Note:
This product is designed for 3-wire potentiometer signal input with a DC24V power supply.
For customizations such as input signal, output signal, or other specifications, please feel free to contact us.
Description:
- The potentiometer signal conditioner is fully isolated and includes a sensor constant current source. It converts potentiometer and slide resistance displacement signals into process signals.
- The transmitter receives the slide resistance signal, converts it into other linear signals (such as 4-20mA or 0-5V standard signals), and outputs them to a DCS or other secondary instruments.
- The device features standard 35mm DIN rail mounting with independent channel configuration. Parameters can be customized as needed.
Product Parameters:
Input
- Input Signal: 3-wire potentiometer signal input, range: 0-100KΩ
- Excitation Method: Internal current source excitation
Output
- Output Signal: 4-20mA, 0-20mA, 0-10mA, 0-5V, 0-10V, 1-5V (Customizable)
- Output Load Resistance:
- RL ≤ 500Ω (for output current signal)
- RL ≥ 10KΩ (for output voltage signal)
Other Parameters
- Power Supply: DC24V ±10%
- Current Consumption: ≤ 50mA (1 in, 1 out, 24V power supply, output 20mA)
- Accuracy: 0.1% F.S.
- Temperature Drift: 0.005% F.S./℃ (-20℃ to +55℃)
- Response Time: ≤10ms (0-90%) (typical)
- Isolation Intensity: 1500V AC/1min (between input, output, and power)
- Insulation Resistance: ≥ 100MΩ (between input, output, and power)
- Working Temperature & Humidity: -20℃ to +55℃
- EMC Compliance: Complies with GB/T 18268 (IEC 61326-1)