The Carrier HN680173 Electrical Contactor features an Eaton DILM12-10 three-pole power contactor with a 24V AC, 50/60Hz operating coil and one normally open auxiliary contact.
Designed for electrical switching applications, this contactor allows a compatible equipment control circuit to energize and de-energize three-phase electrical loads.
The Eaton contactor is identified by the markings DILM12-10 and XTCE012B10. Its three main power poles and integrated normally open auxiliary contact provide switching functionality for compatible HVAC equipment.
The contactor carries an AC-3 operational rating of 12A at 400V and an AC-1 conventional thermal current rating of 22A.
BRAND NEW IN ORIGINAL FACTORY BOX.
CARRIER REPLACEMENT PART
Listed under Carrier part number HN680173.
EATON CONTACTOR
Manufacturer-marked DILM12-10 / XTCE012B10.
24V AC OPERATING COIL
Designed for compatible 50/60Hz control circuits.
THREE MAIN POWER POLES
Three-pole electrical switching configuration.
INTEGRATED AUXILIARY CONTACT
One normally open contact, terminals 13 and 14.
12A AC-3 RATING
Motor-duty operational current rating at 400V.
22A AC-1 RATING
Conventional thermal current rating for the specified utilization category.
COMMERCIAL HVAC APPLICATION
Suitable for compatible equipment requiring the specified contactor configuration.
FREE SHIPPING
Carefully packaged for delivery within the contiguous United States.
| SPECIFICATION | DETAILS |
|---|---|
| Carrier Part Number | HN680173 |
| Contactor Manufacturer | Eaton |
| Contactor Model | DILM12-10 |
| Additional Marking | XTCE012B10 |
| Product Type | Power Contactor |
| Main Poles | 3 |
| Auxiliary Contacts | 1 Normally Open (13-14) |
| Coil Voltage | 24V AC |
| Coil Frequency | 50/60Hz |
| AC-3 Rating at 400V | 12A |
| AC-1 Conventional Thermal Current | 22A |
| UL Maximum Operating Voltage | 600V AC |
| 3-Phase Motor Rating at 460/480V | 10 HP |
| 3-Phase Motor Rating at 575/600V | 10 HP |
| Insulation Voltage (IEC) | 800V |
| Applicable Standard | IEC/EN 60947-4-1 |
| Condition | Brand New |
| Packaging | Original Factory Box |
Ratings are based on the markings visible on the actual Eaton contactor. Select the appropriate rating for the application, utilization category, supply voltage, and motor load.
| TERMINALS | FUNCTION |
|---|---|
| 1L1 / 2T1 | Main Pole 1 |
| 3L2 / 4T2 | Main Pole 2 |
| 5L3 / 6T3 | Main Pole 3 |
| 13NO / 14NO | Normally Open Auxiliary |
| A1 / A2 | 24V AC Operating Coil |
The Carrier HN680173 contactor is identified in replacement-parts catalogs for selected Carrier commercial HVAC equipment, including certain 30XVA and 30XVB chiller configurations.
Distributor equipment model references include:
| MODEL NUMBER | MODEL NUMBER |
|---|---|
| C30XVA300GM | C30XVA4509H |
| C30XVA450KM | C30XVB300GM |
| C30XVB4501H | C30XVB450KM |
| C30XVB2252M | C30XVA45AJM |
These are distributor model references and do not guarantee compatibility with every configuration or serial-number range.
Before ordering, verify the original equipment part number, complete equipment model and serial number, coil voltage, contact configuration, and applicable electrical ratings.
Similar-looking contactors may have different coils, auxiliary contacts, or electrical ratings and should not be assumed interchangeable.
This listing is for one brand-new Carrier HN680173 replacement contactor featuring an Eaton DILM12-10 contactor.
Carrier Part Number: HN680173
Contactor Manufacturer: Eaton
Model: DILM12-10
Coil: 24V AC, 50/60Hz
Condition: Brand New
Packaging: Original Factory Box
Quantity: One (1)
Carrier Part Number: HN680173
Component: Eaton DILM12-10 Three-Pole Contactor
Auxiliary Contact: One Normally Open
Coil: 24V AC, 50/60Hz
Condition: Brand New
Packaging: Original Factory Box
Separate overload relays, auxiliary contact blocks, mounting accessories, and installation tools are not included unless shown in the actual product photographs.
Installation should be performed by a qualified electrician or HVAC service technician experienced with commercial electrical equipment.
Disconnect and lock out all electrical power sources before servicing. Verify the absence of voltage with appropriate test equipment.
Confirm the correct coil voltage, contact ratings, overload protection, terminal configuration, and manufacturer-approved replacement requirements before installation.
Follow all applicable electrical codes and equipment manufacturer service instructions.
Incorrect selection or wiring may cause equipment damage, electrical hazards, or personal injury.
Your contactor will ship in its original factory box with appropriate protective outer packaging.
Free standard shipping within the contiguous 48 United States.
If your shipment arrives with visible damage, retain all packaging and contact BW Salvage through your eBay order.
At BW Salvage, we believe quality HVAC equipment and replacement components should be available at exceptional value.
We specialize in competitively priced HVAC parts with clear product information and straightforward purchasing terms.
Whether you're an HVAC contractor, service technician, maintenance professional, or equipment owner, we appreciate your business.
WE SALVAGE YOU SAVE!