| Technical data | EL3062 |
|---|---|
| Number of inputs | 2 (single-ended) |
| Power supply | via the E-bus |
| Signal voltage | 0…10 V |
| Distributed clocks | – |
| Internal resistance | > 130 kΩ |
| Input filter limit frequency | 1 kHz |
| Dielectric strength | max. 30 V |
| Conversion time | 0.625 ms default setting, configurable, multiplex |
| Resolution | 12 bit (16 bit presentation incl. sign) |
| Measurement error/uncertainty | < ±0.3% (relative to full scale value) |
| Electrical isolation | 500 V (E-bus/signal voltage) |
| Current consumption E-bus | typ. 130 mA |
| Current consumption power contacts | – |
| Bit width in the process image | inputs: 8 byte |
| Special features | activatable FIR/IIR filters, limit value monitoring |
| Weight | approx. 60 g |
| Operating temperature | -25…+60°C |
| Storage temperature | -40…+85°C |
| Relative humidity | 95%, no condensation |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Pluggable wiring | for all ESxxxx terminals |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, CCC, ATEX, IECEx |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |