C-Tec XFP510-16 XFP Repeater Panel 16 Zone
The C-Tec XFP510-16 is a repeater panel designed to replicate the functions of an XFP Main panel at remote locations, ideal for areas such as fire service entrances. It provides full access to all controls and functions of the XFP Main panel (including access levels 1, 2, and 3). The panel includes an onboard fault relay and requires its own dedicated mains power and battery backup supply.
Up to eight XFP Repeaters can be connected to a single non-networked XFP Main panel. Communication between the XFP Main panel and the repeater is managed through the CFP761 network driver card, which is standard in all XFP510-16 panels and available as an optional extra for Main XFP 16 Zone panels. The repeater network must be wired in 1.5mm² two-core screened fire-resistant cable, and the network length cannot exceed 500 meters.
Key Features:
Can be used to replicate the functions of an XFP Main panel at remote sites such as fire service entrances.
Offers all functions and controls of the XFP Main panel (access levels 1, 2, and 3).
Includes an onboard fault relay.
Requires dedicated Mains power and battery backup supply.
A maximum of 8 repeaters can be connected to one non-networked XFP Main panel.
Communication between Main panel and Repeater requires CFP761 network driver card (standard in XFP510-16, available for Main XFP 16 Zone panels).
Repeater network must use 1.5mm² two-core screened fire-resistant cable, with a maximum network length of 500 meters.
Protocol/Compatibility:
Compatible with C-TEC's XFP CAST, Apollo XP95/Discovery, and Hochiki ESP main panels.
Specifications:
Mains Supply: 230V, 50/60Hz.
Mains Rated Current: 350mA maximum.
Internal Power Supply: 27V DC nominal.
Total Output Current: Limited to 1.4A @ 230Vac (Imax: 210mA; Imin: 40mA).
Max Battery Size and Type: 2 x 12V 3.2Ah VRLA batteries connected in series.
Auxiliary Relays: Fault (Failsafe; capable of switching 1A @ 30V DC; not to be used for switching Mains voltages).
Indicators:
2 line x 40 character backlit display.
16 Zonal LEDs.
General Fire, Energized, Pre-Alarm, Remote Output Activated, Remote Output Disabled, Accessed, Disablement, Test, Silenced, General Fault, System Fault.
Expansion Connections: Onboard CFP761 network driver card for connecting additional XFP Repeaters.
Product Dimensions (mm):
Panel Size: 380 W x 235 H x 96 D mm.
Flush Mounting Hole Size: 367 W x 220 H x 75 D mm (no bezel required).
Construction & Finish:
Material: Plastic lid and base.
Finish: RAL7035 textured.
IP Rating: IP30.
Weight: 1.8 kg (without batteries).
Operating Conditions/Temperature:
Temperature: -5ºC to +40ºC.
Max Relative Humidity: 95%.
Network Specification:
Maximum number of Repeaters per Main XFP: 8 (any mix).
Maximum total length of Repeater network: 500m.
Cabling Requirements: 1.5mm² two-core screened fire-resistant cable