| Range | ComPact |
|---|---|
| Range of product | ComPact NSX100...250 |
| Product or component type | Trip unit |
| Trip unit name | MicroLogic 4.2 |
| Trip unit technology | Electronic |
| Range compatibility | ComPact NSX100 ComPact NSX160 ComPact NSX250 |
| Device application | Distribution |
| Number of poles | 3P |
| Protected poles description | 3t |
| Neutral position | Left |
| Trip unit protection functions | LSoIR |
| Protection type | L : for overload protection (long time) So : for short time short-circuit protection with fixed delay I : for instantaneous short-circuit protection R : for earth-leakage protection |
| Trip unit rated current | 40 A at 40 °C |
| [Ue] rated operational voltage | 440 V AC 50/60 Hz |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Long-time pick-up adjustment type Ir (thermal protection) | Adjustable 9 settings |
|---|---|
| [Ir] long-time protection pick-up adjustment range | 18...40 A |
| Long-time protection delay adjustment type tr | Fixed |
| [tr] long-time protection delay adjustment range | 11 s at 7.2 x Ir 16 s at 6 x Ir 400 s at 1.5 x Ir |
| Thermal memory | 20 minutes before and after tripping |
| Short-time protection pick-up adjustment type Isd | Adjustable |
| [Isd] Short-time protection pick-up adjustment range | 1.5...10 x Ir |
| Short-time protection delay adjustment type tsd | Fixed |
| [tsd] Short-time protection delay adjustment range | 0.02 s |
| Instantaneous protection pick-up adjustment type Ii | Fixed |
| [Ii] instantaneous protection pick-up adjustment range | 600 A |
| Earth-leakage protection | Integrated |
| Earth-leakage protection class | Class A |
| Earth-leakage protection sensitity adjustment type IΔn | Adjustable |
| [IΔn] earth-leakage protection sensitivity adjustment range | 1 A 100 mA 300 mA 30 mA 5 A 500 mA 3 A |
| Earth-leakage protection specific mode | OFF using the IΔn rotary switch |
| Earth-leakage protection time delay adjustement type Δt | Adjustable |
| [Δt] Earth-leakage protection time delay adjustment range | 0 ms 500 ms 60 ms 1 s 150 ms |
| Zone selective interlocking ZSI | Without |
| Local signalling | Flashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload Color indicator (yellow) for residual current |