KEY FEATURES
Alarm memory – identifies source unit within interconnecting network
Reduced energy consumption – lower lifetime running costs
Dust compensation and bug screen – reduces nuisance alarms
Combined Test/HushTM button allows regular testing of alarm function and can be used to temporarily silence nuisance alarms
Auto reset after activation
Tamper-resistant locking device prevents unauthorised removal without the use of a tool
Mains operation – Built-in rechargeable Lithium back-up tamper-proof battery
WHERE TO USE
Optical alarms are for use in escape or circulation routes and in areas where there is a danger of ignition of furniture and surroundings by cigarettes producing slow, smouldering fires. This mains-powered unit should be installed by a qualified electrician and can be used throughout the home, except in the kitchen where a Firex Heat Alarm is recommended. These alarms comply with UK Building Regulations for new housing and associated standards (Grade D BS 5839, Part 6).
GENERAL FEATURES
Power Supply 230V mains-powered with rechargeable Lithium battery back-up
Temperature Range 0ºC to + 40ºC
Humidity Range Up to 93% Relative Humidity (RH) non-condensing
Storage and Transport -20ºC to +60ºC and 5–95% relative humidity (RH) non-condensing
Alarm Dimensions 127 x 127 x 39mm
Bracket Dimensions 133 x 133 x 6mm
Alarm Weight 242g
Warranty 6 years (including battery)
Approvals BSI certified to BS EN14604:2005
CE tested and certified
TECHNICAL SPECIFICATION
Sensor Optical: Circular lateral chamber with insect-resistant width, 9-slot entry portals
Chamber Size: 35mm outside diameter x 16mm depth approximate (external)
Detection Band: Infrared light wavelength
Button Test: Simulates the effect of smoke within the sensing chamber, checks electronics and sounder
Automatic Self-test: Circuitry is tested and unit beeps (chirps) if fault is detected
Supply Voltage: 230V AC, 50 Hz (nominal UK voltage)
Power Consumption: < 15mA
Connection: Push-in/snap-fit type connector with 150mm long flying leads (supplied)
Battery Back-up: Non user-replaceable 3 x 3V rechargeable Vanadium Pentoxide Lithium cells (VL2330)
Power-on Indicator: Continuous green LED
Alarm Sounder: Electronic piezo-electric sounder (T3 pattern sound - three pulses - space - three pulses) with soldered contacts
Sound Output: 85dB (A) minimum at 3 metres
Alarm Frequency: 3.2 kHz typical
Dust Protection: In-built foam gasket in rear of alarm to prevent dust ingress into rear of the alarm
Alarm Status: Red LED flashes approx once every five minutes = normal operation, Red LED flashes once a second = sensing smoke (sounder alarm sounds), Red LED flashes once every ten seconds = in hush condition (auto-reset after 15 minutes)
Interconnection: Up to 24 Firex and Kidde ‘Slick’ units (smoke, heat and CO) can be hardwire interconnected with optional control (see below)
Optional Controls: Wired Remote Test and Hush Unit (REMTH) allows test and hush of interlinked units
Optional Pattresses: SMK23RU also has integral switchable relay for operating remote devices or SMK4896 – Surface mounting base for added ease of installation
Fixing: Mounting bracket ring supplied with two ‘T’ slot fitting option, 57mm spacing to a maximum of 90mm for standard screw fittings on back boxes, Bracket has 50mm diameter central access hole for cabling
Plastics used: NORYL – Cover, main body and mounting bracket
Lead-Free Status: All Firex alarms are lead-free