| Device Application | Distribution |
|---|---|
| Sherry | Acti 9 |
| Product Name | Acti9 iC60 |
| Product or Component Type | Miniature circuit breaker |
| Product Group | IC60N |
| Definition of the Pole | 2P |
| number of protected poles | 2 |
| [In] nominal current | 6 A |
| Network Type | AC DC |
| opening unit technology | Thermal Magnetic |
| slope code | C |
| cutting capacity | 36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2 20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2 6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2 10 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2 6000 A Icn at 400 V AC 50/60 Hz conforming to EN/IEC 60898-1 |
| usage category | Category A conforming to EN/IEC 60947-2 |
| suitability for insulation | Yes, compliant with EN/IEC 60898-1. Yes, compliant with EN/IEC 60947-2. |
| Standards | EN/IEC 60947-2 EN/IEC 60898-1 |
| Network Frequency | 50/60 Hz |
|---|---|
| magnetic field limit | 8 x In +/- 20% |
| [Ics] nominal service interruption capacity | 27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz 15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz 7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz 4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz 10 kA 100 % conforming to EN/IEC 60947-2 - <= 125 V DC |
| limiting class | Compliant with EN/IEC 60898-1 |
| [Ui] nominal insulation voltage | 500 V AC 50/60 Hz conforming to EN/IEC 60947-2 |
| [Uimp] nominal impulse withstand voltage | Suitable for 6 kV EN/IEC 60947-2 |
| contact position indicator | Yes |
| Control type | Transition |
| On-device signaling | On indicator |
| Mounting Type | Still |
| Assembly Support | DIN rail |
| comb busbar distribution block compatibility | Top or bottom: YES |
| 9 mm screw pitch | 4 |
| Height | 85 mm |
| Width | 36 mm |
| Depth | 78.5 mm |
| Product Weight | 0.25 kg |
| colour | White |
| Mechanical durability | 20,000 cycles |
| electrical resistance | 10,000 cycles |
| connections - terminals | Single terminal (top or bottom) 1…25 mm² rigid Single terminal (top or bottom) 1…16 mm² flexible |
| wire stripping length | 14 mm for top or bottom connection |
| tightening torque | 2 Nm above or below |
| soil leakage protection | Separate block |
| IP protection rating | IP20 conforming to IEC 60529 |
|---|---|
| pollution level | Compliant with EN/IEC 60947-2 |
| overvoltage category | IV |
| tropical climate | Compliant with IEC 60068-1 |
| relative humidity | 95% at 55°C |
| Working Height | 0...2000 m |
| Nominal Operating Ambient Temperature | -35…70 °C |
| Storage Environment Conditions | -40…85 °C |
| Unit Type of Package 1 | PCE |
|---|---|
| Number of units in the package | 1 |
| Package 1 Height | 7,500 cm |
| Package 1 Width | 3,700 cm |
| Package 1 Length | 9,500 cm |
| Package weight (Lbs) | 213,000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 8,500 cm |
| Package 2 Width | 10,000 cm |
| Package 2 Length | 22,500 cm |
| Package 2 Weight | 1,346 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 66 |
| Package 3 Height | 30,000 cm |
| Package 3 Width | 30,000 cm |
| Package 3 Length | 40,000 cm |
| Package 3 Weight | 15,293 kg |
| Warranty (in months) | 18 |
|---|