C-Tec XFP510-32 XFP Repeater Panel 32 Zone
The C-Tec XFP510-32 is a 32-zone repeater panel designed to repeat the functions of an XFP Main panel at remote locations, such as fire service entrances or other critical points on a site. This panel offers full access to all functions and controls of the XFP Main panel, including access levels 1, 2, and 3, and includes an onboard fault relay.
The XFP510-32 requires its own dedicated mains power and battery backup supply, and up to eight XFP Repeaters can be connected to a non-networked XFP Main panel. Communication between the XFP Main panel and the repeater is managed through the AFP711 network driver card, which is standard in all XFP510-32 units.
The repeater network must be wired with 1.5mm² two-core screened fire-resistant cable, and the total network length must not exceed 500 meters.
Key Features:
Can be used to repeat the functions of an XFP Main panel at remote locations such as fire service entrances.
Offers all of the functions and controls of the XFP Main panel (access levels 1, 2, and 3).
Includes an on-board fault relay for added reliability.
Requires its own mains power and battery backup supply.
A maximum of 8 XFP Repeaters can be connected to a single non-networked XFP Main panel.
Communication between the Main panel and the Repeater requires the AFP711 network driver card (standard in XFP510-32 units).
Repeater network is wired in 1.5mm² two-core screened fire-resistant cable. Network length cannot exceed 500 meters.
Protocol/Compatibility:
Compatible with C-TEC's XFP CAST, Apollo XP95/Discovery, and Hochiki ESP main panels.
Specifications:
Mains Supply: 230V 50/60Hz.
Mains Rated Current: 680mA maximum.
Internal Power Supply: 27V DC nominal.
Total Output Current: Limited to 3A @ 230Vac (Imax: 250mA; Imin: 70mA).
Max Battery Size and Type: 2 x 12V 7Ah VRLA batteries connected in series.
Auxiliary Relays: Fault (Failsafe; capable of switching 1A @ 30V DC; not for switching mains voltages).
Indicators:
2-line x 40-character backlit display.
32 Zonal LEDs.
General Fire, Energized, Pre-Alarm, Remote Output Activated, Remote Output Disabled, Accessed, Disablement, Test, Silenced, General Fault, System Fault.
Expansion Connections: Onboard AFP711 network driver card for connecting additional XFP Repeaters.
Product Dimensions (mm):
Panel Size: 410 W x 250 H x 80 D mm (base).
Flush Mounting Hole Size: 412 W x 255 H x 50 D mm (requires XFP385 bezel).
Lid Dimensions: 439 W x 274 H x 7 D mm.
Construction & Finish:
Material: Metal.
Finish: Textured, RAL7035.
IP Rating: To be confirmed.
Weight: 4.5 kg (without batteries).
Operating Conditions/Temperature:
Temperature: -5ºC to +40ºC.
Max Relative Humidity: 95%.
Network Specification:
Maximum number of Repeaters per Main XFP: 8 (any mix).
Maximum total length of Repeater network: 500m.
Cabling Requirements: 1.5mm² two-core screened fire-resistant cable.
The network is non-redundant.