit RTD input
Special featuresintegrated digital filter, limit value monitoring, variable connection technology
Weightapprox. 60 g
Operating/storage temperature-25…+60 °C/-40…+85 °C
Relative humidity95 %, no condensation
EMC immunity/emissionconforms to EN 61000-6-2/EN 61000-6-4
Vibration/shock resistanceconforms to EN 60068-2-6/EN 60068-2-27
Protect. rating/installation pos.IP20/variable
Pluggable wiringfor all ESxxxx terminals
Approvals/markingsCE, UL, ATEX, IECEx
Ex markingATEX:
II 3 G Ex nA IIC T4 Gc
IECEx:
Ex ec IIC T4 Gc