NEW! NEVER USED!
IN ITS ORIGINAL PACKAGING!!!!

NUOVO! MAI USATO!
NELLA SUA CONFEZIONE ORIGINALE!!!!
Short description
I/O module4 safe type A digital outputs, with current monitoring, 24 VDC, 0.5 A, OSSD <500 µs
General information
B&R ID code0x1DBE
System requirements
Automation Studio3.0.71 or later
Automation Runtime2.95 or later
SafeDESIGNER2.58 or later
Safety Release1.1 or later
mapp Technology Package mapp Safety 5.7.0 or later
Status indicatorsI/O function per channel, operating state, module status
Diagnostics
Module run/errorYes, using LED status indicator and software
OutputsYes, using LED status indicator and software
Blackout mode
ScopeModule
FunctionModule functionality
Standalone modeNo
Max. I/O cycle time800 µs
Power consumption
Bus0.25 W
Internal I/O1.3 W
Additional power dissipation caused by actuators (resistive) [W] 0.24
Electrical isolation
Channel - BusYes
Channel - ChannelNo
Certifications
CEYes
UKCAYes
Functional safetycULus FSPC E361559
Energy and industrial systems
Certified for functional safety
ANSI UL 1998:2013
Functional safetyIEC 61508:2010, SIL 3
EN 62061:2005/A2:2015, SIL 3
EN ISO 13849-1:2015, Cat. 4 / PL e
IEC 61511:2004, SIL 3
Functional safetyEN 50156-1:2004
ATEXZone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
ULcULus E115267
Industrial control equipment
HazLoccCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNVTemperature: A(0 to 45°C)
Humidity: B(up to 100%)
Vibration: A(0.7 g)
EMC: B(bridge and open deck)
CCSYes
LRENV1
KRYes
ABSYes
BVEC21B
Temperature: 5 - 45°C
Vibration: 0.7 g
EMC: Bridge and open deck
KCYes
Safety characteristics
EN ISO 13849-1:2015
CategoryCat. 3 if parameter "Disable OSSD = Yes - Warning",
Cat. 4 if parameter "Disable OSSD = No" 
PLPL d if parameter "Disable OSSD = Yes - Warning",
PL e if parameter "Disable OSSD = No" 
DC>60% if parameter "Disable OSSD = Yes - Warning",
>94% if parameter "Disable OSSD = No" 
Mission timeMax. 20 years
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
SIL CLSIL 2 if parameter "Disable OSSD = Yes - Warning",
SIL 3 if parameter "Disable OSSD = No" 
SFF>60% if parameter "Disable OSSD = Yes - Warning",
>90% if parameter "Disable OSSD = No" 
PFH / PFHd
openSAFETY wiredNegligible
openSAFETY wireless<1*10-14* Number of openSAFETY packets per hour
Proof test interval (PT)20 years
Safe digital outputs
EN ISO 13849-1:2015
MTTFD per channel100 years if parameter "Disable OSSD = Yes - Warning",
2500 years if parameter "Disable OSSD = No" 
IEC 61508:2010,
IEC 61511:2004,
EN 62061:2013
PFH / PFHd per channel<5*10-8if parameter "Disable OSSD = Yes - Warning",
<1*10-10if parameter "Disable OSSD = No" 
PFD per channel<1*10-3if parameter "Disable OSSD = Yes - Warning",
<2*10-5if parameter "Disable OSSD = No" 
I/O power supply
Nominal voltage24 VDC
Voltage range24 VDC -15% / +20%
Integrated protectionReverse polarity protection
Safe digital outputs
Quantity4
VariantFET, 1x positive switching, 1x negative switching, type A, output level readable, open-circuit detection
Nominal voltage24 VDC
Nominal output current0.5 A
Total nominal current2 A
Output protectionSee section "Inrush current behavior for output channels".
Braking voltage when switching off inductive loadsMax. 90 VDC 
Open-circuit detectionVia internal current measurement,
output current <10 mA: Signal "CurrentOK" = FALSE,
output current 10 to 50 mA: Signal "CurrentOK" = Undefined,
output current >50 mA: Signal "CurrentOK" = TRUE
Error detection time1 s
Insulation voltage between channel and bus500 Veff
Peak short-circuit currentSee section "Inrush current behavior for output channels".
Leakage current when the output is switched off<10 µA
RDS(on)240 mΩ
Switching voltageI/O power supply minus voltage drop due to RDS(on)
Max. switching frequencySee section "Inrush current behavior for output channels".
Test pulse lengthMax. 500 µs
Time between two test pulsesMin. 49.5 ms
Max. capacitive load100 nF
Operating conditions
Mounting orientation
HorizontalYes
VerticalYes
Installation elevation above sea level0 to 2000 m, no limitation
Degree of protection per EN 60529IP20
Ambient conditions
Temperature
Operation
Horizontal mounting orientation0 to 60°C
Vertical mounting orientation0 to 50°C
DeratingSee section "Derating".
Storage-40 to 85°C
Transport-40 to 85°C
Relative humidity
Operation5 to 95%, non-condensing
Storage5 to 95%, non-condensing
Transport5 to 95%, non-condensing
Mechanical properties
NoteOrder 1x safety-keyed terminal block separately.
Order 1x safety-keyed bus module separately.
Pitch25+0.2mm