6-Channel Voltage & Current Data Logger with Voltage 0.01V-600V Current 1mA-400A


Introduction:

Features:

Specifications:

Specification Name

Parameters

Power Supply

Rechargeable lithium battery, DC 3.7V, 5200mAh

Display Mode

2.8-inch TFT color LCD screen; display area 58mm × 44mm

Input Channel

6 channels (3 current channels, 3 voltage channels)

Voltage

Range: 0.01V~600V
Resolution: 0.01V
Accuracy: ±1.5%rdg±5dgt

Current

Range: 1mA~400A
Resolution: 0.01A
Accuracy: ±1.5%rdg±5dgt

Active Power

Range: 0.01mW~240kW
Resolution: 0.01A
Accuracy: ±1.5%rdg±5dgt

Apparent Power

Range: 0.01mW~240kW
Resolution: 0.01A
Accuracy: ±1.5%rdg±5dgt

Power Factor

Range: -1.000~1.000
Resolution: 0.001
Accuracy: ±0.03

Frequency

Range: 45Hz~65Hz
Resolution: 0.01Hz
Accuracy: ±1.5%rdg±5dgt

Jaw Size

32mm × 42mm

Main Unit Size

170mm × 87mm × 48.5mm

Weight

Approx. 2.21kg (including accessories)

Storage Interval

Charge time adjustable from 1s to 99min

Battery Life

48 hours on a full charge

Recording Time 

(External Power Supply)

A 1-second interval allows for continuous recording for 50 hours.

A 10-second interval allows for continuous recording for 20 days.

A 1-minute interval allows for continuous recording for 125 days.

Data Storage

200,000 data sets (data will not be lost during power outages or battery replacements); each data set records data from 6 channels simultaneously.

Communication Interface

TYPE-C interface

Download Speed

2MB/Min

Host Computer System 

Requirements

2000/XP/Vista

Power Frequency

50/60Hz

Line Voltage

Tested on AC600V and below lines

Battery Capacity

Five-segment battery indicator. Zero bars indicate battery voltage <3.3V; please charge promptly.

Rated Current

Approximately 100mA with backlight off; maximum 170mA with backlight on.

Operating Temperature and 

Humidity

- 20℃~50℃; below 80%RH; (1% error applies below -10℃ or above 40℃)

Storage Temperature and 

Humidity

- 10℃~60℃; below 70%RH

Insulation Resistance

100MΩ or greater, 1000V

Compliance with Safety 

Regulations

IEC1010-1, IEC1010-2-032, Pollution Degree 2, CAT Ⅲ (600V), IEC61326 (EMC standard)

Accessories

Main unit (1 PC)
Current transformer
Voltage input lines
Data cable (1 PC)
Power adapter (1 PC)
Tool bag (1 PC)