Surge Diverter / Surge Arrester Testclass II / T2 / C/ for overvoltage protection of voltage spikes with wavefrom 8/20 micro seconds. Suitable for installation in distribution boards and load centres.
Sure arresters Class T2 are not suitable for protection from direct lighting strikes.Where direct lighting strikes can occur onto supplying overhead conducturs it is recommended to use Lighting arrester Testclass II / T2 / B.
![]()
SPECIFICATIONS:
Number of poles: 1
Arrester class: Testclass II (C) IEC61643-1+A1/EN61643-11
Max. continuous rating voltage Uc: 280V AC
Max. discharge current (8/20)Iimax: 40 kA
Nominal discharge current (8/20)In: 20 kA
Protection level Up (at in): 1400 V
Response time: < 25 ns
Charge at in: 0,57As
Specific energy at In: 5,7kJ/Ω
Thermal disconnection: Yes
Back up fuse: up to 125A
Short circuit withstand current: 50kAeff / 50hz
Temperature range: -40°c - +70°c
Degree of protection: IP40 (mounted)
Terminal cross section: 4 – 25mm²
Tightening torque: 2,4 – 3Nm
Dimensions [mm]: 17,5 x 45 x 80