Engineering Specification
Model HL-22ESFR PendentAutomatic Sprinklers
Recommended CSI MasterFormat Specification Location: 21 13 00, Fire Suppression Sprinkler Systems (formerly 13930)
Sprinklers
shall be Early Suppression Fast Response (ESFR) pendent suppression mode
sprinklers [cULus Listed] [FM Approved] for commodity
storage applications. Sprinkler frame
and deflector to be of bronze construction with deflector located inside of the
frame arms. Sprinkler shall have a
maximum listed/approved ceiling-to-deflector distance of 18”. Fusible alloy solder link assembly shall
utilize the strut and lever principle of operation with approved fast response
beryllium-nickel thermal element with protective [black painted, 165ºF
(74ºC)] [gray painted, 212ºF (100ºC)] coating. Water seal shall
consist of a Teflon-coated Bellville spring washer and brass cap assembly
containing no plastic parts. ESFR
sprinklers shall have a nominal K-factor of 22.4gpm/psi1/2 (320
l/min/bar1/2) and [1” NPT threaded] [ISO7 R-1 threaded]
[IGSTM Style V9 Sprinkler Coupling]end connections. Sprinklers shall have a rated working
pressure of 175 psi (12 bar).Sprinkler temperature rating shall be [Ordinary
165ºF (74ºC)] [Intermediate 212ºF (100ºC)]. ESFR pendent sprinklers shall be Reliable
Model HL-22, SIN RA1011. Refer to Reliable Bulletin 010 for associated
sprinkler information.
For
Specific Application (UL Listing) for 45’ storage of Class I - IV and cartoned
unexpanded Group A plastic in 48’ buildings, add:
Sprinklers
shall have a Specific Application UL listing for 45’ storage of Class I - IV
and cartoned unexpanded Group A plastic in 48’ buildings.Refer to Table C of Reliable
Bulletin 010 for associated information.