System Sensor V4R2415ADA Speaker Strobe 15 Candela
The System Sensor V4R2415ADA Speaker Strobe 15 Candela is a legacy audible/visible fire alarm notification appliance from the System Sensor V400 Series. It combines an emergency voice speaker with a fixed 15-candela strobe for fire alarm voice evacuation applications.
The V4R2415ADA supports both 25V and 70.7V speaker circuits with selectable speaker power taps from ¼ to 2 watts. The speaker and strobe operate on separate circuits, allowing connection to compatible emergency voice and notification appliance circuits.
Product Functions
- Provides emergency voice notification
- Provides visible fire alarm notification
- Combines speaker and strobe functions
- Fixed 15-candela visual output
- Supports 25V speaker circuits
- Supports 70.7V speaker circuits
- Provides selectable speaker wattage
- Supports evacuation messages
- Supports emergency announcements
- Supports live emergency paging
- Supports prerecorded messages and tones
- Separate speaker and strobe circuits
- Designed for compatible voice evacuation systems
Emergency Voice Speaker
The V4R2415ADA incorporates a speaker designed for emergency voice communication and signaling.
Typical functions include evacuation instructions, emergency announcements, alert tones, prerecorded messages, and live emergency paging.
The published speaker frequency range is:
400–4,000 Hz
25V / 70.7V Audio Operation
The speaker supports:
25 VRMS
70.7 VRMS
This dual-voltage capability allows the appliance to operate with common distributed fire alarm voice evacuation systems.
Selectable Speaker Wattage
The V4R2415ADA provides selectable speaker power taps:
¼ W
½ W
1 W
2 W
The appropriate wattage can be selected according to required sound level, ambient noise, amplifier capacity, and emergency voice coverage.
15 Candela Strobe
The V4R2415ADA incorporates a fixed:
15 cd strobe
The visual portion operates from a compatible 24V notification appliance circuit.
Unlike multi-candela notification appliances, this model provides a fixed visual output.
Separate Speaker & Strobe Circuits
The speaker and strobe portions operate from independent circuits.
Speaker: Emergency voice/audio circuit
Strobe: 24V notification appliance circuit
This configuration allows the fire alarm system to manage emergency voice and visible notification according to the system design.
Electrical & Audio Information
Model: V4R2415ADA
Series: V400
Device Type: Speaker Strobe
Strobe Output: 15 cd
Strobe Voltage: 24V
Speaker Voltage: 25 / 70.7 VRMS
Speaker Taps: ¼ / ½ / 1 / 2 W
Speaker Frequency: 400–4,000 Hz
Notification Type: Audible / Visible
Product Status
The V4R2415ADA is a legacy System Sensor V400 Series notification appliance. For replacement applications, speaker voltage, wattage, strobe output, circuit voltage, and voice evacuation system compatibility should be verified.
V4R2415ADA Datasheet