The through terminal block (item number 2004-1302) is designed for seamless electrical installations. Strip lengths must be between 11 and 13 mm when connecting conductors to this through terminal block. Whether in industrial or building applications, our rail-mount through terminal blocks are the perfect solution to quickly and securely connect electrical conductors. Depending on the variant, you can use them for either typical through-wiring or potential distribution. Featuring conductor terminals along with Push-in CAGE CLAMP®, this product outperforms the competition. Push-in CAGE CLAMP® technology provides a universal connection solution for any type of conductor. It allows both solid and fine-stranded conductors with ferrules to be inserted directly into the clamping point without the need for tools. Dimensions: (6.2 x 65.5 x 39.5) mm (width x height x depth). This through terminal block is suitable for conductor cross sections ranging from 0.5 mm² to 6 mm².
An operating tool is used to operate this through rail-mount terminal block. Our TOPJOB® S rail-mount terminal blocks guarantee reliable electrical connections across many different industrial applications and modern building installations. They simplify wiring, as you can quickly plug in solid, stranded, and fine-stranded conductors with ferrules. This product is designed for specific Ex applications (please refer to the product datasheet).
Electrical data
IEC Approvals
Ratings per
IEC/EN 60947-7-1
Overvoltage category
III
III
II
Pollution degree
3
2
2
Nominal voltage
800 V
-
-
Rated impulse withstand voltage
8 kV
-
-
Rated current
32 A
-
-
Current at conductor cross-section (max.) mm²
41 A
-
-
UL Approvals
Approvals per
UL 1059
Use group
B
C
D
Rated voltage
600 V
600 V
-
Rated current
30 A
30 A
-
CSA Approvals
Approvals per
CSA 22.2 No 158
Use group
B
C
D
Rated voltage
600 V
600 V
-
Rated current
30 A
30 A
-
Ex information
Reference to hazardous areas
See application instructions in section “Knowledge and Downloads – Documentation – Additional Information: Technical Section; Technical Explications”
Ratings per
ATEX: PTB 05 ATEX 1095 U / IECEx: PTB 05.0033U (Ex eb IIC Gb)
Rated voltage EN (Ex e II)
550V
Rated current (Ex e II)
30A
Power Loss
Power loss, per pole (potential)
1.024W
Rated current IN for power loss specification
32A
Resistance value for specified, current-dependent power loss
0.001Ω
General information
Wiring direction
Front-entry wiring
Connection Data
Clamping units
3
Total number of potentials
1
Number of levels
1
Number of jumper slots
2
Connection 1
Connection technology
Push-in CAGE CLAMP®
Actuation type
Operating tool
Connectable conductor materials
Copper
Nominal cross-section
4 mm²
Solid conductor
0.5 … 6 mm² / 20 … 10 AWG
Solid conductor; push-in termination
1.5 … 6 mm² / 14 … 10 AWG
Fine-stranded conductor
0.5 … 6 mm² / 20 … 10 AWG
Fine-stranded conductor; with insulated ferrule
0.5 … 4 mm² / 20 … 12 AWG
Fine-stranded conductor; with ferrule; push-in termination
1.5 … 4 mm² / 18 … 12 AWG
Note (conductor cross-section)
Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.