BRAND NEW WITH FULL MANUFACTURERS WARRANTYEATON DEFINITE PURPOSE MAGNETIC MOTOR STARTER.
A27CGF45B057 15HP 3 PHASE 230V 45AMP
EATON OFFERS THE MOST COMPLETE LINE OF DEFINITE
PURPOSE (DP) CONTACTORS IN THE INDUSTRY. DESIGNED FOR
HEATING, VENTILATION, AIR CONDITIONING, AIR COMPRESSORS AND REFRIGERATION, HVAC APPLICATIONS, EATON?S DEFINITE PURPOSE CONTACTORS ARE DESIGNED TO HANDLE THE MOST CHALLENGING INSTALLATIONS.
EATON DEFINITE PURPOSE STARTERS ARE UL APPROVED AND CSA CERTIFIED. EATON/CUTLER HAMMER MAGNETIC STARTERS ARE AMONG THE MOST ROBUST AND RELIABLE MAGNETIC STARTERS ON THE MARKET TODAY.
THIS EATON DEFINITE PURPOSE MAGNETIC STARTER IS SPECIFICALLY DESIGNED TO BE USE WITH 15 HP 230 VOLT 3 PHASE ELECTRIC MOTORS THAT DRAW 42 FULL LOAD AMPS AT 230V OR LESS. THIS STARTER HAS AN ADJUSTABLE OVERLOAD RELAY WHICH MEANS IT DOES NOT REQUIRE HEATER ELEMENTS AS YOUR MOTOR PROTECTION. SIMPLY TURN THE DIAL TO YOUR APPROPRIATE OVERLOAD PROTECTION AMP RATING. ALWAYS CONSULT WITH THE FULL LOAD AMP RATING ON YOUR ELECTRIC MOTOR NAMEPLATE TO
DETERMINE EXACTLY WHAT AMP SETTING TO SET THE STARTER TO.
INSTRUCTIONAL AND WIRING INFORMATION INCLUDED WITH EACH UNIT.
HP: 15
PHASE: 3 (3 POLE)
VOLTAGE: 230V ( NOT SUITED FOR 15HP 208V MOTORS)
AMPERAGE: 45 AMP CONTACTOR (ONLY SUITED FOR 15HP 3PH MOTORS THAT DRAW 42 AMPS AT 230V OR LESS. IF YOUR ELECTRIC MOTOR DRAWS 43AMPS OR MORE, OR IS CONNECTED TO A 208V POWER SOURCE, YOU WOULD REQUIRE A 50AMP CONTACTOR)
ADJUSTABLE OVERLOAD RELAY AMP RANGE: 30-45 AMPS (GENERAL RULE OF THUMB IS TO ADJUST THE OVERLOAD PROTECTION 10-15% HIGHER THAN THE FLA RATING OF YOUR ELECTRIC MOTOR)
ENCLOSURE DIMENSION: 10"H X 6"W X 6"D
PROFESSIONAL INSTALLATION IS REQUIRED
MORE PRODUCT FEATURES: CLASS 10 TRIP CLASS BI-METALLIC AMBIENT COMPENSATED OPERATED TRIP FREE MECHANISM SHROUDED FINGER PROOF TERMINALS REDUCE POSSIBILITY OF ELECTRIC SHOCK SINGLE PHASE SENSITIVITY. NEMA 1 GENERAL PURPOSE RATED CONTACTOR.