Description
The EST2 Fire Alarm System is modular in design allowing systems
to be easily configured to match installation requirements. With one
Signature Data Circuit (SDC) EST2 is capable of supporting 96 detectors and 94 modules and has two built in Notification Appliance
Circuits (NAC). The system supports the full line of Signature series
detectors and modules. EST2’s modular design means the system
easily expands to two SDCs and four NACs by adding a single 2-LCX
module increasing system capacity to 380 points/zones with four
built in Notification Appliance Circuits.
The EST2 provides an RS-232 port to facilitate computer, coder and
printer interfacing and an RS-485 communication port for supporting remote annunciation. Annunciation of system events are
displayed on a back lit LCD with enhanced diagnostic LEDs on the
front panel. There is space to add up to 48 additional points/zones
of software controlled LED annunciation and switch control on the
front panel. Both alpha-numeric LCD and annunciation LEDs are
available for remote annunciation and control with the GE Security
2-LSRA and SAN series of annunciators.
EST2 features Auto Programming through the front panel and
Custom Programming via PC laptop interface. The Auto Program
mode will identify all devices on the SDC and automatically assign
addresses to each device. Then the auto programming feature automatically links the proper response to the proper input, providing
real time savings during installation.
Standard Features
Supports all GE Security Signature devices
Autoprogramming of Signature data circuits
Class B or A Signature data circuit(s), 96 detectors and 94 modules per circuit
Two integral Class A or B notification appliance circuits
Alarm, trouble, and supervisory contacts
Prioritized status queues for alarm, supervisory, trouble and
monitor inputs
576 event history log
Enhanced sensitivity reports
Optional expander Signature data circuit
Designed and manufactured to ISO 9001 standards