Universal Converter (RTD/ TC/ Ohmm/ mA/ V) to 4-20mA (loop powered)

K121 is a performant universal converter able to manage all analog signals (mA, mV, V, PT100, Pt1000, Pt500, Ni100, TCs, Ohm) and convert / isolate it into 4..20mA loop powered signal. The output mode (normal/inverted), scale overrange, output in case of fault sensor are selectable parameters available by PC software. A 2-way galvanic isolation among input // output circuits assures the integrity of your datas. K121 is ATEX compliant product II 3G Ex nA IIC T4 Gc X (gas) II 3D Ex tc IIIC T135°C Dc X (dust).

    Specifications:
  • Conversion and transmission of the input read into a normalized signal current in the output for the loop 4 ..20 mA that is connected with 2 wire connection.
  • Thermocouple input J, K, R, S, T, B, E, N ( EN 60584 ).
  • RTD input (PT100 - 500 - 1000, Ni100) with 2, 3 o 4 wire connections.
  • Voltage input ± 30 V.
  • Voltage input ± 150 mV
  • Current input ± 24 mA.
  • Potentiometer input with resistance between 500 ? and 10 K?.
  • Resistance input up to 1760 ?.
  • Reduced response time (Voltage and Current input): 140 ms
  • Reduced response time (Other inputs): < 620 ms
  • High precision: 0,1%.
  • 16-bit measurement conversion.
  • 500 Vac output isolation.
  • Compact size 93 x 102,5 x 6,2 mm

"International buyers – please note: Import duties, taxes, and charges aren't included in the item price or postage cost. These charges are the buyer's responsibility.

"Please check with your country's customs office to determine what these additional costs will be prior to bidding or buying."

    
GENERAL DATA
Power Supply7..30 Vdc (from loop 4..20mA)
Side Power-
Hot swappingyes
Current consumption24 mA
Power consumption < 660 mW
A/D Conversion16 bit
Rejection50 o 60 Hz (configurable)
Settingssoftware (EASY)
FilterAdded for stable reading
Dimensions (w x h x d)6,2 x 93,1 x 102,5 mm
Isolation1,5 KVac (3-way
Isolation techniqueDigital (optocoupler)
Data processing32 bit floating point
Colourblack
EnclosurePBT
Weght45 g
Operating temperature-20..+65 °C
Connections8 Clamp terminals
Protection degreeIP 20
Precision class0,10%
Thermal drift< 120 ppm/K
Status indicatorsFault, alarm
Special functionsCold junction compensation
Filter
Reversed output
ApprovalsCE, II 3G Ex nA IIC T4 Gc X, II 3D Ex tc IIIC T135°C Dc X
NormsSafety (EN 61010-1), EMC (EN 61000-6-2, EN 61000-6-4, EN 61000-4-2, EN 61000-4-3, EN 61000-4-4, EN 61000-4-5, EN 61000-4-6, EN 61000-4-11), Atex (EN 60079-0, EN 60079-15)
INPUT DATA
Channels1
Type Type THERMOCOUPLE J, K, R, S, T, E, B, N (EN 60584)
RTD (PT100, PT500, PT1000, NI100) connection 2,3,4 wires
Voltage (V) ± 30V, impedance 200 kO
Voltage (mV) ±150 mV, impedance 10 MO
Current: ±24 mA, impedance 40 O
Potentiometer: 500 O..10 KO
Resistance: up to 1760 O
OUTPUT DATA
Channels1
Type CURRENT 4..20mA
Response time (10-90%)140..620ms