SAP 1 Loop 16 Zone Addressable Sprinkler Monitoring Panel (XP95/Discovery Protocol)
Order code: SAP501E/X
The SAP501E/X is an advanced sprinkler monitoring panel, ideal for monitoring up to 126 sprinkler flow switches. This panel utilizes the same reliable technology as C-TEC's XFP addressable fire panels, making it a robust solution for sprinkler flow monitoring in fire protection systems. The panel supports up to 16 sprinkler zone indicators which can be assigned via the panel’s PC programming tools.
It is designed for both flush and surface mounting in an attractive plastic enclosure and includes combined keypad or keyswitch entry for convenient operation.
Compatibility: Compatible with Apollo XP95/Discovery protocol.
Mains Supply: 230V, 50/60Hz, with a maximum rated current of 350mA.
Internal Power Supply: 27V DC nominal.
Output: Total output current is limited to 1.4A @ 230V AC (with current ranges between 40mA and 210mA).
Quiescent Current: 50mA (loop unloaded).
Max Battery Size: 2 x 12V 3.2Ah VRLA batteries connected in series.
Loop Driver: 1 loop driver with 500mA max loop output current (25V min; 34V max).
Max. Loop Length: 1KM.
Addressable Devices per Loop: Supports up to 126 addressable devices per loop.
Conventional Sounder Circuits: 2 circuits (max. length per circuit: 500m).
End-of-Line (EOL) Resistor: 6800Ω 5% tolerance, 0/25W.
Max Sounder Output: 400mA.
Auxiliary Relays:
3 programmable relays (programmable from C&Es).
1 fault relay (active when no faults are present), with a maximum switch current of 1A and maximum switch voltage of 30V DC.
Outputs: 24V Aux Power (19.5V min, 28V max), protected by a resettable fuse (max. current: 100mA).
Auxiliary Inputs: 2 programmable inputs, non-latching with max input voltage of 27V.
PC Connection: Through RS232 molex connector (included in XFP507 upload/download software kit). No printer connection is available.
Indicators:
2-line, 40-character backlit display.
16 Zonal LEDs for various statuses (e.g., General Fire, Pre-Alarm, General Fault).
Network/Repeater: A 2-wire RS485 non-redundant network/repeater connection is available via an optional XFP761 network card.
Max: 8 mains or 8 repeaters per non-networked main panel.
Network length: Maximum 1KM.
Dimensions: 380 W x 235 H x 96 D mm (base).
Hole for Flush Mounting: 367 W x 220 H x 75 D mm. No bezel is required.
Material: Plastic lid and base, textured RAL7035.
IP30 (suitable for indoor environments).
1.8kg (without batteries).
Temperature Range: -5°C to +40°C.
Humidity: Max 95% relative humidity.