ABB XT1C 160 TMD 160-1600 4p F F InN=100%

Price: 180.99 USD

ABB XT1C 160 TMD 160-1600 4p F F InN=100%

XT1C 160 TMD 160-1600 4p F F InN=100%

Extended Product Type: XT1C 160 TMD 160-1600 4p F F InN=100%

Product ID: 1SDA067410R1

EAN: 8015644013042

Catalog Description: XT1C 160 TMD 160-1600 4p F F InN=100%

Long Description: C.BREAKER TMAX XT1C 160 FIXED FOUR-POLE WITH FRONT TERMINALS AND THERMOMAGNETIC RELEASE TMD R 160-1600 A FULLY RATED NEUTRAL

ABB EcoSolutions: Yes

UL 2799 Zero Waste To Landfill Validation available

Recyclability Rate acc. to EN45555: 55.9 %

RoHS Information: Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Order Code US and Canada: XT1CE4160AFF000XXX

E-Number (Norway): 4309719

Minimum Order Quantity: 1 piece

Customs Tariff Code: 85362090

Product Net Width: 10.16 cm

Product Net Height: 13.0 cm

Product Net Depth: 7.0 cm

Product Net Weight: 1.4 kg

Container Packaging: box 1 piece, Width 12.8 cm, Height 13.5 cm, Depth 14.3 cm, Gross Weight 1.454 kg

Circuit Breaker Type to be Associated: Power Distribution

Product Main Type: SACE Tmax XT

Product Name: Moulded Case Circuit Breaker

Product Type: Automatic Circuit Breaker

Version: F

Connecting Capacity Main Circuit: Busbar 45.5 ... 80 mm²

Current Type: AC/DC

Electrical Durability: 8000 cycles

Mechanical Durability: 25000 cycles

Number of Poles: 4

Opening Time: CB with SOR 30 ms / CB with UVR 30 ms

Power Loss per Pole: 15 W

Rated Current (In): 160 A

Rated Frequency: 50 / 60 Hz

Rated Impulse Withstand Voltage (Uimp): 8 kV

Rated Instantaneous Short-Circuit Current Setting (Ii): 1600 A

Rated Insulation Voltage (Ui): 800 V

Rated Operational Voltage: 690 V AC / 500 V DC

Rated Service Short-Circuit Breaking Capacity (Ics): (220-240 V AC) 40 kA, (380-415 V AC) 25 kA, (440 V AC) 12.5 kA, (500 V AC) 9 kA, (525 V AC) 8 kA, (690 V AC) 4 kA, (250 V DC) 2 Poles in Series 25 kA, (500 V DC) 3 Poles in Series 25 kA

Rated Ultimate Short-Circuit Breaking Capacity (Icu): (220-240 V AC) 40 kA, (380-415 V AC) 25 kA, (440 V AC) 25 kA, (500 V AC) 18 kA, (525 V AC) 8 kA, (690 V AC) 4 kA, (250 V DC) 2 Poles in Series 25 kA, (500 V DC) 3 Poles in Series 25 kA

Rated Uninterrupted Current (Iu): 160 A

Rated Voltage (Ur): 690 V

Recommended Screw Driver: Main Circuit M6

Release: TMD

Release Type: TM

Setting Range: 112...160 A

Short-Circuit Performance Level: C

Standards: IEC60947-2

Sub-type: XT1

Terminal Connection Type: Front

Terminal Type: Bolt

Tightening Torque: 6 N·m

ATEX Certificate: No certification needed

GL Certificate: 1SDL000163R0103

LR Certificate: LRs certificate Tmax XT

UL Certificate: No certification needed

VDE Certificate: No certification needed

ETIM 9 and 10 Classification: EC000228 - Power circuit-breaker for trafo/generator/installation protection

Object Classification Code: Q

UNSPSC: 39120000

WEEE Category: 5. Small Equipment (No External Dimension More Than 50 cm)

eClass: V11.1 : 27370409

SKU: 1SDA067410R1
Weight: 1.4 KG
 
 

Shipping

Delivery time:


4-6 Business Days from date of payment..

Payment

Ebay managed payment option only.

Conditions

 Seller is not responsible for any arising foreign charges at the buyers country such as but not limited to customs duties.
     Images are for illustrative purposes only