K121 is a performant universal converter able to manage all analog signals (mA, mV, V, PT100, Pt1000, Pt500, Ni100, TCs, Ohm) and convert / isolate it into 4..20mA loop powered signal. The output mode (normal/inverted), scale overrange, output in case of fault sensor are selectable parameters available by PC software. A 2-way galvanic isolation among input // output circuits assures the integrity of your datas. K121 is ATEX compliant product II 3G Ex nA IIC T4 Gc X (gas) II 3D Ex tc IIIC T135°C Dc X (dust).
"International buyers – please note: Import duties, taxes, and charges aren't included in the item price or postage cost. These charges are the buyer's responsibility.
"Please check with your country's customs office to determine what these additional costs will be prior to bidding or buying."
| GENERAL DATA | |
| Power Supply | 7..30 Vdc (from loop 4..20mA) |
| Side Power | - |
| Hot swapping | yes |
| Current consumption | 24 mA |
| Power consumption | < 660 mW |
| A/D Conversion | 16 bit |
| Rejection | 50 o 60 Hz (configurable) |
| Settings | software (EASY) |
| Filter | Added for stable reading |
| Dimensions (w x h x d) | 6,2 x 93,1 x 102,5 mm |
| Isolation | 1,5 KVac (3-way |
| Isolation technique | Digital (optocoupler) |
| Data processing | 32 bit floating point |
| Colour | black |
| Enclosure | PBT |
| Weght | 45 g |
| Operating temperature | -20..+65 °C |
| Connections | 8 Clamp terminals |
| Protection degree | IP 20 |
| Precision class | 0,10% |
| Thermal drift | < 120 ppm/K |
| Status indicators | Fault, alarm |
| Special functions | Cold junction compensation Filter Reversed output |
| Approvals | CE, II 3G Ex nA IIC T4 Gc X, II 3D Ex tc IIIC T135°C Dc X |
| Norms | Safety (EN 61010-1), EMC (EN 61000-6-2, EN 61000-6-4, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-11), Atex (EN 60079-0, EN 60079-15) |
| INPUT DATA | |
| Channels | 1 |
| Type | Type THERMOCOUPLE J, K, R, S, T, E, B, N (EN 60584) RTD (PT100, PT500, PT1000, NI100) connection 2,3,4 wires Voltage (V) ± 30V, impedance 200 kO Voltage (mV) ±150 mV, impedance 10 MO Current: ±24 mA, impedance 40 O Potentiometer: 500 O..10 KO Resistance: up to 1760 O |
| OUTPUT DATA | |
| Channels | 1 |
| Type | CURRENT 4..20mA |
| Response time (10-90%) | 140..620ms |