ETCR4000A Intelligent Double Clamp Digital Phase Voltmeter CT Size Φ8mm
Notice:
The standard package don't include batteries.Because,the international air shipping forbid to ship liquid,powder and batteries,we can not put them in the package box.Hope you can understand buy them in your local store or supermarket.
At the same time, please forgive us that we are unable to provide the English user manual. If you need it, please contact the customer service after purchase.
Thanks for your support!
Product Main Function
1. Simultaneous measurement of two channel AC current, range: 0.0mA~20.0A
2. Simultaneous measurement of two channel AC voltage, range: 0.00V~600V
3. Simultaneous measurement the phase between UU, II, UI, range: 0.0°~360.0°
4. Measurement frequency, phase sequence, active power, reactive power, apparent power, power factor and others parameters.
5. Judge transformer group, inductive, capacitive circuit, overhaul line device.
6. Line Voltage: below 600V
7. CT Size: Φ8mm
ETCR4000A Intelligent Double Clamp Digital Phase Voltmeter is a well-developed full-automatic, multi-functional, digital, intelligent meter specifically designed for field testing, which is a overall upgrade product based on mechanical knob phase volt-ampere meter, can simplify operation and reduce the possibility of misoperation, featuring high accuracy, high stability, low power consumption, easiness to use and so on. It can directly measure AC voltage and AC current without opening the measured circuit, phases between three voltages, three currents and phase between the voltage and current; in addition, the power factor and power of the circuit can be indirectly measured, it can also be used to distinguish three-phase sequence, transformer wiring group, inductive and capacitive circuits, test second circuit and bus differential protection systems, read the phase relationship between CTs of the differential protection, check the meter wiring right, repair lines and equipment, etc. Apply to electric power, petroleum chemical industry, metallurgy, railway, and meteorology, industrial and mining enterprises, scientific research institutions, measurement sector and so on. Especially for the electricity billing system and relay protection system, and electricity measurement, electricity check, power inspection for power marketing department. Assembling, relay protection, differential detection, start experiment, substation overhaul, or power practical training, skills match for biotech department.
ETCR4000A Intelligent Double Clamp Digital Phase Voltmeter has well designed shell mould made of newest material, attach with shakeproof, skidproof, high insulation sheath, has a 240dots×160dots LCD screen, all the test data display on the screen simultaneously, vector diagram indication, and looks exquisite and comfortable. Meter equipped with USB-RS232 interface, can store 1500 sets of data, through the system software upload stored data to the computer, implementing online real-time monitoring and historical inquires, dynamic display. Can read, save, report, print history data, etc. Its small mouth clamps are suitable for line densely places.
ETCR4000A Intelligent Double Clamp Digital Phase Voltmeter aliases: full-automatic double-clamp digital phase voltmeter, multi-functional double-clamp digital phase voltmeter, full-automatic phase voltmeter, digital phase voltmeter, including the functions of the general mechanical double-clamp digital phase voltmeter, suitable for electric power, petrochemical, metallurgy, railway, industrial and mining enterprises, scientific research institutions, measurement departments.Especially suitable for electric energy billing system and relay protection system, its power supply Marketing Department of electric energy measurement, electricity inspection, electric power inspection, the production and technology department of the table connected to electricity, relay protection, differential detection, starting test, transformation maintenance, or electric power training, skills and so on.
|
Function
|
Measure two channel AC voltages, current, phase between voltages, phase between currents, phase, frequency, phase sequence, active power, reactive power, apparent power, and power factor between voltage and current. Discriminate the transformer wiring group, inductive and capacitive circuits, test the secondary circuit and the busbar protection system, read the phase relationship between the CTs of the differential protection groups, check the wiring of the meter for correctness, and repair the line equipment, etc.
|
|
Power Supply
|
DC 9V Alkaline dry battery LR14 1.5V 6 PCS
|
|
Clamp
|
Sharp-nose current clamp: 7.5mm×13mm
|
|
Range(Automatic)
|
Voltage:AC 0.00V~600V ;
|
|
Current:AC 0.0mA~20.0A;
|
|
Phase:0.0°~360.0°;
|
|
Frequency:45.00Hz~65.00Hz;
|
|
Active power:0.0W~12kW;
|
|
Reactive power :0.0VAR~12kVAR;
|
|
Apparent Power:0.0VA~12kVA;
|
|
Power factor:-1~+1;
|
|
Resolution
|
Voltage:AC 0.01V
|
|
Current:AC 0.1mA
|
|
Phase:0.1°
|
|
Frequency:0.01Hz
|
|
Active Power:0.1W
|
|
Reactive power:0.1VAR
|
|
Apparent Power:0.1VA
|
|
Power factor:0.001
|
|
Date Storage
|
1200 groups
|
|
RS232 Interface
|
USB-RS232 interface, the stored data upload computer, convenient to analyze management data
|
|
Power Consumption
|
Open backlight with Max power consumption135mA, the battery continues working 6 hours
|
|
Close backlight,the meter power consumption 90mA,the battery continuesworking 9 hours
|
|
Display Mode
|
2.8 inch color LCD screen, display area: 58mm×44mm
|
|
Meter Diamension
|
196mm×92mm×54mm
|
|
Test Rate
|
About 2 second/times
|
|
Data Hold
|
In measurement, press HOLD key to hold data,“DH” symbol display
|
|
Auto Shut Down
|
15 minutes after boot up, the meter shuts down automatically without any operation, to reduce battery consumption
|
|
Backlight Function
|
Yes, stuitable for dark place and use at night; it will close backlight after 5 minutes without any operation
|
|
Voltage Detection
|
When the battery voltage is lower than 7.2V, low battery symbol display,and remind to replace the battery.
|
|
Instrument Weight
|
Host: 550g
|
|
Current Clamp: 170gX2
|
|
Test Wires: 250g
|
|
Test Wire Length
|
1.5m
|
|
Current Clamp wire Length
|
2mX φ4mm
|
|
Working Temperature
|
-10℃~40℃;below 80%rh
|
|
Store Temperature
|
-10℃~60℃;below 70%rh
|
|
Input Impedance
|
Test voltage input impedance is:1MΩ
|
|
Withstanding Voltage
|
It took 1 minute to withstand 1000V/50Hz sine wave AC voltage between the meter line and the out shell.
|
|
Insulation
|
Between the meter line and the out shell ≥ 100MΩ
|
|
Structure
|
Double insulated, with insulated vibration-proof jacket
|
|
Suitable Safety Standard
|
IEC61010-1 CAT Ⅲ 600V,IEC61010-031,IEC61
|
|
Model
|
Shift
|
CT Size
|
Current Range
|
Voltage Range
|
Communication Interface
|
Data Storage
|
|
ETCR4000
|
manual control
|
Φ8mm
|
0.0mA~10A
|
0~500V
|
-
|
-
|
|
ETCR4000A
|
automatic
|
Φ8mm
|
0.0mA~20.0A
|
0~600V
|
USB-RS232 interface
|
1200 groups
|
|
ETCR4100
|
manual control
|
Φ8mm
|
-
|
-
|
-
|
-
|
|
ETCR4200
|
automatic
|
35x40mm
|
0.0mA~600A
|
0~600V
|
USB-RS232 interface
|
1200 groups
|
|
Package
|
Outer Package
|
Carton
|
|
Inner Package
|
Aluminum box
|
|
Accessory
|
Host
|
1 PCS
|
|
Instrument Case
|
1 PCS
|
|
Current Clamp
|
2 PCS
|
|
Test Wires
|
4 PCS(red 2 pcs,black 2pcs )
|
|
Data Cable
|
1 PCS
|
|
Manual , Warranty Card ,Certificate
|
1 SET
|