Weidmüller ACT20P-CMT-30-AO-RC-P Current Measuring Transducer 30A
Product Basic Information:
- Manufacturer: Weidmüller
- Catalog number: ACT20P-CMT-30-AO-RC-P
- Alternate part number: ACT20PCMT30AORCP
- Order number: 1510320000
- Product family/series: ACT20P
- Product type: Current-measuring transducer
- Country of origin: Slovakia
- HS customs code: 8543709860
Technical Specifications:
- Input measurement range: Configurable, 0 to 20/25/30 A AC RMS or DC
- Input frequency: 15 to 700 Hz for AC true RMS measurement
- Input signal: Current-carrying cable in feed-through hole
- Number of inputs: 1
- Overload behaviour: Max. peak current 10 x input for 1 second
- Supply voltage: 16.8 to 31.2 V DC
- Power consumption, typ.: 0.9 W
- Power consumption, max.: 2.2 W
- Analogue current output: Adjustable 0 to 20 mA, 4 to 20 mA, -20 to +20 mA
- Analogue voltage output: Adjustable 0 to 10 V, 2 to 10 V, 0 to 5 V, 1 to 5 V, -5 to +5 V, -10 to +10 V
- Transmit function: Direct or inverted
- Digital output: Relay, 1 CO contact, normal / inverse adjustment
- Max. switching voltage: 250 V AC, 24 V DC
- Rated switching current: 6 A
- Step response time: Less than or equal to 300 ms RMS, less than or equal to 60 ms AA
- Configuration: DIP switch and potentiometer
- Mounting rail: TS 35 DIN rail
- Protection degree: IP20
- Connection type: PUSH IN
- Galvanic isolation: 4-way isolator between input, output, supply, and relay
- Operating temperature: -25 C to +60 C
Product Features:
- Current-measuring transducer for AC and DC current monitoring
- True RMS or arithmetic averaging measurement capability
- Contactless through-hole current sensing design
- Integrated limit value monitoring for overcurrent or undercurrent applications
- Relay output with normal or inverse adjustment
- Adjustable trigger delay for filtering current peaks
- Operational status and error display on a front panel LED
- Four-way galvanic isolation for secure signal separation
- PUSH IN connection for streamlined wiring
Product Designed Use:
- Designed to measure and monitor AC and DC current in industrial control systems
- Used to convert measured current into configurable analogue current or voltage output signals
- Used for overcurrent or undercurrent limit monitoring with relay alarm output
- Suitable for DIN rail panel installations in automation and process monitoring applications