3 Attempt Automatic Generator Control Module 

Model: AECM107

With automatic battery voltage sensor (BVS) and multi-range stop delay timer on-board. 

  • Capable to detect the low voltage battery threshold and start the generator automatically.
  • It is possible to select an external battery or engine starting battery to monitor.
  • Engine starts on low battery detected, and carries on running on stop delay timer.


AECM107 also comes with remote wired/local start/stop function by default.



AECM107 controller is suitable for single and three phase electric start generators.

Not suitable for petrol generators with manual choke.



DESCRIPTION



The Model AECM107 is an intelligent Generator / Engine Control Module, supplied with Battery Voltage Sensor (BVS) and multi-range stop delay timer on-board. It is designed to automatically operate the electric start generator and used to replace the standard manually operated (Off-GlowRun-Start) or (Off-Run-Start) ignition switch. Unique features - BVS and multi-range stop delay timer are designed to control an external battery bank (up to 40Vdc) or the engine starting battery voltage by automatically starting, running and shutting down the engine ones the run time set by multi-range stop delay timer has elapsed. The selection of the controlled battery is made by the “External / Engine Battery Monitor Selector” button located at the top left corner of the module.


 Start and stop commands could be received from:

• Local Control Toggle switch
• Wired remote toggle switch
• Volt-free inverter relay
• ATS panel volt-free relay
• (BVS) start-stop commands
• Wireless key fob (optional function).
Key Fob button “A” is for start/stop command, button “B” is for emergency stop. There is an option to pair more than one key fob with 100m range (default), 250m or 1000m. Please contact us to order.

START SEQUENCE (EXAMPLE)

0.5 second after the fuel relay is energised, the 3-attempt start will begin its start sequence: the start relay will energise, feeding battery +ve on terminal7 to terminal 2 and thence on to the start circuit. The crank period is set for 12 seconds (each starting attempt time is auto-regulated and may become shorter if generator starts quicker). If the engine has not fired by the end of 1st attempt, the starter is turned off for a 20 sec. period. The sequence will then repeat up to a maximum number of start attempts. Following a successful start, sensed when AC alternator's frequency rises above 30Hz, the crank relay is de-energised and latched out to prevent re-engagement of the starter with the engine running.

POSSIBLE START/STOP MODES WITH STOP DELAY TIMER* ENABLED.

Please make sure the multi-range stop delay timer is powered (DIP switch #1 is moved to ON position marked up as “TP” which means “Timer Power”. Set up the timer according to the multi-range stop delay timer table (1).

START FROM START/STOP TOGGLE SWITCH (LOCAL CONTROL):

Turn the Start/Stop Toggle Switch from OFF to ON position to start and run the engine. Turn to OFF position to stop. The stop delay timer will continue to run the generator if it was initially set up and powered by the Red DIP switch #1. To interrupt the stop delay timer current work and stop the engine earlier is possible from the “Timer Reset” button. Press and hold this button for 2 sec to interrupt the stop delay timer and shut down the engine. Alternatively, apply the emergency stop button. Any engine faults identified (low oil, high engine temperature, over/under speed) will override any current AECM107 controller work and shutdown the engine immediately.

START FROM REMOTE WIRED SWITCH:

The AECM107 (terminal 1) connected to battery negative (terminal 8). The generator will be running as long as these terminals are connected together. However, if the remote wired switch is turned off soon after the engine successful start, the AECM107 controller will continue to run the engine according to the stop delay timer settings. All operating modes and stopping conditions for a running generator are valid as indicated in the description above. Please refer to "Start from Start/Stop Toggle Switch (Local Control)" description.

START FROM THE KEY FOB (WIRELESS CONTROL):
Make sure there are no metal doors/walls/other metal shields between you and controlled generator. Any metal obstacle can significantly reduce the working distance between the remote control device (кеу fоb) and controlled generator. Press the wirеlеss controller button A to start and run the engine. Press wirеlеss controller button A again to stop. Button B is acting the same way as an Emergency Stop input 4. If button B is pressed, the controller becomes inactive and cannot be used until the button B is pressed again. Please note that the shape of the supplied key fob may differ from the one shown in the picture, but it will have the same functionality and approximate size.

START FROM THE BATTERY VOLTAGE SENSOR (BVS):

Connect the external battery bank to AECM107 terminals A+ and B- and select "External Battery Control" mode by using the "External / Engine Battery Monitor Selector" Button. When external battery bank voltage drops below 12Vdc the BVS will automatically start and run the engine. The BVS will stop requesting the AECM107 controller to run when the external battery bank voltage becomes equal or higher than 12.8Vdc. The stop delay timer will continue to run the generator if it was initially set up and powered by the Red DIP switch #1. All operating modes and stopping conditions for a running generator are valid as indicated in the description above (please refer to "start from remote wired switch" description). While the BVS is requesting the AECM107 to run, it is possible to stop the engine earlier by disconnecting terminal A+ or B- (or both) and then press and hold the “Timer Reset” button for 2sec. It is also possible to control the engine starting battery voltage (12Vdc or 24Vdc) when the "Engine Battery Control" mode selected by using
the "External / Engine Battery Monitor Selector Button".

The AECM107 controller supplied with BVS settings for 12V battery by default.
  • 12V battery settings 
Low Voltage Threshold: 12Vdc
High Voltage Threshold: 12.8dc
  • 24V battery settings
Low Voltage Threshold: 24Vdc
High voltage Threshold: 25.6Vdc

*To de-activate the stop delay timer completely, turn the Red DIP switch #1 (TP) to OFF position. This will power off the delay timer and allow to operate AECM107 control module normally without stop delay function.

OTHER USEFUL FUNCTIONS

• Over / Under engine speed protection.

This mode is activated by the RED DIP switch #3 (SP) when turned to ON position.
The AECM107 controller will monitor the AC alternator frequency and shutdown the engine immediately when the frequency drops down below or rises above the set value.
For countries with 50Hz standard frequency these settings will be 30Hz-57Hz.
For countries with 60Hz standard frequency these settings will be 45Hz-69Hz.
The customer can specify their own values during order.

• Pre-heat function.

This mode is activated by RED DIP switch #4 (GL) when it is set to ON.
The AECM107 controller energizes the preheat output for 10 seconds (terminal 9) before each start attempt, making it easier to start the diesel generator. The "TEMP/GL" LED will flash continuously during the pre-heat time.
The customer can specify their own pre-heat time before order.

• Load control function.

After a successful start, when engine's parameters are settled, the Load Control Output (terminal #10) will energise and send a +12Vdc (+24Vdc) signal to an external power relay 4. This energizes a contactor which will connect the running generator output to the load.
After receiving a stop command, the Load Control Output (terminal #10) will de-energise immediately leaving the running generator to cool down. The engine warm-up time before connecting load and the cool-down time after disconnecting load are set for 10sec by default. The customer can specify their own warm-up and cool-down times with a limit of 255 sec max. before order.
Should the engine still fail to start after the maximum number of attempts, START FAIL LED is flashing and the starter is latched out until reset via “OFF” position of remote/local toggle switch or via key fob button B if the engine start was initially made via remote wireless start signal.
Disable BVS by disconnecting at least 1 wire from the terminal A+ or B- to interrupt the start and run request sent by BVS.


  Wiring diagrams

Power relays 1,2,3,4 should be used to buffer all AECM107 outputs.


AECM107 SPECIFICATION


AECM107 Default Settings and Specifications

DC Supply: 12V or 24V (8...40Vdc)

Max. standby current: 6,5mA @12Vdc

Start/Fuel/Glow/Load relay output: 20A max @ 30Vdc

Number of attempts (max): 3

Pause between each attempt: 20 sec

Each start attempt duration (max) 12 sec (self-regulated)

Protective sensors activation time delay: 7 sec

Timer run time max.: 24h

Operating temperature range: -30 to +70°C

Humidity Range Operating: 20-80%

Enclosure mount: flat surface or DIN rail

Dimensions: 95x90x40

All settings are user-configurable prior to shipment.



Package Includes:


1x AECM107 controller with battery voltage sensor and stop delay timer on-board

1x Wiring diagram/user manual

The DIN rail is not included