XALD213 GREEN FLUSH/RED FLUSH PUSHBUTTON Ø22 SCHNEIDER / NEW FACTORY SEALED

Main
range of product
Harmony XALD
product or component type
Complete control station
device short name
XALD
product destination
For XB5 Ø 22 mm control and signalling units
control station application
Start-Stop function
colour of base of enclosure
Light grey RAL 7035
colour of cover
Dark grey RAL 7016
material
Polycarbonate
operator profile
2 flush push-buttons
operators description
Green ''I'' 1 NO - red ''O'' 1 NC
control station composition
1 flush push-button green 1 NO I marking
1 flush push-button red 1 NC O marking
marking location
Marking on push-button
contact operation
Slow-break
Complementary
cable entry
2 knock-outs for cable entry, clamping capacity: 14 mm
2 knock-outs for Pg 13 cable gland and ISO M20, clamping capacity: 12 mm
product weight
0.51 lb(US) (0.233 kg)
resistance to high pressure washer
1015.26 psi (7000000 Pa) at 131 °F (55 °C), distance: 0.1 m
colour of marking
Black marking when white caps
White marking when green, red or black caps
positive opening
With conforming to EN/IEC 60947-5-1 appendix K
operating travel
0.06 in (1.5 mm) (NC changing electrical state)
0.1 in (2.6 mm) (NO changing electrical state)
0.17 in (4.3 mm) (total travel)
operating force
3.5 N (NC changing electrical state)
3.8 N (NO changing electrical state)
mechanical durability
10000000 cycles
connections - terminals
Screw clamp terminals: <= 2 x 1.5 mm² with cable end conforming to EN/IEC 60947-1
Screw clamp terminals: >= 1 x 0.22 mm² without cable end conforming to EN/IEC 60947-1
tightening torque
7.08...10.62 lbf.in (0.8...1.2 N.m) conforming to EN/IEC 60947-1
shape of screw head
Cross, Philips no 1
Cross, pozidriv No 1
Slotted, flat Ø 4 mm
Slotted, flat Ø 5.5 mm
contacts material
Silver alloy (Ag/Ni)
short-circuit protection
10 A by gG cartridge fuse conforming to EN/IEC 60947-5-1
[Ith] conventional free air thermal current
10 A conforming to EN/IEC 60947-5-1
[Ui] rated insulation voltage
600 V (degree of pollution: 3) conforming to EN/IEC 60947-1
[Uimp] rated impulse withstand voltage
6 kV conforming to EN/IEC 60947-1
[Ie] rated operational current
AC-15, A600: Ue = 120 V Ie = 6 A conforming to EN/IEC 60947-5-1
AC-15, A600: Ue = 240 V Ie = 3 A conforming to EN/IEC 60947-5-1
AC-15, A600: Ue = 600 V Ie = 1.2 A conforming to EN/IEC 60947-5-1
DC-13, Q600: Ue = 125 V Ie = 0.55 A conforming to EN/IEC 60947-5-1
DC-13, Q600: Ue = 250 V Ie = 0.27 A conforming to EN/IEC 60947-5-1
DC-13, Q600: Ue = 600 V Ie = 0.1 A conforming to EN/IEC 60947-5-1
electrical durability
1000000 cycles AC-15, 2 A at 230 V, operating rate: <= 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles AC-15, 3 A at 120 V, operating rate: <= 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles AC-15, 4 A at 24 V, operating rate: <= 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles DC-13, 0.2 A at 110 V, operating rate: <= 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
1000000 cycles DC-13, 0.5 A at 24 V, operating rate: <= 3600 cyc/h, load factor: 0.5 conforming to EN/IEC 60947-5-1 appendix C
electrical reliability
Λ < 10exp(-6) at 5 V, 1 mA conforming to EN/IEC 60947-5-4
Λ < 10exp(-8) at 17 V, 5 mA conforming to EN/IEC 60947-5-4
Environment
protective treatment
TH
ambient air temperature for storage
-40...158 °F (-40...70 °C)
ambient air temperature for operation
-40...158 °F (-40...70 °C)
overvoltage category
Class II conforming to IEC 60536
IP degree of protection
IP69
IP67
IP66 conforming to IEC 60529
IP69K
NEMA degree of protection
NEMA 13
NEMA 4X
IK degree of protection
IK03 conforming to EN 50102
standards
EN/IEC 60947-1
EN/IEC 60947-5-1
EN/IEC 60947-5-4
EN/IEC 60947-5-5
JIS C 4520
UL 508
CSA C22.2 No 14
vibration resistance
5 gn (12...500 Hz) conforming to IEC 60068-2-6
shock resistance
30 gn (duration = 18 ms) half sine wave acceleration conforming to IEC 60068-2-27
50 gn (duration = 11 ms) half sine wave acceleration conforming to IEC 60068-2-27