| Range | TeSys TeSys Deca |
|---|---|
| Product name | TeSys D TeSys DF |
| Type of product or component | Connector |
| Device short name | LC1D |
| contactor application | resistive load Engine control |
| employment category | AC-3 AC-4 AC-1 AC-4 |
| Number of poles | 3P |
| power pole contact composition | 3 NA |
| [Ue] Nominal operating voltage | Power circuit, state 1 <= 690 V AC 25...400 Hz Power circuit, state 1 <= 300 V direct current |
| [Ie] Nominal operating current | 25 A 60 °C) at <= 440 V AC AC-1 for power circuit 12 A 60 °C) at <= 440 V AC AC-3 for power circuit 12 A 60 °C) at <= 440 V AC AC-4 for power circuit |
| engine power in kW | 3 kW at 220...230 V AC 50/60 Hz - cable type: AC-3) 5.5 kW at 380...400 V AC 50/60 Hz - cable type: AC-3) 5.5 kW at 415...440 V AC 50/60 Hz - cable type: AC-3) 7.5 kW at 500 V AC 50/60 Hz - cable type: AC-3) 7.5 kW at 660...690 V AC 50/60 Hz - cable type: AC-3) 3.7 kW at 400 V AC 50/60 Hz - cable type: AC-4) 3 kW at 220...230 V AC 50/60 Hz - cable type: AC-4) 5.5 kW at 380...400 V AC 50/60 Hz - cable type: AC-4) 5.5 kW at 415...440 V AC 50/60 Hz - cable type: AC-4) 7.5 kW at 500 V AC 50/60 Hz - cable type: AC-4) 7.5 kW at 660...690 V AC 50/60 Hz - cable type: AC-4) |
| motor power HP (UL/CSA) | 0.5 hp at 115 V AC 50/60 Hz for 1 phase motor 2 hp at 230/240 V AC 50/60 Hz for 1 phase motor 3 hp at 200/208 V AC 50/60 Hz for 3 phase motor 3 hp at 230/240 V AC 50/60 Hz for 3 phase motor 7.5 hp at 460/480 V AC 50/60 Hz for 3 phase motor 10 hp at 575/600 V AC 50/60 Hz for 3 phase motor |
| control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 110V AC 50/60Hz |
| composition of auxiliary contacts | 1 NO + 1 NC |
| [Uimp] Resistance to voltage spikes | 6 kV according to IEC 60947 |
| Overvoltage category | III |
| [Ith] Conventional thermal current | 25 A at <60°C for power circuit 10 A at <60 °C for signaling circuit |
| Irms nominal connection power | 250 A at 440 V for power circuit according to IEC 60947 140 A AC for signaling circuit according to IEC 60947-5-1 250 A direct current for signaling circuit according to IEC 60947-5-1 |
| Assigned cutting power | 250 A at 440 V for power circuit according to IEC 60947 |
| [Icw] Allowable temporary current | 105 A at <40 °C - 10 s for power circuit 210 A at <40 °C - 1 s for power circuit 30 A at <40 °C - 10 min for power circuit 61 A at <40°C - 1 min for power circuit 100 A - 1 s for signaling circuit 120 A - 500 ms for signaling circuit 140 A - 100 ms for signaling circuit |
| associated fuse | 10 A gG for signaling circuit according to IEC 60947-5-1 40 A gG at <= 690 V coordination type 1 for power circuit 25 A gG at <= 690 V coordination type 2 for power circuit |
| average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| [Ui] Rated insulation voltage | Power circuit, state 1 690 V according to IEC 60947-4-1 Power circuit, state 1 600 V CSA certified Power circuit, state 1 600 V UL certified Signaling circuit, state 1 690 V according to En> 40 A Signaling circuit, state 1 600 V CSA certified Signaling circuit, state 1 600 V UL certified |
| Electrical durability | 2 Mcycles 12 A AC-3 in Ue <= 440 V 0.8 Mcycles 25 A AC-1 at Ue <= 440 V 2 Mcycles 12 A AC-4 in Ue <= 440 V |
| power dissipated per pole | 0.36W AC-3 1.56W AC-1 0.36W AC-4 |
| front cover | With |
| Mounting bracket | Lane Plate |
| standards | CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 IEC 60335-1 |
| Product certifications | CCC B.V. CSA G.L. U.L. FIGHT GOST LROS (Lloyds Register of Shipping) DNV UKCA |
| Connection type | Power circuit, state 1 Screw terminals 1 cable(s) 1…4 mm²flexible without cable end Power circuit, state 1 Screw terminals 2 cable(s) 1…4 mm²flexible without cable end Power circuit, state 1 Screw terminals 1 cable(s) 1…4 mm²flexible with cable end Power circuit, state 1 Screw terminals 2 cable(s) 1…2.5 mm²flexible with cable end Power circuit, state 1 Screw terminals 1 cable(s) 1…4 mm²solid without cable end Power circuit, state 1 Screw terminals 2 cable(s) 1…4 mm²solid without cable end Control circuit, state 1 Screw terminals 1 cable(s) 1…4 mm²flexible without cable end Control circuit, state 1 Screw terminals 2 cable(s) 1…4 mm²flexible without cable end Control circuit, state 1 Screw terminals 1 cable(s) 1…4 mm²flexible with cable end Control circuit, state 1 Screw terminals 2 cable(s) 1…2.5 mm²flexible with cable end Control circuit, state 1 Screw terminals 1 cable(s) 1…4 mm²solid without cable end Control circuit, state 1 Screw terminals 2 cable(s) 1…4 mm²solid without cable end |
| tightening torque | Power circuit, state 1 1.7 Nm - on screw terminals - with Ø 6 flat screwdriver Power circuit, state 1 1.7 Nm - on screw terminals - with Philips #2 screwdriver Control circuit, state 1 1.7 Nm - on screw terminals - with Ø 6 flat screwdriver Control circuit, state 1 1.7 Nm - on screw terminals - with Philips #2 screwdriver Control circuit, state 1 1.7 Nm - on screw terminals - with pozidriv screwdriver No 2 Power circuit, state 1 2.5 Nm - on screw terminals - with pozidriv screwdriver No 2 |
| Maneuver duration | 12...22 ms closing 4...19 ms opening |
| security reliability level | B10d = 1369863 contactor cycles with rated load according to EN/ISO 13849-1 B10d = 20000000 contactor cycles with mechanical load according to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| operating range | 3600 cyc/h at <60°C |
| coil characteristic | Without parasitic filter as standard |
|---|---|
| control circuit voltage limits | 0.3...0.6 Uc -40…70 °C AC disconnection 50/60 Hz 0.8...1.1 Uc -40…60 °C operating AC 50 Hz 0.85...1.1 Uc -40…60 °C operating AC 60 Hz 1...1.1 Uc 60…70 °C operational AC 50/60 Hz |
| On-call consumption in VA | 70 VA 60 Hz 0.75 20 °C) 70 VA 50 Hz 0.75 20 °C) |
| maintenance consumption in VA | 7.5 VA 60 Hz 0.3 20 °C) 7VA 50Hz 0.3 20°C) |
| heat dissipation | 2…3 W at 50/60 Hz |
| type of auxiliary contacts | Mechanically linked type 1 NO + 1 NC according to IEC 60947-5-1 mirror contact type 1 NC according to IEC 60947-4-1 |
| signaling circuit frequency | 25...400 Hz |
| minimum switching current | 5 mA for signaling circuit |
| minimum switching voltage | 17 V for signaling circuit |
| non-overlap time | 1.5 ms in de-excitation between NO and NC contact 1.5 ms in excitation between NO and NC contact |
| insulation resistance | > 10 MOhm for signaling circuit |