The HS replaceable humidity element is designed to lower costs and
reduce downtime. It features thin-film capacitive technology for superior
accuracy and exceptional resistance to contaminants. It is compatible with all
Veris sensors, making replacement quick and easy. No need to install a new
humidity sensing device, just insert a new element into the unit and resume
operation.
5% accuracy
Specifications
- HS Element Digitally profiled
thin-film capacitive (32 bit mathematics) U.S. Patent 5,844,138
- Accuracy at 25°C ±1%, 2%, 3%, or
5%(specify) @ 10 to 80% RH; Multi-point calibration, NIST traceable
- Reset Rate* 24 hours
- Stability ±1% @ 20°C (68°F)
annually, for two years
- Operating Humidity Range 0 to 100%
RH (non-condensing)
- Temperature Coefficient ±0.1%RH/
°C above or below 25°C (typically)
- Analog Output 4-20mA version:
2-wire, polarity insensitive (clipped and capped); 0-5V/0-10V Versions:
3-wire, observe polarity
- Scaling 0–100% RH
- Operating Temperature Range -50°
to 50°C(-58° to 122°F)
- Input Power 4-20mA version: loop
powered 12-30VDC only, 30mA max.; 0-5V/0-10V versions: 12-30VDC/24VAC,
15mA max.
- Optional Temperature Transmitter
Output Digital, 4-20mA, (clipped and capped) or 0-5V/0-10V output;
accuracy ±0.5°C (±1%°F) typically
- EMC Conformance - CE option EN50081-1,
EN 50082-1, EN 61000-4-5, EN 61000-4-3, ENV 50204, EN 61000-4-6
- Range 10° - 35°C (50° - 95°F)
*Reset Rate is the time required to recover the
50% RH after exposure to 90%RH for 24 hours.**Specified accuracy with 24VDC
supplied power with rising humidity. RTD/Thermistors are not compensated for
internal heating of product. One side of transformer secondary is connected to
signal common, so an Isolation transformer or dedicated power supply may be
required. Shielded cabling is required for conformance to EMC standards.
Technical information is available from factory upon request.