Quantity(1) LVS LUT-SHUNT-D White Relay for 0-10V & Line Voltage Applications DPDT 20A.
Application: In the past, all emergency lights were left on 24 hours a day to meet safety codes. Now you can
specify & install a UL924 Listed Emergency Shunt Relay LUT-SHUNT-D, which converts up to
20A of normal light fixtures to approved emergency lights. During normal operation, the
LUT-SHUNT-D dims designated emergency lights with the same control as your normal lights. During
a utility power interruption, the LUT-SHUNT-D turns designated emergency lights on, at full brightness, regardless of dimmer position. The LUT-SHUNT-D can simultaneously bypass
both a line voltage switch and a 0-10V dimming
signal, ensuring that an emergency fixture
illuminates at full brightness during a utility power
interruption.
LUT-SHUNT-D includes:
- 20A Rated N/O & N/C: Used for bypassing line voltage switching,
occupancy sensors or dimmers. Also used as dry
contact to signal relay panels or BMS systems or
utility power interruption
- 1A Rated N/O Contact: Used for bypassing low voltage dimming or
switching signals from room controllers or
dimmers
- Integral test switch and green utility power
indicator
- UL924 Listed
Specifications:- Sensing Input: 120V-277V
- Load Rating: 120V-277V (20A)
- Ballast Load Rating: 20A(120V-277V)(Contact #1)
- Incandescent Load Rating: 1200W (120V) / 1500W (277V)
- Load: Contact #1 20A (120-277V), Contact #2 1A (30V DC)
Item is new in box. Please review the pictures, no returns. Thank you!!!