3 Phase Power Quality Analyzer Power Energy Meter with 4PCS Round Current Sensor
This Power Quality Analyzer comes with 4PCS DZF-3Q-100AClamp Sensors, 0.10A~100A Range.
If you needs other sensors, please contact us.
Introduction:
Product Main Function:
General Specification:
Power supply
|
Rechargeable lithium-ion battery packs 9.6V, backup charger.
|
Battery Level indicator
|
Battery symbol 5 grid Display power, when the battery level is low, automatically shut down after 1 minute indication
|
Working Current
|
about 590mA, continuous working 8hours.
|
Display mode
|
LCD color screen, 640dots × 480dots, 5.6 inches, display field 116mm × 88mm
|
Instrument Size
|
240mm×170mm×68 mm.
|
CT Size
|
DZF-3Q-100A round jaw current clamp: 35mm×40mm;
|
Number of channels
|
4 voltages, 4 currents
|
Line Voltage
|
1.0V~2000V.
|
Phase Voltage
|
1.0V~1000V.
|
Current
|
DZF-3Q-100A current clamp: 0.10A~100A;
|
Frequency
|
40Hz~70Hz.
|
Electricity Energy Parameter
|
W, VA, Var, PF, DPF, cosφ, tanφ.
|
Energy parameters
|
Wh, Varh, Vah.
|
Harmonic Wave
|
Yes, 0 - 50 times
|
Total harmonic distortion
|
Yes, 0 - 50 times, each phase
|
Expert Mode
|
Yes.
|
Transient Record Groups
|
150 groups
|
Voltage Flicker
|
Yes
|
Start Current Mode
|
Yes, 100 seconds
|
Three-phases Unbalance
|
Yes
|
Record
|
300 days (record 20 parameters simultaneously, every 5 seconds record 1 point)
|
Min/Max Recorded Value
|
Yes, the max min value can be measured for a certain time
|
Alarm
|
40 different types of parameter selection, 12800 group alarm logs
|
Peak
|
Yes.
|
Phasor Diagram Display
|
Automatic
|
Screenshot Capacity
|
60PCS
|
Menu language
|
English/Chinese.
|
Communication Interface
|
USB.
|
Automatic Shut Down
|
In the alarm/trend graph recording/transient capture mode (waiting or in progress), the instrument does not automatically shut down
|
In other test modes, there is no button operation within 15 minutes, prompting to automatically shut down after 1 minute.
|
|
Backlight Function
|
Yes, suitable for dark places and nighttime use
|
Instrument Weight
|
Host: 1.6kg (with battery).
|
DZF-3Q-100A circle current clamp: 190g×4;
|
|
Test wires and power adapter: 900g;
|
|
Total weight: about 9.2kg (with package).
|
|
Voltage Test Wire Length
|
3M
|
Current Clamp Wire Length
|
2M
|
Working Temperature
|
-10°C~40°C; below 80%Rh.
|
Storage Temperature
|
-10°C~60°C; below 70%Rh.
|
Input Impedance
|
Test voltage input impedance: 1MΩ
|
Withstand voltage
|
Withstand the sine wave AC voltage of 3700V/50Hz one minute between the instrument line and out shell
|
Insulation
|
Between instrument line and shell ≥10MΩ.
|
Structure
|
Double insulation, with insulation shock-proof sheath.
|
SuitableSafely Standard
|
IEC 61010 1000V Cat III / 600V CAT IV, IEC61010-031, IEC61326, Pollution degree: 2.
|
Accessories
|
Host: 1PCS; Instrument Bag: 1pcs; Test Cable: 5PCS (yellow, green, red, blue, black); Alligator Clip: 5PCS; Probe: 5PCS; Charger 1PCS; Software CD: 1COPY; 2G Memory Card: 1PCS;Current Clamp DZF-3Q-100A 4PCS
|
The following data are presented in reference conditions and ideal current sensors Instrument Accuracy (excluding the current sensor)
(completely linear and without phase displacement).
Measurement Specification
|
Range
|
Display Resolution
|
Max Error of Reference Range
|
Frequency
|
40Hz~70Hz
|
0.01Hz
|
±(0.03)Hz
|
Phase Voltage True RMS
|
1.0V~1000V
|
Min resolution0.1V
|
±(0.5%+5dgt)
|
Line Voltage True RMS
|
1.0V~2000V
|
Min resolution0.1V
|
±(0.5%+5dgt)
|
DC Voltage
|
1.0V~1000V
|
Min resolution0.1V
|
±(1.0%+5dgt)
|
Current True RMS
|
10mA~3000A
|
Min resolution0.1mA
|
±(0.5%+2dgt)
|
Phase Voltage Peak
|
1.0V~1414V
|
Min resolution0.1V
|
±(1.0%+5dgt)
|
Line Voltage Peak
|
1.0V~2828V
|
Min resolution0.1V
|
±(1.0%+5dgt)
|
Current Peak
|
10mA~4200A
|
Min resolution0.1mA
|
±(1.0%+5dgt)
|
Peak Factor
|
1.00~3.99
|
0.01
|
±(1%+2dgt)
|
4.00~9.99
|
0.01
|
±(5%+2dgt)
|
|
Active Power
|
0.000W~9999.9kW
|
Min resolution0.001W
|
±(1%+3dgt);Cosφ≥0.8
|
±(1.5%+10dgt);0.2≤Cosφ<0.8
|
|||
Reactive power
Inductive& Capacitive
|
0.000VAR~9999.9kVAR
|
Min resolution0.001VAR
|
±(1%+3dgt);Sinφ≥0.5
|
±(1.5%+10dgt);0.2≤Sinφ<0.5
|
|||
Apparent Power
|
0.000VA~9999.9kVA
|
Min resolution0.001VA
|
± (1%+3dgt %)
|
Power Factor
|
-1.000~1.000
|
0.001
|
±(1.5%+3dgt);Cosφ≥0.5
|
±(1.5%+10dgt);0.2≤Cosφ<0.5
|
|||
Active Energy
|
0.000Wh~9999.9MWh
|
Min resolution0.001Wh
|
±(1%+3dgt);Cosφ≥0.8
|
±(1.5%+10dgt);0.2≤Cosφ<0.8
|
|||
Reactive Energy
Inductive& Capacitive
|
0.000VARh~9999.9MVARh
|
Min resolution0.001VARh
|
±(1%+3dgt);Sinφ≥0.5
|
±(1.5%+10dgt);0.2≤Sinφ<0.5
|
|||
Apparent Energy
|
0.000VAh~9999.9MVAh
|
Min resolution0.001VAh
|
±(1%+3dgt)
|
Phase Angle
|
-179°~180°
|
1°
|
±(2°)
|
Tanφ(VA≥50VA)
|
-32.768~32.768
|
Min resolution0.001
|
±(1%+5dgt)
|
Displacement Power Factor(DPF)
|
-1.000~1.000
|
0.001
|
±(1%+5dgt)
|
HarmonicRatio(Vrms>50V)
|
0.0 %~99.9 %
|
0.1 %
|
±(1%+5dgt)
|
Harmonic Angle(Vrms >50V)
|
-179°~180°
|
1°
|
±(3°)harmonic1~25
|
±(10°)harmonic26~50
|
|||
Total Harmonic Rate
(DF or THD-F)≤50
|
0.0 %~99.9 %
|
0.1 %
|
±(1%+5dgt)
|
Distortion Factor
(DF or THD-R)≤50
|
0.0 %~99.9 %
|
0.1 %
|
±(1%+10dgt)
|
Transformer K Factor
|
1.00~99.99
|
0.01
|
±(5 %)
|
Three-phase Unbalance
|
0.0%~100 %
|
0.1 %
|
±(1 %)
|