Quantity(1) LVS LUT-SHUNT-D White Relay for 0-10V & Line Voltage Applications DPDT 20A. 

Application: In the past, all emergency lights were left on 24 hours a day to meet safety codes. Now you can specify & install a UL924 Listed Emergency Shunt Relay LUT-SHUNT-D, which converts up to 20A of normal light fixtures to approved emergency lights. During normal operation, the LUT-SHUNT-D dims designated emergency lights with the same control as your normal lights. During a utility power interruption, the LUT-SHUNT-D turns designated emergency lights on, at full brightness, regardless of dimmer position. The LUT-SHUNT-D can simultaneously bypass both a line voltage switch and a 0-10V dimming signal, ensuring that an emergency fixture illuminates at full brightness during a utility power interruption.

LUT-SHUNT-D includes: 
  • 20A Rated N/O & N/C: Used for bypassing line voltage switching, occupancy sensors or dimmers. Also used as dry contact to signal relay panels or BMS systems or utility power interruption
  • 1A Rated N/O Contact: Used for bypassing low voltage dimming or switching signals from room controllers or dimmers
  • Integral test switch and green utility power indicator 
  • UL924 Listed
Specifications:
  • Sensing Input: 120V-277V
  • Load Rating: 120V-277V (20A)
  • Ballast Load Rating: 20A(120V-277V)(Contact #1)
  • Incandescent Load Rating: 1200W (120V) / 1500W (277V)
  • Load: Contact #1 20A (120-277V), Contact #2 1A (30V DC)