RS-232 and USB ports connect to a serial-enabled or USB-enabled device for a variety of communication
options (cables are included). The RPO/ROO connector permits emergency shutdown or remote restart of
all connected equipment. By adding the optional RELAY-MS interface card (sold separately), a drycontact relay port can be programmed through the LCD to provide reliable communications to automation
and industrial components.
You can mount the 5P1550GR in just 1U of space in an EIA-standard 19-inch rack using the included 4-
post rail kit or an optional 2-post rail kit (RK2PA, sold separately). You can also use the included hardware
for wall mounting. The C14 inlet accepts a detachable power cord that connects to a compatible AC outlet.
Specifications:
UPS Type: Line-Interactive
INPUT
Input Phase: Single-Phase
Nominal Input Voltage(s) Supported: 200V AC; 208V AC; 220V AC; 230V AC; 240V AC
UPS Input Connection Type: C14 inlet
Plug Type: C14 inlet
OUTPUT
Output Capacity (VA): 1550
Output Capacity (kVA): 1.55
Output Capacity (Watts): 1100
Output Capacity (kW): 1.1
Power Factor: 0.71
Nominal Voltage Details: 200V, 208V, 220V, 230V, 240V
Frequency Compatibility: 50 / 60 Hz
Load Management Receptacles: Two switchable outlet load banks
Output AC Waveform (AC Mode): True Sine Wave
Output AC Waveform (Battery Mode): Pure Sine wave
Nominal Output Voltage(s) Supported: 200V; 208V; 220V; 230V; 240V
Output Receptacles: (6) C13
Individually Controllable Load Banks: Yes
BATTERY
Battery Type Valve Regulated Lead Acid (VRLA): 2 / 4
Runtime Full Load (min.): 4 min. (1100W)
Runtime Half Load (min.): 13 min. (550W)
Expandable Runtime: No
Internal UPS Replacement Battery: Cartridge
Battery Replacement Description: User replaceable batteries.
Battery Management: ABM technology (3-stage charging extends battery service life by 50% and provides advance warning for battery
replacement)
USER INTERFACE, ALERTS & CONTROLS
Front Panel LCD Display: LCD graphical display
Switches: RPO / ROO
Alarm Cancel Operation: Press ESC to silence the alarm
Audible Alarm: Audible alarm indicates utility failure, low-battery, overload, other UPS/Battery fault or remote shutdown conditions
LED Indicators: 3 status-indicating LEDs
SURGE / NOISE SUPPRESSION
UPS AC Suppression Joule Rating: 350
PHYSICAL
Primary Form Factor: Rackmount
Rack Height: 1U
Installation Form Factors Supported with Included Accessories: 4 post, 19 inch rackmount
Minimum Required Rack Depth (cm): 63.50
Minimum Required Rack Depth (inches): 25
Primary UPS Depth (mm): 554
Primary UPS Height (mm): 43
Primary UPS Width (mm): 442
Unit Dimensions (hwd / in.): 1.700 x 17.400 x 21.800
Unit Dimensions (hwd / cm): 4.32 x 44.20 x 55.37
Unit Dimensions (hwd / mm): 43.2 x 442 x 553.7
Unit Dimensions (in.): 1.7 x 17.4 x 21.8
Unit Weight (lbs.): 42.7
Unit Weight (kg): 19.37
ENVIRONMENTAL
Operating Temperature Range: 32° to 104°F (0° to 40°C)
Relative Humidity 0-90%: non-condensing 3 / 4
AC Mode Efficiency Rating (100% Load): 99
COMMUNICATIONS
Network Management Card: Network Card Optional
Communications Interface: RS-232; USB
FEATURES & SPECIFICATIONS
High Availability UPS Features Automatic Voltage Regulation (AVR); Hot swappable batteries
APPLICATIONS
UPS Applications High-End Desktop/Small Network