Quantity(1) Legrand Wattstopper LMZC-301 DLM Zone Controller Scheduler & Network Interface. 

The LMZC-301 zone controller provides power and connectivity to Digital Lighting Management (DLM) fixture controllers as well as switches, occupancy sensors, daylight sensors, and input modules. It is the foundation of a DLM local network for fixture controllers and includes integral segment network connectivity. The zone controller can be used to enable the automation of lighting functions across a facility.

Features/Specifications:
  • Two free-topology DLM Category 5e local networks for DLM load controllers, sensors, switches, and LMIO series input modules
  • Supports up to 94 DLM communicating devices and up to 64 connected loads
  • Runs event-based schedule routines independently (does not require BAS or Network Controller)
  • Supports astronomical, time-based, and photocell-based event types
  • This product meets the materials restrictions of RoHS
  • Input voltage: 115/277VAC; 60 Hz
  • Class 2 connection to two independent DLM local networks: 24VDC output, up to 250mA across 2 RJ45 ports per local network, or up to 400mA per network with optional LMPB-100 power booster (max. 800mA with two LMPB-100s installed)
  • Free-topology DLM local network segments may include digital load controllers, switches and sensors; Cat 5e cable, 150’ per device to 1,000’ max, per each local network
  • Removable terminal for connection to DLM segment network (BACnet MS/TP)
  • Segment network parameters: 
  • – Wattstopper LM-MSTP wire (required) 
  • – Linear topology; 4000 ft. maximum per segment
  • Upon loss of power, date and time info is maintained for 14+ days. Programming info (including schedules) is maintained for the life of the product.
  • Operating conditions: for indoor use only; 32-122°F (0-50°C); 5-95% RH, non-condensing
  • UL and cUL listed (E207852)
  • FCC part 15 compliant


                                        Item is new in box.  Please review the pictures, no returns.  Thank you!!!