The LMZC-301 zone controller provides power and connectivity to Digital Lighting Management (DLM) fixture controllers as well as switches, occupancy sensors, daylight sensors, and input modules. It is the foundation of a DLM local network for fixture controllers and includes integral segment network connectivity. The zone controller can be used to enable the automation of lighting functions across a facility.
Features/Specifications:
- Two free-topology DLM Category 5e local networks for DLM load controllers, sensors, switches, and LMIO series input modules
- Supports up to 94 DLM communicating devices and up to 64 connected loads
- Runs event-based schedule routines independently (does not require BAS or Network Controller)
- Supports astronomical, time-based, and photocell-based event types
- This product meets the materials restrictions of RoHS
- Input voltage: 115/277VAC; 60 Hz
- Class 2 connection to two independent DLM local networks: 24VDC output, up to 250mA across 2 RJ45 ports per local network, or up to 400mA per network with optional LMPB-100 power booster (max. 800mA with two LMPB-100s installed)
- Free-topology DLM local network segments may include digital load controllers, switches and sensors; Cat 5e cable, 150’ per device to 1,000’ max, per each local network
- Removable terminal for connection to DLM segment network (BACnet MS/TP)
- Segment network parameters:
- – Wattstopper LM-MSTP wire (required)
- – Linear topology; 4000 ft. maximum per segment
- Upon loss of power, date and time info is maintained for 14+ days. Programming info (including schedules) is maintained for the life of the product.
- Operating conditions: for indoor use only; 32-122°F (0-50°C); 5-95% RH, non-condensing
- UL and cUL listed (E207852)
- FCC part 15 compliant
Item is new in box. Please review the pictures, no returns. Thank you!!!