- Product Series: Modicon M221
- Product Type: Programmable Logic Controller
- Rated Supply Voltage [Us]: 100...240 V AC
- Number of Discrete Inputs: 14 discrete inputs, conforming to IEC 61131-2 Type 1
- Number of Analog Inputs: 2 on 0...10 V
- Solid-State Output Type: Normally open relay
- Number of Discrete Outputs: 10 relays
- Discrete Output Voltage:
- Discrete Output Current: 2 A
- Discrete I/O Count: 24
- Number of I/O Expansion Modules:
- 7 (local I/O system)
- 14 (remote I/O system)
- Supply Voltage Range: 85…264 V
- Mains Frequency: 50/60 Hz
- Instantaneous Peak Current: 40 A
- Maximum Power Consumption in VA:
- 55 VA at 100...240 V (with maximum number of I/O expansion modules)
- 32 VA at 100...240 V (without I/O expansion modules)
- Power Supply Output Current:
- 0.52 A at 5 V for expansion bus
- 0.16 A at 24 V for expansion bus
- Discrete Input Logic: Sink or source (positive/negative)
- Discrete Input Voltage: 24 V
- Discrete Input Voltage Type: DC
- Analog Input Resolution: 10 bits
- LSB Value: 10 mV
- Conversion Time: 1 ms per channel + 1 controller cycle time for analog inputs
- Allowable Overload at Inputs:
- ±30 V DC for 5 minutes (maximum) for analog inputs
- ±13 V DC (constant) for analog inputs
- Voltage State 1 Guarantee: ≥15 V for inputs
- Voltage State 0 Guarantee: ≤5 V for inputs
- Discrete Input Current:
- 7 mA for discrete inputs
- 5 mA for fast inputs
- Input Impedance:
- 3.4 kOhm for discrete inputs
- 100 kOhm for analog inputs
- 4.9 kOhm for fast inputs
- Response Time:
- 35 µs off, terminals I2...I5 for inputs
- 10 ms on for outputs
- 10 ms off for outputs
- 5 µs on, terminals I0, I1, I6, I7 for fast inputs
- 35 µs on, other terminals for inputs
- 5 µs off, terminals I0, I1, I6, I7 for fast inputs
- 100 µs off, other terminals for inputs
- Configurable Filter Time:
- 0 ms for inputs
- 3 ms for inputs
- 12 ms for inputs
- Output Voltage Limit:
- Connection Type - Terminal Connection:
- 4 A on COM 2
- 7 A on COM 0
- 7 A on COM 1
- Absolute Accuracy Error: ±1% full scale for analog inputs
- Electrical Life:
- 100,000 operations AC-12, 120 V, 240 VA, resistive (load)
- 100,000 operations AC-12, 240 V, 480 VA, resistive (load)
- 300,000 operations AC-12, 120 V, 80 VA, resistive (load)
- 300,000 operations AC-12, 240 V, 160 VA, resistive (load)
- 100,000 operations AC-15, cos phi = 0.35, 120 V, 60 VA, inductive load
- 100,000 operations AC-15, cos phi = 0.35, 240 V, 120 VA, inductive load
- 300,000 operations AC-15, cos phi = 0.35, 120 V, 18 VA, inductive load
- 300,000 operations AC-15, cos phi = 0.35, 240 V, 36 VA, inductive load
- 100,000 operations AC-14, cos phi = 0.7, 120 V, 120 VA, inductive load
- 100,000 operations AC-14, cos phi = 0.7, 240 V, 240 VA, inductive load
- 300,000 operations AC-14, cos phi = 0.7, 120 V, 36 VA, inductive load
- 300,000 operations AC-14, cos phi = 0.7, 240 V, 72 VA, inductive load
- 100,000 operations DC-12, 24 V, 48 W, resistive (load)
- 300,000 operations DC-12, 24 V, 16 W, resistive (load)
- 100,000 operations DC-13, 24 V, 24 W, inductive (L/R = 7 ms)
- 300,000 operations DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)
- Switching Frequency: 20 switching operations/minute with maximum load
- Mechanical Life: 20,000,000 operations for relay outputs
- Minimum Load: 1 mA at 5 V DC for relay outputs
- Protection Type: No protection at 5 A
- Reset Time: 1 s
- Storage Capacity:
- 256 kB for user data, device RAM, and 10,000 instructions
- 256 kB for internal variable RAM
- Data Backup: 256 kB built-in flash card for application and data backup
- Data Storage Device: 2 GB SD card (optional)
- Battery Type: BR2032 or CR2032X non-rechargeable lithium battery
- Cumulative Operating Time: 1 year at 25 °C (with power interruption)
- Execution Time for 1K Instructions:
- 0.3 ms for event and periodic tasks
- 0.2 µs
- Execution Time per Task: 60 µs response time
- Maximum Target Area Size:
- 255 %C counters
- 8000 %MW memory words
- 512 %M memory bits
- 512 %KW continuous words
- 255 %TM timers
- Real-Time Clock: Available
- Clock Error: ≤30 s/month at 25 °C
- Regulation Loops: Adjustable PID regulators, up to 14 synchronous cycles
- Number of Calculation Inputs: 4 fast inputs (high-speed counting mode) at 100 kHz 32-bit
- Counter Function:
- A/B
- Single-phase
- Pulse/direction
- Integrated Connection Types:
- USB port with mini B USB 2.0 connector
- Non-isolated serial link Serial 1 with RJ45 connector and RS485 interface
- Non-isolated serial link Serial 2 with RJ45 connector and RS232/RS485 interface
- Power Supply: (Continuous) Serial link power supply: 5 V, <200 mA
- Transmission Rate:
- 1.2...115.2 kbit/s (default 115.2 kbit/s) for bus length...15 m for RS485
- 1.2...115.2 kbit/s (default 115.2 kbit/s) for bus length...3 m for RS232
- 480 Mbit/s for USB
- Communication Protocol:
- USB port: USB protocol - SoMachine-Network
- Non-isolated serial link: Serial Modbus protocol master/slave - RTU/ASCII or SoMachine-Network
- Local Signal Indication:
- 1 LED (green) for PWR
- 1 LED (green) for RUN
- 1 LED (red) for module error (ERR)
- 1 LED (green) for accessible SD card (SD)
- 1 LED (red) for BAT
- 1 LED (green) for SL1
- 1 LED (green) for SL2
- 1 LED (green) per channel for I/O status
- Electrical Connection:
- Detachable screw terminals for inputs
- Detachable screw terminals for outputs
- Terminal block, 3 terminals for connecting 24 V DC power supply
- Connector, 4 terminals for analog inputs
- Mini B USB 2.0 connector for a programming terminal
- Maximum Cable Distance Between Devices:
- Shielded cable: <10 m for fast inputs
- Unshielded cable: <30 m for outputs
- Unshielded cable: <30 m for digital signal inputs
- Unshielded cable: <1 m for analog inputs
- Isolation:
- Between input and internal logic: 500 V AC
- Non-insulated between analog inputs and internal logic
- Non-insulated between similar inputs
- Between supply and ground: 1500 V AC
- Between sensor power supply and ground: 500 V AC
- Between input and ground: 500 V AC
- Between output and ground: 1500 V AC
- Between power supply and internal logic: 2300 V AC
- Between sensor power supply and internal logic: 500 V AC
- Between output and internal logic: 2300 V AC
- Between Ethernet terminal and internal logic: 500 V AC
- Between supply and sensor power supply: 2300 V AC
- Marking: CE
- Sensor Power Supply: 24 V DC at 250 mA supplied by the controller
- Mounting Method:
- DIN rail mounting, type TH35-15 conforming to IEC 60715
- DIN rail mounting, type TH35-7.5 conforming to IEC 60715
- Panel or panel with mounting kit
- Dimensions:
- Height: 90 mm
- Depth: 70 mm
- Width: 110 mm
- Net Weight: 0.395 kg
- Conforming Standards:
- IEC 61131-2
- UL 508
- CAN/CSA C22.2 No. 213
- IACS E10
- ANSI/ISA 12-12-01
- Product Certifications:
- LR
- ABS
- DNV-GL
- RCM
- cULus
- EAC
- CE
- UKCA
- cULus HazLoc
- Environmental Characteristics: General and hazardous locations
- Anti-Static Discharge:
- 8 kV in air conforming to IEC 61000-4-2
- 4 kV contact conforming to IEC 61000-4-2
- Anti-Electromagnetic Field:
- 10 V/m 80 MHz...1 GHz conforming to IEC 61000-4-3
- 3 V/m 1.4 GHz-2 GHz conforming to IEC 61000-4-3
- 1 V/m 2...2.7 GHz conforming to IEC 61000-4-3
- Magnetic Field Withstand: 30 A/m 50/60 Hz conforming to IEC 61000-4-8
- Transient Pulse Immunity:
- 2 kV conforming to IEC 61000-4-4 (power line)
- 2 kV conforming to IEC 61000-4-4 (relay output)
- 1 kV conforming to IEC 61000-4-4 (I/O)
- 1 kV conforming to IEC 61000-4-4 (Ethernet cable)
- 1 kV conforming to IEC 61000-4-4 (serial link)
- Surge Withstand:
- 2 kV power line (AC) common mode conforming to IEC 61000-4-5
- 2 kV relay output common mode conforming to IEC 61000-4-5
- 1 kV I/O common mode conforming to IEC 61000-4-5
- 1 kV shielded cable common mode conforming to IEC 61000-4-5
- 0.5 kV power line (DC) differential mode conforming to IEC 61000-4-5
- 1 kV power line (AC) differential mode conforming to IEC 61000-4-5
- 1 kV relay output differential mode conforming to IEC 61000-4-5
- 0.5 kV power line (DC) common mode conforming to IEC 61000-4-5
- Conducted Interference Resistance:
- 10 V 0.15...80 MHz conforming to IEC 61000-4-6
- 3 V 0.1...80 MHz conforming to marine specifications (LR, ABS, DNV, GL)
- 10 V calibration frequency (2, 3, 4, 6.2, 8.2, 12.6, 16.5, 18.8, 22, 25 MHz) conforming to marine specifications (LR, ABS, DNV, GL)
- Electromagnetic Emission:
- Conducted emission - test level: 79 dBμV/m QP/66 dBμV/m AV (power line (AC)) at 0.15…0.5 MHz conforming to IEC 55011
- Conducted emission - test level: 73 dBμV/m QP/60 dBμV/m AV (power line (AC)) at 0.5…300 MHz conforming to IEC 55011
- Conducted emission - test level: 120...69 dBµV/m QP (power line) at 10…150 kHz conforming to IEC 55011
- Conducted emission - test level: 63 dBμV/m QP (power line) at 1.5…30 MHz conforming to IEC 55011
- Radiated emission - test level: 40 dBμV/m QP Class A (10 m) at 30…230 MHz conforming to IEC 55011
- Conducted emission - test level: 79...63 dBμV/m QP (power line) at 150…1500 kHz conforming to IEC 55011
- Radiated emission - test level: 47 dBμV/m QP Class A (10 m) at 200…1000 MHz conforming to IEC 55011
- Transient Power Interruption Immunity: 10 ms
- Ambient Temperature:
- -10…55 °C (vertical mounting)
- -10…35 °C (vertical mounting)
- Storage Ambient Temperature: -25…70 °C
- Relative Humidity:
- 10…95%, non-condensing (in operation)
- 10…95%, non-condensing (during storage)
- IP Protection Rating: IP20 with protective cover in place
- Pollution Degree: ≤2
- Operating Altitude: 0...2000 m
- Storage Altitude: 0…3000 m
- Vibration Resistance:
- 3.5 mm at 5…8.4 Hz on uniform rail
- 3.5 mm at 5…8.4 Hz on panel mounting
- 1 gn at 8.4…150 Hz on uniform rail
- 1 gn at 8.4…150 Hz on panel mounting
- Shock Resistance: 98 m/s² for 11