Apollo Series 65 Heat Detector, Optical Smoke Detector & Diode
Base
Please Select the item you require from the dropdown menu.
Apollo Series 65 A1R Heat Detector - 55000-122APO
The Series 65 Heat Detector
monitors temperature by using a dual thermistor network which provides a
voltage output proportional to the external air temperature. There are 12 heat
detectors in the Series 65 range designed to suit a wide variety of operating
conditions. Apollo Series 65 smoke & heat detector range are a direct
replacement for the earlier Series 60 devices. Series 65 detectors have a wide
voltage range (9-33 volt DC) and can be integrated on to security systems when
used with the 12 volt relay base (45681-508).
The heat detector operates by
using a matched pair of thermistors to sense heat. One thermistor is exposed to
the ambient temperature, the other is sealed. In normal conditions, the two
thermistors register similar temperatures, but, on the development of a fire,
the temperature recorded by the exposed thermistor will increase rapidly,
resulting in an imbalance of the thermistors and causing the detector to change
to the alarm state.
A1R, BR and CR are Rate of
Rise detectors, designed to detect a fire as the temperature increases, but
they also have a fixed upper limit at which the detector will go into alarm if
the rate of temperature increase has been too slow to trigger the detector
earlier.
Key Features:
Can be used for applications
where smoke detectors are unsuitable
Ideal for environments that
are dirty or smoky under natural conditions
Wide operating voltage
Flashing LED and magnet
operated test switch option
Wide-operating voltage of 9–33
V DC
Wide-operating and storage
temperature of -20°C to +60°C
Can be used on security
systems
Electrically and mechanically
compatible with Series 60
Proven detection performance
Apollo Series 65 Optical Smoke Detector - 55000-317APO
The Series 65 Optical Smoke Detector
incorporates a pulsing LED located within the housing of the detector. The
external detector moulding is identical to that of the ionisation detector but
has an indicator LED which is clear in quiescent state but produces a red light
in alarm. As part of the Apollo Series 65 Detector Range the 55000-317 Optical
Conventional Smoke Detector offers a fire detection solution to many
applications. The detector can be used
with most modern conventional fire alarm panels.
The Apollo Series 65
conventional optical smoke detector (55000-317) uses an internal pulsing LED
and a photo-diode at an obtuse angle. In the event of smoke entering the
chamber, the light pulse from the LED will be scattered and registered by the
photo-diode. The detector will then enter the alarm state and the indicator LED
lights up. The Apollo Series 65 optical smoke detector housing is identical to
that of the Apollo ionisation smoke detector but has an indicator LED which is
clear in quiescent state but produces red light in alarm.
Key Features:
Wide operating voltage
Advanced electronic technology
Flashing LED option
Magnetic test switch option
Can be used on security
systems
Electrically compatible with
Series 60
Mechanically compatible with
Series 60
Proven detection performance
Designed to meet approvals
worldwide
Range of bases available
Apollo Series 65 Diode Base 45681-201APO
The Series 65 Diode Base is
designed for use with conventional systems that have manual call points and
detector bases on the same circuit. The base is fitted with a Schottky diode on
the "L1 IN" and "L1 OUT" wiring terminals. This base can
only be used with compatible control equipment.
Operation:
All detectors in the Series 65
range fit into Series 60 standard mounting bases. The bases are of 100mm
diameter and have five terminals marked according to their function: Line 1 in,
line 1 out, line 2 in and out, remote indicator negative, earth. Detectors are
polarity insensitive, so that identification of positive and negative lines is
only required if a remote LED is fitted. An earth connection is not required
for either safety or correct operation of detectors.
The earth terminal is provided
for tidy termination of earthed conductors or cable screens and to maintain
earth continuity where necessary. Bases have a wide interior diameter for ease
of access to cables and terminals and there are two slots for fixing screws at
a spacing of 51 to 69mm. Detectors fit into bases one way only and require
clockwise rotation without push force to be plugged in.
Key Features:
Detector locking mechanism
One way fit
Easy to wire
Contains an earth connector
Continues to work during
unauthorised removal of detectors
Brand Features:
Wide-operating voltage of 9–33
V DC
Wide-operating and storage
temperature of -20°C to +60°C
Can be used on security
systems
Electrically and mechanically
compatible with Series 60
Proven detection performance